Error
Action Required
VRoot:#1 FYI. The
mapDesc called <%s> is
too short.
§
The length of the Map Descriptor used to expose driver statistics
is too short. Set the length to at least 600.
VRoot:#2 FYI. You could
have used a mapDesc
called <%s> to expose
diagnostic info.
You can safely ignore this message. It is a prompt. Refer to
Appendix B.1.
*VRoot:#3 Err. Data
Type=%d is unknown. Data
will be discarded.
The driver has encountered a message reporting an alarm for an
equipment category/data type the driver does not recognize.
Take a port log and consult with FieldServer Technical Services.
VRoot:#4 FYI. If there is
more than one VRoot node
then connect each node to
a dedicated port
You may ignore this message if only one Veeder-Root node is
connected to the FieldServer. If more than one node is
connected then, you must explicitly connect each node to a
separate port. Do this by editing the CSV file and then reset the
FieldServer to eliminate the message.
The CSV fragment below illustrates explicit connection of a node
to a port.
Connections,
Port,…,Protocol.
P1,…...,VRoot
Nodes,.…, Port, ….,Protocol
N1 ,…., P1 ,…..,Vroot
VRoot:#5 Err. Data Type
invalid for this driver.
Md=<%s>
§
The Data types must be spelled, spaced and punctuated exactly
as in Appendix A.1
VRoot:#6 Err. No Default
Poll Function for this data
type. Md= <%s>
§
Some data types require an addition Map Descriptor parameter
‘VEED_Function’ to be specified. Read the notes / example in the
Advanced Topics section to determine the requirements to
correct this error.
VRoot:#7 Err. Length too
short. Rqd=%d. Md=<%s>
§
The message reports the offending Map Descriptor and the
number of array elements required. Adjust the length parameter
accordingly. Ensure that the new length coupled with the offset
fits in the array size.
VRoot:#11 Err. Command
0x54 cannot specify all
tanks
§
For the Data Type (or Veed_Function) specified the address may
not be set to zero. You need one Map Descriptor per
tank/sensor/input/device. There are a few variations of this error
message each reporting the offending function.
VRoot:#12 Err. Command
0x54. Bad confirmation
code.
You cannot take any corrective action to eliminate this error.
Report the message to FieldServer support. It will assist in the
diagnosis of the error if you can take a port log. . There are a few
variations of this error message each reporting the offending
function.
§
This is a configuration error which can be eliminated by correcting an error in the CSV file and resetting
the FieldServer.