FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 20 of 22
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll Free
: (888) 509-1970
Appendix B.
Troubleshooting tips
Appendix B.1.
Connection Tips & Hints
•
Communication errors will be experienced if the port is disabled at the panel. Please check the Notifier
Manuals on how to enable the panel port connected to the FieldServer and ensure that it is set to 80
columns NO supervision.
•
If connecting the Panel to one of the FieldServer RS-232 ports causes the FieldServer to reboot, then an
Optical Isolator is required to balance ground potential problems.
Appendix B.2.
Networking Tips
•
By default FieldServer does not take any action on receiving a “SYSTEM RESET”. Normally when a Node
initiates “SYSTEM RESET” by pressing the “RESET” button on the Panel, the panel sends an individual
“CLEAR” message for every point, it clears in its memory area. The FieldServer therefore waits for the
“CLEAR” message to clear a specific bit in its memory for a particular Node or for the “SYSTEM NORMAL”
message to clear all bits in its memory for every Node. Use Clear_on_Reset parameter if required.
•
It may be advisable to configure the Notifier panel to suppress less important “Supervisory” or “Trouble”
messages which could prevent the generation of “SYSTEM NORMAL” messages. Consult Notifier for this
configuration or recommendation.
•
Ensure that every Node is working with a printer or HyperTerminal, before calling FieldServer for Support.