General Description  

 

The TWINFLEX

®

pro Expansion Card allows a 4 zone TWINFLEX

®

pro panel to be converted to an 8 zone panel. 

The card is only compatible with the 4-zone TWINFLEX

®

pro panel. It is not compatible with the 2-zone 

TWINFLEX

®

pro panel or with any earlier TWINFLEX

®

 or TWINFLEX

®

 Checkpoint Plus panels. 

 

 
Installation 

 

The panel must be completely powered down before this card is fitted. 
 

1.  Remove the right hand cover moulding from the unit by unscrewing the two fixing screws. 

 

2.  Next disconnect the battery by removing one of the push on battery leads at the battery. Always disconnect 

the battery first before removing the mains power to the panel. 

 

NOTE: Do not disconnect the battery by removing the wires from the terminals on the CIE circuit 
board. Doing this may allow the batteries to short circuit. 
 

3.  Remove mains power from the panel by removing the fuse in the fused spur that supplies the panel or 

switching off the circuit breaker. At this stage there should be no LEDs lit on the panel and the display 
should be blank. 
 

4.  Disconnect all cabling from the CIE terminals. Make sure these cables are suitably labelled to facilitate 

correct re-connection after fitting the Expansion Card. 
 

5.  Unscrew the two fixing screws that secure the left hand CIE assembly, then slide the assembly to the left 

and flip the assembly over clockwise. 

 

 

 

Summary of Contents for Twinflex pro 505-0006

Page 1: ...g one of the push on battery leads at the battery Always disconnect the battery first before removing the mains power to the panel NOTE Do not disconnect the battery by removing the wires from the terminals on the CIE circuit board Doing this may allow the batteries to short circuit 3 Remove mains power from the panel by removing the fuse in the fused spur that supplies the panel or switching off ...

Page 2: ... will only fit one way 8 Flip the left hand CIE assembly back over anti clockwise and plug the other end of the ribbon cable assembly into the connector marked expansion connector on the CIE PCB again this will only fit one way 9 Slide the CIE assembly onto the base moulding ensure that the CIE assembly moulding engages into the clips on the base moulding and that all cables ends are accessible fo...

Page 3: ...directly to the Expansion Card For details of how to connect the zone cables see the TWINFLEX pro Engineering Commissioning Manual 12 Re connect the mains power to the panel before connecting the battery by refitting the fuse in the fused spur that supplies the panel or switching on the circuit breaker 13 Now re connect the battery 14 Refit the right hand cover moulding ensure the moulding engages...

Page 4: ...te enable switch back to off when finished Technical Data For specifications of the TWINFLEX pro Panel when upgraded to 8 Zones please see the TWINFLEX pro Engineering Commissioning Manual Technical Support Contact your supplier for technical support on this product Due to the complexity and inherent importance of a life risk type system training on this equipment is essential and commissioning sh...

Reviews: