QuickServer Start-up Guide
Page 11 of 43
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
4
INSTALLING THE QUICKSERVER
4.1
RS-485
4.1.1
RS-485 Connection R2 port
Connect to the 3 pins on the left-hand-side of the 6 pin connector as shown.
The following Baud Rates are supported on the R2 Port:
4800, 9600, 19200, 38400, 57600, 115200
Refer to Appendix D.7 for the Dip Switch Settings for these Baud Rates.
For connection to RS-232 or RS-422, please refer to Appendix A.2
4.1.2
RS-485 Connection R1 Port (Only on Non-LonWorks QuickServers)
Connect to the 3-pin connector as shown.
The following Baud Rates are supported on the R1 Port:
110, 300, 600, 1200, 2400, 4800, 9600, 19200, 20833, 28800, 38400, 57600, 76800, 115200
Refer to Appendix D.7 for the Dip Switch Settings for these Baud Rates.
+
-
GND
B+
A-
SG