Fike FIK-5496 Installation & Operation Manual Download Page 2

2

FIK-5496 Manual — 

P/N LS10253-001FK-E:A  03/02/2021

Fire Alarm & Emergency Communication System Limitations

While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!

An automatic fire alarm system

—typically made up of smoke 

detectors, heat detectors, manual pull stations, audible warning 
devices, and a fire alarm control panel (FACP) with remote 
notification capability—can provide early warning of a developing fire. 
Such a system, however, does not assure protection against property 
damage or loss of life resulting from a fire. 

An emergency communication system

—typically made up of an 

automatic fire alarm system (as described above) and a life safety 
communication system that may include an autonomous control unit 
(ACU), local operating console (LOC), voice communication, and 
other various interoperable communication methods—can broadcast 
a mass notification message. Such a system, however, does not 
assure protection against property damage or loss of life resulting 
from a fire or life safety event. 
The Manufacturer recommends that smoke and/or heat detectors be 
located throughout a protected premises following the 
recommendations of the current edition of the National Fire Protection 
Association Standard 72 (NFPA 72), manufacturer's 
recommendations, State and local codes, and the recommendations 
contained in the Guide for Proper Use of System Smoke Detectors, 
which is made available at no charge to all installing dealers. This 
document can be found at http://www.systemsensor.com/appguides/. 
A study by the Federal Emergency Management Agency (an agency 
of the United States government) indicated that smoke detectors may 
not go off in as many as 35% of all fires. While fire alarm systems are 
designed to provide early warning against fire, they do not guarantee 
warning or protection against fire. A fire alarm system may not 
provide timely or adequate warning, or simply may not function, for a 
variety of reasons: 

Smoke detectors

 may not sense fire where smoke cannot reach the 

detectors such as in chimneys, in or behind walls, on roofs, or on the 
other side of closed doors. Smoke detectors also may not sense a fire 
on another level or floor of a building. A second-floor detector, for 
example, may not sense a first-floor or basement fire. 

Particles of combustion or “smoke”

 from a developing fire may not 

reach the sensing chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, chimneys, 
even wet or humid areas may inhibit particle or smoke flow. 

Smoke particles may become “cold,” stratify, and not reach the 
ceiling or upper walls where detectors are located. 

Smoke particles may be blown away from detectors by air outlets, 
such as air conditioning vents. 

Smoke particles may be drawn into air returns before reaching the 
detector. 

The amount of “smoke” present may be insufficient to alarm smoke 
detectors. Smoke detectors are designed to alarm at various levels of 
smoke density. If such density levels are not created by a developing 
fire at the location of detectors, the detectors will not go into alarm. 
Smoke detectors, even when working properly, have sensing 
limitations. Detectors that have photoelectronic sensing chambers 
tend to detect smoldering fires better than flaming fires, which have 
little visible smoke. Detectors that have ionizing-type sensing 
chambers tend to detect fast-flaming fires better than smoldering 
fires. Because fires develop in different ways and are often 
unpredictable in their growth, neither type of detector is necessarily 
best and a given type of detector may not provide adequate warning 
of a fire. 
Smoke detectors cannot be expected to provide adequate warning of 
fires caused by arson, children playing with matches (especially in 
bedrooms), smoking in bed, and violent explosions (caused by 
escaping gas, improper storage of flammable materials, etc.). 

Heat detectors

 do not sense particles of combustion and alarm only 

when heat on their sensors increases at a predetermined rate or 
reaches a predetermined level. Rate-of-rise heat detectors may be 
subject to reduced sensitivity over time. For this reason, the rate-of-
rise feature of each detector should be tested at least once per year 
by a qualified fire protection specialist. Heat detectors are designed to 
protect property, not life. 

IMPORTANT! Smoke detectors

 must be installed in the same room 

as the control panel and in rooms used by the system for the 
connection of alarm transmission wiring, communications, signaling, 
and/or power. If detectors are not so located, a developing fire may 
damage the alarm system, compromising its ability to report a fire. 

Audible warning devices such as bells, horns, strobes, speakers 
and displays

 may not alert people if these devices are located on the 

other side of closed or partly open doors or are located on another 
floor of a building. Any warning device may fail to alert people with a 
disability or those who have recently consumed drugs, alcohol, or 
medication. Please note that:

An emergency communication system may take priority over a fire 
alarm system in the event of a life safety emergency.

Voice messaging systems must be designed to meet intelligibility 
requirements as defined by NFPA, local codes, and Authorities 
Having Jurisdiction (AHJ).

Language and instructional requirements must be clearly dissemi-
nated on any local displays.

Strobes can, under certain circumstances, cause seizures in peo-
ple with conditions such as epilepsy. 

Studies have shown that certain people, even when they hear a 
fire alarm signal, do not respond to or comprehend the meaning of 
the signal. Audible devices, such as horns and bells, can have dif-
ferent tonal patterns and frequencies. It is the property owner's 
responsibility to conduct fire drills and other training exercises to 
make people aware of fire alarm signals and instruct them on the 
proper reaction to alarm signals. 

In rare instances, the sounding of a warning device can cause 
temporary or permanent hearing loss. 

A life safety system

 will not operate without any electrical power. If 

AC power fails, the system will operate from standby batteries only for 
a specified time and only if the batteries have been properly 
maintained and replaced regularly. 

Equipment used in the system

 may not be technically compatible 

with the control panel. It is essential to use only equipment listed for 
service with your control panel. 

Alarm Signaling Communications:

IP connections

 rely on available bandwidth, which could be lim-

ited if the network is shared by multiple users or if ISP policies 
impose restrictions on the amount of data transmitted. Service 
packages must be carefully chosen to ensure that alarm signals 
will always have available bandwidth. Outages by the ISP for 
maintenance and upgrades may also inhibit alarm signals. For 
added protection, a backup cellular connection is recommended.

Cellular connections

 rely on a strong signal. Signal strength can 

be adversely affected by the network coverage of the cellular car-
rier, objects and structural barriers at the installation location. Uti-
lize a cellular carrier that has reliable network coverage where the 
alarm system is installed. For added protection, utilize an external 
antenna to boost the signal.

Telephone lines

 needed to transmit alarm signals from a premise 

to a central monitoring station may be out of service or temporarily 
disabled. For added protection against telephone line failure, 
backup alarm signaling connections are recommended.

The most common cause

 of life safety system malfunction is 

inadequate maintenance. To keep the entire life safety system in 
excellent working order, ongoing maintenance is required per the 
manufacturer's recommendations, and UL and NFPA standards. At a 
minimum, the requirements of NFPA 72 shall be followed. 
Environments with large amounts of dust, dirt, or high air velocity 
require more frequent maintenance. A maintenance agreement 
should be arranged through the local manufacturer's representative. 
Maintenance should be scheduled as required by National and/or 
local fire codes and should be performed by authorized professional 
life safety system installers only. Adequate written records of all 
inspections should be kept.

Limit-F-2020

Summary of Contents for FIK-5496

Page 1: ...A P N LS10253 001FK E A ECN 151526 Document LS10253 001FK E 03 02 2021 Distributed Power Module FIK 5496 Installation Operation Manual ...

Page 2: ...ches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used ...

Page 3: ...ior to any drilling filing ream ing or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with ...

Page 4: ... questions about software and the appropriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title...

Page 5: ...rrent Draw and the Standby Battery 8 2 6 1 Worksheet Requirements 8 2 6 2 Current Draw Worksheet 9 2 6 3 Wire Routing 10 Section 3 Hardware Installation 11 3 1 AC Power 11 3 2 Battery Connection 11 3 3 Connecting the FIK 5496 to the FACP 12 3 4 Setting the Device ID 12 3 5 Notification Appliance Wiring 13 3 5 1 Class A Supervised Wiring 13 3 5 2 Class A Output Notification Circuits 13 3 5 3 Class ...

Page 6: ...circuits Outputs are rated 3 0 A 6 0 A total for each FIK 5496 The FIK 5496 is optically isolated providing ground loop isolation and transient protection The FIK 5496 provides the configuration options that eliminate the need for sychronization modules when you use the AMSECO Faraday Gentex System Sensor or Wheelock synchronization appliances 1 2 Agency Requirements TheFIK 5496 has the same requi...

Page 7: ... unit should be mounted where it will NOT be exposed to temperatures outside the range of 0 C 49 C 32 F 120 F or humidity outside the range of 10 93 at 30 C 86 F non condensing 2 3 Preventing Water Damage The water damage to the fire system can be caused by moisture entering the cabinet through the conduits Conduits that are installed to enter the top of the cabinet are most likely to cause water ...

Page 8: ...n the manual refer to the device manual for the current ratings 4 Make sure that the total alarm current you calculated including the current for the panel itself does not exceed 6 0 A This is the maximum alarm current allowable 5 Complete the remaining instructions in Table 2 4 to determine battery size requirements Terminal and Label Description Rating Voltage Current B AC input hot 120 VAC 60 H...

Page 9: ...ator Transmitter DACT Table 2 3 Maximum Battery Standby Load NOTE Use the 33 maximum battery size for the FM Factory Mutual installations Device Number of Devices Current per Device Standby Current Alarm Current For each device use this formula This column X This column Current per number of devices FIK 5496 Intelligent Power Module Current draw from battery 1 Standby 40 mA 40 mA Alarm 160 mA 160 ...

Page 10: ...Routing You must follow the power limited wiring standards These standards require you to do the following Maintain one quarter inch spacing between the power limited and the non power limited circuits Separate the high and the low voltage circuits Figure 2 2 Wire Routing Example FIK 5496 Board To AC Power To Battery To SBUS Terminals To NACs ...

Page 11: ... be necessary for a professional electrician to make this connection The AC terminals are rated as 120 VAC 50 or 60 Hz 2 5 A Figure 3 1 AC Power Connection 3 2 Battery Connection The following list the battery connection requirements The FIK 5496 battery charge capacity is 7 0 AH not to exceed 35 0 AH Use 12V batteries of the same AH rating It is recommended that you replace the batteries every fi...

Page 12: ... following Fike addressable FACP Installation Manuals that are located on the on Fike s website at www fike com Figure 3 3 Class B FIK 5496 Connection to FACP 3 4 Setting the Device ID All SBUS modules in the System must have a unique number 1 31 to identify them to the FACP Use the DIP switch on the FIK 5496 board to set the module ID number Figure 2 1 on page 2 shows the location of the dipswitc...

Page 13: ...Supervised Input Output Connections 3 5 3 Class B Supervised Wiring Figure 3 6 on page 13 shows how to wire for the Class B output supervision Use the In Out wiring methods for the proper supervision To identify which notification appliances to be used with the FIK 5496 refer to Appendix A 3 5 4 Class B Output Notification Circuits Figure 3 6 on page 13 shows four 1 5 amp devices wired as Class B ...

Page 14: ...e with the Fire Door applications When there are no alarms in the System and the panel has AC power the door holder circuits have 24 volt power present at their terminals Any alarm will cause power to discontinue The Power will be re applied when the System is reset If the AC power is off for more than 15 seconds the auxiliary door holder power will be discontinued to conserve the battery backup p...

Page 15: ...sor or Wheelock synchronization appliances A 2 Agency Requirements TheFIK 5496 has the same requirements as the main control panel These requirements are listed in the Fike addressable FACP Installation Manuals For additional information refer to the Fike s website at www fike com A 3 Reference Documentation This manual describes the installation of the FIK 5496 hardware The software configuration...

Page 16: ...FIKE CORPORATION 704 SW 10th Street Blue Springs MO 64015 Telephone 1 816 229 3405 www fike com ...

Reviews: