Theory of Operation;

 

The  TUTHILL  meters  LPG  metering  system  combines  an 
oval  gear  positive  displacement  meter,  differential  valve, 
strainer and vapor eliminator in one assembly.  The differen-
tial  valve  incorporates  a  diaphragm  type  construction  with 
the piston moving away from its seat when at least 15 PSI 
pressure  (above  product  vapor  pressure)  is  maintained  at 
the  meter  outlet.    The  differential  valve  assures  measure-
ment accuracy by requiring pump operation for delivery, by 
requiring adequate back pressure to prevent product vapori-
zation  during  measurement  and  by  requiring  blockage  of 
flow  when the vapor eliminator release valve is open.  The 
strainer prevents foreign particulate from entering and dam-
aging the meter.  The meters close tolerance machine con-
struction  and  no  metal  to  metal  contact  provides  accurate 
liquid measurement. 

Installation, Flow Meter: 

Install  the  meter  assembly  to  a  secure  base  using  the  bolt 
holes on the “feet” of the meter assembly base.  Make inlet 
and outlet connections at the flanged surfaces on the meter-
and differential valve, respectively.  

Leave a minimum of 12 

inches between he strainer flange and any obstacle for 
servicing the strainer. 

I

nstallation, Vent Line:

 

The vent line from the meter’s vapor vent to the vapor space 
on the supply tank should be a minimum of 1/2” inside diam-
eter  tube  or  pipe.    A  shutoff  valve  must  be  installed  in  the 
vapor vent line to allow removal of the strainer or service on 
the meter.  The vapor release vent line must be returned to 
the vapor space of the supply tank and normally should not 
be made common with the other vapor return lines or pump 
by-pass lines.   

When  properly  installed,  this  line  must  permit  free  flow  in 
either direction.  If the vent line is closed the meter will not 
function,  as  the  differential  valve  will  not  open.    These  in-
structions  must  be  followed  to  maintain  proper  function  of 
the differential valve. 

Support: 

Prevent  pipe  strain  or  stress  from  occurring  when  making 
connections  to  meter  or  accessories  and  during  repairs. 
Pipe  strain  and  stress  occurs  when  the  pipes  are  not  sup-
ported or are not aligned correctly to the meter.  The weight 
of  the  pipes  must  always  be  supported  independent  of  the 
meter.  This meter and accessories can easily be removed 
without  affecting  the  pipes  or  the  pipe  alignment.    Never 
leave any of the pipes hinging. 

Storage: 

If  the  meter  is  used  for  seasonal  work,  at  the  end  of  each 
season the meter should be removed from the system and 
thoroughly  flushed  with  a  compatible  liquid.    This  includes 
removing the drain on the front and rear covers.  Then flush 
the product from the front and rear covers.  If flushing with 
water  is  preferred,  extra  care  should  be  taken  to  drain  the 
meter  completely  and  to  dry  all  internal  parts.      Immediate 
refilling with a compatible liquid (or oil misting) is essential to 
prevent corrosion as well as ice damage to parts from mois-
ture that was overlooked after flushing and drying. 

Installation  &  Operation  continued 

Typical Installation Diagram 

mdi - Manufacturers Distributor Inc. | Phone: (813) 241 - 4900 | Fax: (813) 571 - 0422 | www.FillRitePumpSales.com | [email protected]

Summary of Contents for TS20A

Page 1: ...anual TS20A LPG Anodized Aluminum Electronic Bulk Tank Meter for LPG with 2 Thermo Wells TS20A LPG Models mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillRitePumpSales co...

Page 2: ...ainer 11 Vapor Eliminator 11 Differential Valve 11 Parts List Inlet Check Valve 12 Vapor Eliminator 13 Differential Valve 14 Security Valve 15 Meter Strainer 16 SCL Pulser Assembly 18 Meter calibratio...

Page 3: ...epartment or oth er appropriate authorities In the event of a small contained gas leak Isolate and stop the leak Prevent accidental ignition Prevent entrance of gas into other portions of the build in...

Page 4: ...e connecting pipe as the means of support It is recommended that a strainer be installed upstream of each meter to prevent damage from foreign matter such as weld slag pipe scale etc A means to calibr...

