FML-E3/FSL-E3 Product Installation Instructions —
P/N LS10178-002FK-E:A 03/04/2021
All components should be located per the following requirements:
•
Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that could
cause condensation.
•
Equipment must be securely mounted on rigid, permanent walls.
•
Operating temperature shall not exceed the range of 32° to 120° F (0 to 49° C).
•
Operating humidity not to exceed 93% non-condensing at 90° F (32° C).
•
All sub-assemblies and components are to be located in compliance with the local, the national codes and the
manufacturer’s recommendations.
•
All installation field wiring shall be in compliance with the local code, the national code and the manufacturer’s
recommendations.
•
Use the Architects and Engineering Specifications for detailed information on your Facility’s Configuration.
3.1 FIK-FML/FIK-FSL Installation
1. Remove the unit from its static-shield bag, observing proper static protection measures.
2. Visually inspect the unit for damage.
If any components are damaged, notify the shipping carrier immediately. Report missing components to the Silent Knight
Customer Service.
3. Use the Hardware Kit provided with the unit.
4. Plug the Fiber Module #1 into P6 of the FIK-NVCM or FIK-NIC circuit as shown in Location 1 in Figure 3 and Figure 4.
5. To connect the Fiber Module # 1 to the FIK-NVCM or FIK-NIC, insert and secure three screws (#4-40 x 1/4”) as shown in
Location 2 in Figure 3 and Figure 4.
6. Plug the Fiber Module #1 into P5 of the FIK-NVCM or FIK-NIC circuit as shown in Location 3 in Figure 3 and Figure 4.
7. To connect the Fiber Module #1 to the FIK-NVCM or FIK-NIC, insert and secure three screws (#4-40 x 1/4”) as shown in
Location 4 in Figure 3 and Figure 4.
!
CAUTION: STATIC SENSITIVE EQUIPMENT:
THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY HANDLED.
TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT WHICH MIGHT
NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.
DISCONNECT ALL POWER:
REMOVE ALL SOURCES OF POWER BEFORE YOU SERVICE, REMOVE OR INSTALL ANY UNITS.
NOTE 1:
FIBER MODULES:FIK-FSL AND FIK-FML
INSTALL A MAXIMUM OF TWO BOARDS PER INSTALLATION.THE FIBER MODULES CAN BE COMBINED.
Figure 3 illustrates the FIK-FML/FIK-FSL installed to the
FIK-NIC.
Figure 3 FIK-FML Installation
Figure 4 illustrates the FIK-FML/FIK-FSL installed to the
FIK-NVCM.
Figure 4 FIK-FSL Installation
FIK
-NI
C
FIK
-FM
L
FIK
-FS
L
FIK
-FM
L
FIK
-FS
L
FIK
-FM
L
FIK
-FS
L
FIK
-NV
CM
FIK
-FM
L
FIK
-FS
L
FIK
-FM
L
FIK
-FS
L