background image

FS-8700-130 Notifier NCA2/NFS-3030 Manual 

 

 

 

 

Page 15 of 22 

FieldServer Technologies

 1991 Tarob Court Milpitas, California 95035 USA   

Web

: www.fieldserver.com 

Tel

: (408) 262-2299   

Fax

: (408) 262-2269   

Toll Free

: (888) 509-1970   

email

[email protected] 

System Trouble         

Address   

System Trouble         

Address 

ANNUN 6 TROUBLE                             

54 

 

UNPROGRAMMED DEVICE ON LOOP 3               

308 

ANNUN 7 TROUBLE                             

55 

 

UNPROGRAMMED DEVICE ON LOOP 4               

309 

ANNUN 8 TROUBLE                             

56 

 

UNPROGRAMMED DEVICE ON LOOP 5               

310 

ANNUN 9 TROUBLE                             

57 

 

UNPROGRAMMED DEVICE ON LOOP 6               

311 

ANNUN 10 TROUBLE                            

58 

 

UNPROGRAMMED DEVICE ON LOOP 7               

312 

ANNUN 11 TROUBLE                            

59 

 

UNPROGRAMMED DEVICE ON LOOP 8               

313 

ANNUN 12 TROUBLE                            

60 

 

UNPROGRAMMED DEVICE ON LOOP 9               

314 

ANNUN 13 TROUBLE                            

61 

 

UNPROGRAMMED DEVICE ON LOOP 10              

315 

ANNUN 14 TROUBLE                            

62 

 

IR ENABLED ON LOOP 1                        

316 

ANNUN 15 TROUBLE                            

63 

 

IR ENABLED ON LOOP 2                        

317 

ANNUN 16 TROUBLE                            

64 

 

IR ENABLED ON LOOP 3                        

318 

ANNUN 17 TROUBLE                            

65 

 

IR ENABLED ON LOOP 4                        

319 

ANNUN 18 TROUBLE                            

66 

 

IR ENABLED ON LOOP 5                        

320 

ANNUN 19 TROUBLE                            

67 

 

IR ENABLED ON LOOP 6                        

321 

ANNUN 20 TROUBLE                            

68 

 

IR ENABLED ON LOOP 7                        

322 

ANNUN 21 TROUBLE                            

69 

 

IR ENABLED ON LOOP 8                        

323 

ANNUN 22 TROUBLE                            

70 

 

IR ENABLED ON LOOP 9                        

324 

ANNUN 23 TROUBLE                            

71 

 

IR ENABLED ON LOOP 10                       

325 

ANNUN 24 TROUBLE                            

72 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 1           

326 

ANNUN 25 TROUBLE                            

73 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 2           

327 

ANNUN 26 TROUBLE                            

74 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 3           

328 

ANNUN 27 TROUBLE                            

75 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 4           

329 

ANNUN 28 TROUBLE                            

76 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 5           

330 

ANNUN 29 TROUBLE                            

77 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 6           

331 

ANNUN 30 TROUBLE                            

78 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 7           

332 

ANNUN 31 TROUBLE                            

79 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 8           

333 

ANNUN 32 TROUBLE                            

80 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 9           

334 

REMOTE DISPLAY 1 TROUBLE                    

81 

 

TX/RX ERROR ABOVE LIMIT ON LOOP 10          

335 

REMOTE DISPLAY 2 TROUBLE                    

82 

 

TOO MANY DEVICES ON LOOP 1                  

336 

REMOTE DISPLAY 3 TROUBLE                    

83 

 

TOO MANY DEVICES ON LOOP 2                  

337 

REMOTE DISPLAY 4 TROUBLE                    

84 

 

TOO MANY DEVICES ON LOOP 3                  

338 

REMOTE DISPLAY 5 TROUBLE                    

85 

 

TOO MANY DEVICES ON LOOP 4                  

339 

REMOTE DISPLAY 6 TROUBLE                    

86 

 

TOO MANY DEVICES ON LOOP 5                  

340 

REMOTE DISPLAY 7 TROUBLE                    

87 

 

TOO MANY DEVICES ON LOOP 6                  

341 

REMOTE DISPLAY 8 TROUBLE                    

88 

 

TOO MANY DEVICES ON LOOP 7                  

342 

REMOTE DISPLAY 9 TROUBLE                    

89 

 

TOO MANY DEVICES ON LOOP 8                  

343 

REMOTE DISPLAY 10 TROUBLE                   

90 

 

TOO MANY DEVICES ON LOOP 9                  

344 

REMOTE DISPLAY 11 TROUBLE                   

91 

 

TOO MANY DEVICES ON LOOP 10                 

345 

REMOTE DISPLAY 12 TROUBLE                   

92 

 

MISMATCHED LOOP TYPE ON LOOP 1              

346 

REMOTE DISPLAY 13 TROUBLE                   

93 

 

MISMATCHED LOOP TYPE ON LOOP 2              

347 

REMOTE DISPLAY 14 TROUBLE                   

94 

 

MISMATCHED LOOP TYPE ON LOOP 3              

348 

REMOTE DISPLAY 15 TROUBLE                   

95 

 

MISMATCHED LOOP TYPE ON LOOP 4              

349 

REMOTE DISPLAY 16 TROUBLE                   

96 

 

MISMATCHED LOOP TYPE ON LOOP 5              

350 

REMOTE DISPLAY 17 TROUBLE                   

97 

 

MISMATCHED LOOP TYPE ON LOOP 6              

351 

REMOTE DISPLAY 18 TROUBLE                   

98 

 

MISMATCHED LOOP TYPE ON LOOP 7              

352 

REMOTE DISPLAY 19 TROUBLE                   

99 

 

MISMATCHED LOOP TYPE ON LOOP 8              

353 

REMOTE DISPLAY 20 TROUBLE                   

100 

 

MISMATCHED LOOP TYPE ON LOOP 9              

354 

REMOTE DISPLAY 21 TROUBLE                   

101 

 

MISMATCHED LOOP TYPE ON LOOP 10             

355 

REMOTE DISPLAY 22 TROUBLE                   

102 

 

MAPPING IN PROGRESS LOOP 1                  

356 

REMOTE DISPLAY 23 TROUBLE                   

103 

 

MAPPING IN PROGRESS LOOP 2                  

357 

REMOTE DISPLAY 24 TROUBLE                   

104 

 

MAPPING IN PROGRESS LOOP 3                  

358 

REMOTE DISPLAY 25 TROUBLE                   

105 

 

MAPPING IN PROGRESS LOOP 4                  

359 

REMOTE DISPLAY 26 TROUBLE                   

106 

 

MAPPING IN PROGRESS LOOP 5                  

360 

REMOTE DISPLAY 27 TROUBLE                   

107 

 

MAPPING IN PROGRESS LOOP 6                  

361 

REMOTE DISPLAY 28 TROUBLE                   

108 

 

MAPPING IN PROGRESS LOOP 7                  

362 

REMOTE DISPLAY 29 TROUBLE                   

109 

 

MAPPING IN PROGRESS LOOP 8                  

363 

REMOTE DISPLAY 30 TROUBLE                   

110 

 

MAPPING IN PROGRESS LOOP 9                  

364 

REMOTE DISPLAY 31 TROUBLE                   

111 

 

MAPPING IN PROGRESS LOOP 10                 

365 

REMOTE DISPLAY 32 TROUBLE                   

112 

 

LIB #1 SCB RECEIVE ERROR                    

366 

Summary of Contents for NCA2-NFS2-3030

Page 1: ...ITY EFFECTIVITY Effective for all systems manufactured after January 2009 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 130 Notifier NCA2 NFS2 3030 Driver Version 1 02 Document Revision 1 ...

Page 2: ... 2 Data Arrays Descriptors 8 4 3 Client Side Connection Descriptions 9 4 4 Client Side Node Descriptors 9 4 5 Client Side Map Descriptors 10 4 5 1 FieldServer Related Map Descriptor Parameters 10 4 5 2 Driver Related Map Descriptor Parameters 10 4 5 3 Map Descriptor Example Standard example 11 5 Configuring the FieldServer as a Notifier NCA2 NFS2 3030 Server 12 Appendix A Advanced Topics 13 Append...

Page 3: ...itored by third party tools Since the FieldServer does not actively poll for data the accuracy and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues If a networked panel does not send the CLEARED message for latched points via the NCA2 it is not possible to detect cleared points unless a system reset is done It is possible to configure...

Page 4: ...n drawing Configure the Notifier Panel according to manufacturer s instructions FieldServer FieldServer Part 8917 16 Pigtail for RJ45 Port RJ45 Connection to TB5 Printer Port Notifier NCA2 NFS2 3030 Connect to one of the RS 232 Ports on the FieldServer P1 CTX CRX REF PTX PRX REF TB5 Printer CRT Rx Brown Tx Orange White Com Blue White 1 8 Connector Pinouts TB5 CRT Function Receive Reference Transmi...

Page 5: ...l 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 3 1 Hardware Connection Tips Hints The FieldServer should preferably be connected to the TB5 Printer port It is theoretically possible to connect to the TB5 CRT port but this has not been fully tested The Panel s port must be enabled and set to 80 Columns Not Supervised ...

Page 6: ...ing the text messages sent to the printer or CRT port Not all messages will be interpreted as many messages do not directly pertain to device status or are not currently supported The following subset of event messages is recognized Active Events FIRE ALARM SECURITY ALARM LIFE LIFE CRITICAL ALARM MEDICAL EMERGENCY SECURITY ALARM CRITICAL PROCESS SUPERVISORY TROUBLE FAULT DISABLED PREALARM ACTIVE O...

Page 7: ...Active 1432 1590 ON OFF 1591 1749 Memory Type Detector_Trouble Module_Trouble Troubles Faults 1 159 Parameter Addresses For each Node Memory Type Node_Trouble Troubles Faults 1 508 Memory Type Panel Panel Maximum12 Boards and 8 Panel circuits per Board Hardware address memory address Board 1 panel 1 1 Board 1 panel 2 2 Board 2 panel 1 9 Board 12 panel 8 96 Fire Alarm 1 96 Security Life 97 192 Life...

Page 8: ...ide Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal value being the default Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Bit Sin...

Page 9: ...its Specify data bits 8 Vendor limitation Stop_Bits Specify stop bits 1 Vendor limitation Example Client Side Connections Connections Port Protocol Baud Stop_Bits Parity P8 nfs2 nca 9600 1 None 4 4 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID Station address of any physical Node on netwo...

Page 10: ...riptor Passive 4 5 2 Driver Related Map Descriptor Parameters Column Title Function Legal Values Node_Name Name of Node to fetch data from One of the Node names specified in Client Node Descriptor above Data_Type Specify memory area type Detector Module Detector_Trouble Module_Trouble Panel Panel_Trouble Bell_Trouble Node_Trouble Address Starting address of block As per Data_type Detector Module 1...

Page 11: ...fset Function Node_Name Loop Data_Type Address Length Capture Node Events SMD_N2_Troubles DA_SYS_N2 0 Passive NODE2 Node_Trouble 1 508 SMD_N2_PANEL DA_N2_PANEL 0 Passive NODE2 Panel 1 1056 SMD_N2_PANEL_T DA_N2_PANEL_T 0 Passive NODE2 Panel_Trouble 1 96 SMD_N2_BELL_T DA_N2_BELL_T 0 Passive NODE2 Bell_Trouble 1 4 Capture Loop 1 events SMD_N2L01D DA_N2L01D 0 Passive NODE2 1 Detector 1 1749 SMD_N2L01D...

Page 12: ...logies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 5 CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2 NFS2 3030 SERVER This driver cannot be configured as a Server ...

Page 13: ... states 1 0 SECURITY ALARM CLEARED SECURITY ALARM states 1 0 CRITICAL PROCESS CRITICAL PROCESS states 1 0 SUPERVISORY CLEARED SUPERVISORY states 1 0 TROUBLE FAULT CLEARED TROUBLE FAULT States counter DISABLED CLEARED DISABLED states 1 0 PREALARM CLEARED PREALARM states 1 0 ACTIVE CLEARED ACTIVE states 1 0 ON OFF OFF states 1 0 SYSTEM NORMAL Resets all addresses in all memory areas but only if data...

Page 14: ...D 5 276 STYLE 6 NEG LOOP 10 23 COMM FAULT LOOP INTERFACE BOARD 6 277 STYLE 6 POS LOOP 1 24 COMM FAULT LOOP INTERFACE BOARD 7 278 STYLE 6 POS LOOP 2 25 COMM FAULT LOOP INTERFACE BOARD 8 279 STYLE 6 POS LOOP 3 26 COMM FAULT LOOP INTERFACE BOARD 9 280 STYLE 6 POS LOOP 4 27 COMM FAULT LOOP INTERFACE BOARD 10 281 STYLE 6 POS LOOP 5 28 CATASTROPHIC ISIB COMMUNICATIONS FAULT 282 STYLE 6 POS LOOP 6 29 MEM...

