4.1.1. FieldServer
Related
Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map
Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array
where data is to be
stored in the
FieldServer
One of the Data Array
names from “Data Array”
section above
Data_Array_Location
Starting location in
Data Array
0 to maximum specified in
“Data Array” section
above
Function
Function of Client
Map Descriptor
ARS, RDBC, WRBC,
WRBX, AWT
4.1.2.
Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch
data from
One of the node names
specified in “Client Node
Descriptor” above
GRAFIK_command
Specifies the command
to be sent to the
eLumen.
A list of commands is
provided in Appendix A.
Link
Wallstation link number
0–11 for
GRAFIK_command:
ena_wallstation,
dis_wallstation,
sim_ws_sw_press,
sim_ws_sw_rls,
0-31 for
GRAFIK_command:
wallstation_status,
switch_status,
Area
GRAFIK system area
number
0–511
Link_station
Wallstation on link’s
number
0–31
Switch
Wallstation switch
number
0–31
Zone
GRAFIK system zone
number
0–511
Sys_var
GRAFIK system variable
number
0–65535