PROGRAMMING GUIDE
Ethernet Module Programming Guide
Page 19 of 20
P/N: 06-388-1
Rev 0, 09/08
9 – If changes were made, click
Apply Settings
.
Preloaded Factory Settings
The following settings are preloaded into Ethernet Module by Fike prior to shipment from the Factory.
Network / IP Configuration
Channel 1 / Serial Settings
•
IP Address – Customer Provided;
factory defaulted to 10.10.10.10
•
Subnet Mask – Customer Provided;
factory defaulted to 255.255.255.0
•
Default Gateway – Customer Provided;
factor defaulted to 10.10.10.1
Server / Advanced
Channel 1 / Disable Serial Port – Off
Port Settings / Protocol – RS232
Port Settings / Baud Rate – 9600
Port Settings / Data Bits – 8
Port Settings / Flow Control – None
Port Settings / Parity – None
Port Settings / Stop Bits – 1
Pack Control / Enable Packing – Off
Flush Mode / Flush Input Buffer – all set to NO
Flush Mode / Flush Output Buffer – all set to NO
Channel 1 / Connection
•
ARP Cache Timeout – 600 seconds
•
TCP Keepalive – 45 seconds
•
Monitor Mode @ Bootup – Enable
•
CPU Performance Mode – Regular
•
HTTP Server Port – 80
•
MTU Size - 1400
•
Connect Protocol / Protocol – UDP
•
Datagram Mode / Datagram Type – 00
•
Datagram Mode / Accept Incoming - Yes