Page 5: ...omplished in the following manner Throttle the meter inlet valve and allow the meter and pip ing to fill slowly by gravity Crack open the outlet valve and start the pump then slowly open the inlet val...

Page 6: ...es also application specific Do NOT transfer to another flow meter without consulting with Tuthill 2 Use 4 conductor shielded cable 3 Terminate shields at receiving instrument register 4 Move W1 shunt...

Page 7: ...ued EL0304 to MCR 05 Register Pulser cable plugs into J1 on EL0304 Signal output cable is connected to TB1 mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillRitePumpSales c...

Page 8: ...e vapor release vent line must be returned to the vapor space of the supply tank and normally should not be made common with the other vapor return lines or pump by pass lines When properly installed...

Page 9: ...atched in any way If it is undamaged it can be re used Examine all fasteners make sure fasteners are not bent rusted or have pulled or burred threads The threads should all appear evenly placed If the...

Page 10: ...s and blemishes If the dam age is more than superficial replace the body Inspect the post and post plate Replace if there is any wear Inspect the O ring seals and replace any damaged or brittle seals...

Page 11: ...ar or damage Replace worn or brittle seals Reassemble the valve and install in the strainer hous ing This valve is optional and will not retrofit into strain er housing not originally supplied with th...

Page 12: ...m Seal Kit Item Qty Description 1 1 Body 2 Backcheck Finish Coated 2 1 Piston 2 Backcheck Anodized 3 1 O Ring Buna 4 1 Screw 10 32 X 3 8 SHCS 5 1 Poppet 2 Backcheck 6 1 Spring 2 Backcheck LPG VP1950 B...

Page 13: ...tion 9 1 Mounting Block Reed 10 2 Ring Retaining 11 1 Relief Valve Hydrostatic 12 1 Plug Air Elim LPG 13 1 Plug Limited Bleed Air Elim LPG 14 1 Cover Air Eliminator LPG Anodized 15 1 Cover Blind Air E...

Page 14: ...er 2 Differential 7 3 Screw 10 32 X 5 8 SHCS SS 8 12 Screw 5 16 18 X 1 1 4 ALPLHHCS Grade 5 9 1 Shaft Guide 10 1 O Ring Buna 11 1 O Ring Buna 12 12 Washer Split Locking 5 16 13 1 Spring 2 Differential...

Page 15: ...6 1 Tubing Assembly TS20A Sec Vlv AE LPG 7 1 Tubing Assembly TS20A Sec Vlv Meter LPG 8 1 Tubing Assembly TS20A Sec Vlv Diff LPG 9 1 Screw 5 16 18 X 1 25 SHCS SS 10 2 Washer Split Locking 1 4 Included...

Page 16: ...16 Exploded View mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillRitePumpSales com Sales FillRitePumpSales com...

Page 17: ...non functioning pump Differential valve not open or not functioning Replace valve Meter frozen Clean meter internals and inspect for damage Vapor vent line valve shut or obstruction in vapor vent lin...

Page 18: ...e the pulse output A decrease in pulse output will increase the volume in a prover vessel If in the plus position an in crease in the S3 and S4 will increase the pulse out put An increase in pulse out...

Page 19: ...ution The opposite is true if S2 is already in the minus position at the beginning of calibration Finally Re seal the flow meter Enter date and correction on the permanent flow meter record As long as...

Page 20: ...20 NOTES DC001337 000 Rev 1 mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillRitePumpSales com Sales FillRitePumpSales com...

Page 21: ...0A GLP Medidor de tanque a granel electr nico de aluminio anodizado para GLP con 2 pozos termom tricos Modelos TS20A GLP mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillR...

Page 22: ...liminador de vapor 11 V lvula diferencial 11 Lista de piezas V lvula de retenci n de entrada 12 Eliminador de vapor 13 V lvula diferencial 14 V lvula de seguridad 15 Medidor y filtro 16 SCL conjunto d...

Page 23: ...fuga Evite inflamaciones accidentales Evite que el gas ingrese a otras partes del edificio Tenga presente que el GLP es m s pesado que el aire y se ir a los niveles inferiores Evacue a toda las person...

Page 24: ...r de una manera tal que permanezca lleno de l quido en todo momento Instale las bridas de acoplamiento Apriete a una posici n que permita que medidor se emperne a las bridas de acoplamiento sin tensi...

Page 25: ...en aire o vapor Esto se puede lograr de la siguiente manera Regule la v lvula de entrada del medidor y deje que este y las tuber as se llenen lentamente por gravedad Abra ligeramente la v lvula de sa...

Page 26: ...fiera a otro medidor de flujo sin consultarlo con Tuthill 2 Use un cable blindado con 4 conductores 3 Termine los blindajes en el instrumento receptor registrador 4 Mueva el derivador de corriente W1...

Page 27: ...CANAL B NO SE USA NO SE USA SE AL A SE AL B AMP EL0304 a registrador MCR 05 El cable del generador de impulsos se conecta en J1 en EL0304 El cable de salida de se al se conecta en TB1 7 mdi Manufactur...

Page 28: ...ntilaci n de vapor del medidor hacia el espacio para el vapor en el tanque de suministro debe ser un tubo o una tuber a con un di metro interior de al menos 13 mm Se debe instalar una v lvula de cierr...

Page 29: ...as con un compuesto antiagarrotamiento Retiro de los sellos de la brida Cuando retire el conjunto de brida siempre retire cuidadosamente el sello de la junta t rica Aseg rese de que la superficie de l...

Page 30: ...y la placa de bornes 3 Limpie todas las superficies con un cepillo o una tela de esmeril fina grano 200 Inspeccione y repare la v lvula de retenci n de entrada si cuenta con esta opci n Inspeccione s...

Page 31: ...asa del eliminador de vapor Retire la cubierta de la carcasa del eliminador de vapor Retire el conjunto de v lvula y flotador de la cubierta para su inspecci n Inspeccione si el flotador est da ado o...

Page 32: ...cm Conjunto de antirreflujo VP1950 N de elemento Cant Descripci n 1 1 Cuerpo antirreflujo de 5 1 cm acabado con revestimiento 2 1 Cuerpo antirreflujo de 5 1 cm anodizado 3 1 Junta t rica Buna 4 1 Torn...

Page 33: ...o de retenci n 11 1 V lvula de alivio hidrost tica 12 1 Tap n eliminador de aire GLP 13 1 Tap n purga limitada eliminador de aire GLP 14 1 Cubierta eliminador de aire GLP anodizado 15 1 Cubierta ciega...

Page 34: ...l de 5 1 cm 7 3 Tornillo de cabeza hueca 10 32 x 5 8 acero inoxidable 8 12 Tornillo de cabeza hexagonal 5 16 18 x 1 1 4 ALPL grado 5 9 1 Eje gu a 10 1 Junta t rica Buna 11 1 Junta t rica Buna 12 12 Ar...

Page 35: ...x 1 4 NPT macho GLP 6 1 Conjunto de tubos TS20A v lvula de seguridad eliminador de aire GLP 7 1 Conjunto de tubos TS20A v lvula de seguridad medidor GLP 8 1 Conjunto de tubos TS20A v lvula de segurida...

Page 36: ...Vista despiezada 16 mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillRitePumpSales com Sales FillRitePumpSales com...

Page 37: ...o Limpie las piezas internas del medidor e inspeccione si hay da os La v lvula de la tuber a de ventilaci n de vapor est cerrada o hay obstrucci n en dicha tuber a Abra la v lvula o retire la obstrucc...

Page 38: ...n estar en su posici n definida S2 Se usa en conjunto con S3 y S4 Si est en la posici n menos un aumento en la configuraci n del interruptor S3 y S4 disminuir la salida de pulsos Una disminuci n en la...

Page 39: ...ocar en la posici n menos y S3 y S4 se deben girar a la posici n adecuada para obtener el cambio deseado en la resoluci n de pulsos Lo opuesto se aplica si S2 ya se encuentra en la posici n menos al c...

Page 40: ...20 NOTAS DC001337 000 Rev 1 mdi Manufacturers Distributor Inc Phone 813 241 4900 Fax 813 571 0422 www FillRitePumpSales com Sales FillRitePumpSales com...

Reviews: