Notification Appliance Wiring
Hardware Installation
3.5 Notification Appliance Wiring
3.5.1 Class A Supervised Wiring
Figure 3.5 on page 13 shows how to wire for Class A output supervision. Use In/Out wiring methods for the proper supervision. Refer to
Section 4 for a list of the notification appliances compatible with the FIK-5496.
3.5.2 Class A Output Notification Circuits
The configuration shown in Figure 3.5 on page 13 illustrates two, 3-amp devices, wired as Class A circuits. When you use the outputs as
Class A circuits, loop the wiring back to the corresponding circuit pair. For Class A wiring, no external EOL is necessary since it is built into
the FIK-5496 board.
Figure 3.5 Class A Supervised Input/Output Connections
3.5.3 Class B Supervised Wiring
Figure 3.6 on page 13 shows how to wire for the Class B output supervision. Use the In/Out wiring methods for the proper supervision. To
identify which notification appliances to be used with the FIK-5496, refer to Appendix A.
3.5.4 Class B Output Notification Circuits
Figure 3.6 on page 13 shows four, 1.5 amp devices wired as Class B circuits.
Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable the supervision when using all outputs as Class B notification
appliance circuits. The 4.7k EOLs must be wired to the terminals whether or not you are using all output terminals.
Figure 3.6 Regulated Class B Supervised Input/Output Connections
NOTE:
Not all devices can use the Sync feature. Be sure to check Figure A-1 on page 1 in Figure A on page 1 to ensure the device you have
chosen will work with this feature.
Power-Limited
1.5
Ω
max
Power-Limited
1.5
Ω
max