background image

D500-74-00  3 I56-2463-008

FIGURE 2. TYPICAL CLASS B, STYLE Y NAC CONFIGURATION:

TO NEXT

DEVICE

FROM PANEL OR

PREVIOUS DEVICE

SIGNAL LINE CIRCUIT (SLC)

30 VDC MAX.

TWISTED PAIR RECOMMENDED

(–)

(+)

(–)

(+)

EOL

RESISTOR

UL LISTED

EOL RELAY

SHOWN

ENERGIZED

24 VDC COIL

A77-716B OR

EQUIVALENT

REQUIRED FOR PANELS 

WITHOUT POWER SUPPLY 

MONITORING

FROM TERMINALS

7 AND 8 OF LAST

CONTROL MODULE

ON BRANCH

MODULE POLARITIES ARE

SHOWN IN ALARM

14

13

12

11

10

9

8

7

24 VDC

POWER

SUPPLY

TO NEXT CONTROL MODULE

TERMINALS 10 (+) AND 9 (–)

OR END OF LINE RELAY

(IF REQUIRED)

+

1

2

3

4

+

24 VDC POWER SUPPLY

ISOLATED, REGULATED,

POWER LIMITED PER NFPA 70

LISTED FOR FIRE PROTECTION

WITH BATTERY BACK-UP

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

FIGURE 3. TYPICAL CLASS A, STYLE Z NAC CONFIGURATION:

TO NEXT

DEVICE

FROM PANEL OR

PREVIOUS DEVICE

SIGNAL LINE CIRCUIT (SLC)

30 VDC MAX.

TWISTED PAIR RECOMMENDED

(–)

(+)

(–)

(+)

EOL RESISTOR

IS INTERNAL

AT TERMINALS

13 & 14

UL LISTED

EOL RELAY

SHOWN

ENERGIZED

24 VDC COIL

A77-716B OR

EQUIVALENT

REQUIRED FOR PANELS 

WITHOUT POWER SUPPLY 

MONITORING

FROM TERMINALS

7 AND 8 OF LAST

CONTROL MODULE

ON BRANCH

MODULE POLARITIES ARE SHOWN IN ALARM

14
13
12
11
10

9
8
7

24 VDC

POWER

SUPPLY

TO NEXT CONTROL MODULE

TERMINALS 10 (+) AND 9 (–)

OR END OF LINE RELAY

(IF REQUIRED)

+

1
2
3
4

+

24 VDC POWER SUPPLY

ISOLATED, REGULATED,

POWER LIMITED PER NFPA 70

LISTED FOR FIRE PROTECTION

WITH BATTERY BACK-UP

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

C0107-04

C0937-00

Summary of Contents for 55-042

Page 1: ...ted 24 VDC Trouble Range 0 to 2 VDC Maximum NAC Current Ratings For Class B Wiring Systems 3A For Class A Wiring Systems 2A Temperature Range 32 F to 120 F 0 C to 49 C Humidity 10 to 93 RH Non condensing Dimensions 4 675 H x 4 275 W x 1 4 D Accessories 39 kΩ End of Line Resistor Part A2263 00 included Wall cover plate included SMB500 Surface Mount Electrical Box A2143 60 Bypass capacitor EA CB Con...

Page 2: ...te during shipping To ensure that the switch contacts are in their correct state modules must be made to com municate with the panel before connecting circuits controlled by the module TERMINAL DEFINITIONS T1 SLC in out T9 External Power Line in out T2 SLC in out T10 External Power Line in out T3 SLC in out T11 NAC A B T4 SLC in out T12 NAC A B T7 External Power Line in out T13 Class A T8 External...

Page 3: ...FOR FIRE PROTECTION WITH BATTERY BACK UP ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED FIGURE 3 TYPICAL CLASS A STYLE Z NAC CONFIGURATION TO NEXT DEVICE FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT SLC 30 VDC MAX TWISTED PAIR RECOMMENDED EOL RESISTOR IS INTERNAL AT TERMINALS 13 14 UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL A77 716B OR EQUIVALENT REQUIRED FOR PANELS WITHOUT POWER SUPPL...

Page 4: ...e equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help FIGURE 4 TYPICAL CLASS B STYLE Y AUDIO NAC CONFIGURATION TO NEXT DEVICE FROM PANEL OR PREVIOUS DEVICE SIGNAL LINE CIRCUIT SLC 30 VDC MAX TWISTED PAIR RECOMMENDED EOL RESISTOR SPEAKERS MUST BE LISTED FOR F...

Reviews: