3. Hardware
Connections
The FieldServer is connected to the Veeder-Root Panel as shown below.
Configure the Veeder-Root Panel according to manufacturer’s instructions.
DATE: 1/17/02
BY: MN
(408)-262-2299
BASE NAME:
FILE NAME: FS-T28700-74 .VSD
VEEDER ROOT
CONNECTION DIAGRAM
P4
P1
Rx
P2
P3
Tx
Rx
Tx
Tx
Rx
Rx
P7
P5
P6
Tx
Rx Tx
Tx
Rx
Rx
P8
R1
Tx
Rx
Tx
Rx
Tx
R2
Net 1
Tx
Rx
Rx
Tx
Con
Net 2
Sy
s
Co
m
Tx
Rx Con
Ac
t
Ru
n
Pw
r
RS485
RS232
10 Base T
ETHERNET
P1
P7
R1
P2
R2
P3
P4
P5
P6
P8
N1
N2
8917-07
FieldServer
FIELDSERVER
FUNCTION
FROM
TO
COLOR
RX
RJ45-01
DB25M-02 WHITE
CTS
RJ45-02
DB25M-05 BROWN
DSR
RJ45-03
DB25M-08 YELLOW
GND
RJ45-04
DB25M-07 GREEN
DTR
RJ45-06
DB25M-20 BLACK
RTS
RJ45-07
DB25M-06 ORANGE
TX
RJ45-08
DB25M-03 BLUE
TLS-350
8917-07 WIRE LIST
RJ45 CAT 5 Cable
Connect to
RS232 port P1-P8