Page 15: ...BOVE LIMIT ON LOOP 10 335 REMOTE DISPLAY 2 TROUBLE 82 TOO MANY DEVICES ON LOOP 1 336 REMOTE DISPLAY 3 TROUBLE 83 TOO MANY DEVICES ON LOOP 2 337 REMOTE DISPLAY 4 TROUBLE 84 TOO MANY DEVICES ON LOOP 3 338 REMOTE DISPLAY 5 TROUBLE 85 TOO MANY DEVICES ON LOOP 4 339 REMOTE DISPLAY 6 TROUBLE 86 TOO MANY DEVICES ON LOOP 5 340 REMOTE DISPLAY 7 TROUBLE 87 TOO MANY DEVICES ON LOOP 6 341 REMOTE DISPLAY 8 TRO...

Page 16: ...NNUN 6 NO ANSWER 138 LIB 8 NIB COMMUNICATION ERROR 392 ANNUN 7 NO ANSWER 139 LIB 9 COMMUNICATION ERROR 393 ANNUN 8 NO ANSWER 140 LIB 10 NIB COMMUNICATION ERROR 394 ANNUN 9 NO ANSWER 141 LIB 1 NIB M S PROGRAMMING ERROR 395 ANNUN 10 NO ANSWER 142 LIB 2 NIB M S PROGRAMMING ERROR 396 ANNUN 11 NO ANSWER 143 LIB 3 NIB M S PROGRAMMING ERROR 397 ANNUN 12 NO ANSWER 144 LIB 4 NIB M S PROGRAMMING ERROR 398 A...

Page 17: ...R SECONDARY STATUS 450 UDACT NO ANSWER 197 LINK PROTECTOR PRIMARY NOT PRESENT 451 MASTER BOX NO ANSWER 198 EVENT BUFFER 80 FULL 452 DAA NO ANSWER 199 EBI STATUS 453 NO ANSWER 200 SOFTWARE MISMATCH 454 NETWORK FAILURE 201 NO POWER SUPPLY INST 455 WORKSTATION FAN FAILURE 202 TEST PROGRAM UPDATE 456 UPS FAILURE 203 HISTORY 80 FULL 457 NCM COMM FAILURE 204 FLASH IMAGE ERROR 458 NODE COMMUNICATIONS FAI...

Page 18: ...L PORT B 244 DVC COMM LOSS 498 STYLE 4 SHORT A L1 245 A C POWER LOSS BACK UP ACTIVATED 499 STYLE 4 SHORT B L1 246 BUZZER OFF LINE 500 STYLE 4 SHORT A L2 247 PANEL DOOR OPEN 501 STYLE 4 SHORT B L2 248 OFF NETWORK 502 STYLE 4 SHORT A L3 249 INSTALL ERROR 503 STYLE 4 SHORT B L3 250 OR AUDIO TELEPHON 504 STYLE 4 SHORT A L4 251 EXPANDER MODULES 505 STYLE 4 SHORT B L4 252 MANUAL CONTROL 506 STYLE 4 SHOR...

Page 19: ...NCA 2 EIA 232 Protocol Data Formats 53219 Rev A 1 3 2008 Any changes or additions by Notifier will not be reflected in this driver unless specifically revised This driver will not record information about zone status that is incorporated with point status messages There can only be one panel connected to any given FieldServer port This driver records data as presented to the printer CRT port by th...

Page 20: ...e ground potential problems Appendix B 2 Networking Tips By default FieldServer does not take any action on receiving a SYSTEM RESET Normally when a Node initiates SYSTEM RESET by pressing the RESET button on the Panel the panel sends an individual CLEAR message for every point it clears in its memory area The FieldServer therefore waits for the CLEAR message to clear a specific bit in its memory ...

Page 21: ... d Node u Loop d Data_Type s Address d The FieldServer got a recognized message on this particular port Node loop Address_Type and Address but did not find a defined Map Descriptor To capture this data add a new Map Descriptor with the required parameters 2 Err Reset Normal queue d full on MD s This driver keeps track of all non zero memory locations per Map Descriptor When the track queue is full...

Page 22: ...n 0 This occurs due to poor synchronization between the FieldServer and the Notifier panel or because a problem existed before connection 3 It will rectify itself upon System Normal message Check the configuration file to identify the address and memory area type mapped to this offset and the Data Array which is causing the error 3 All Data Arrays on the FieldServer are initialized to zero on rebo...