OPERATING INSTRUCTIONS

FP-AI-100

8-Channel, 12-Bit Analog Input Module

These operating instructions describe the installation, features, and 
characteristics of the FP-AI-100. For more information about 
configuring and accessing the FP-AI-100 over a network, refer to 
the user manual for the particular FieldPoint network module you 
are using with the FP-AI-100.

Features

The FP-AI-100 is a FieldPoint analog input module with the 
following features:

Eight analog voltage or current input channels

11 input ranges: ±15 V, ±5 V, ±1 V, 0–15 V, 0–5 V, 0–1 V, 
±20 mA, 0–20 mA, 4–20 mA, 0–30 V, ±30 V

12-bit resolution

Hot plug and play operation

2,500 Vrms input-to-output isolation

Double insulated for 250 V safe working voltage

–40 to +70 °C operation

Installation

The FP-AI-100 mounts on a FieldPoint terminal base (FP-TB-xx
unit. Because of its hot plug and play operation, you can install the 
FP-AI-100 onto a powered terminal base without disturbing the 
operation of other modules or terminal bases. The FP-AI-100 
receives operating power from the terminal base.

Summary of Contents for FP-AI-100

Page 1: ...icular FieldPoint network module you are using with the FP AI 100 Features The FP AI 100 is a FieldPoint analog input module with the following features Eight analog voltage or current input channels 11 input ranges 15 V 5 V 1 V 0 15 V 0 5 V 0 1 V 20 mA 0 20 mA 4 20 mA 0 30 V 30 V 12 bit resolution Hot plug and play operation 2 500 Vrms input to output isolation Double insulated for 250 V safe wor...

Page 2: ...odule Field Wiring The terminal base provides connections for each input channel and an external supply to power field devices Each channel has one input terminal for voltage Vin or current Iin inputs Both voltage and current inputs are referenced to the COM terminals To connect an external supply to power field devices connect to the V and C terminals of the terminal base If you use an external s...

Page 3: ...f the FP AI 100 module Table 1 Terminal Assignments Channel Terminal Numbers Vin Iin Vsup COM 0 1 2 17 18 1 3 4 19 20 2 5 6 21 22 3 7 8 23 24 4 9 10 25 26 5 11 12 27 28 6 13 14 29 30 7 15 16 31 32 External Power Supply Loop Powered Current Transmitter Powered Voltage Transmitter V C Vsup Iin Vsup Vin OUT COM a With an External Supply to Power Field Devices Current Source Voltage Source Iin COM Vin...

Page 4: ...am of the input circuit of one single channel Figure 3 Analog Input Circuit Voltage Inputs Connect positive voltage inputs to the Vin terminal and connect negative voltage inputs to the COM terminal The input ranges for voltage signals are 15 V 5 V 1 V 0 15 V 0 5 V 0 1 V 0 30 V and 30 V Current Inputs Connect current inputs to the Iin terminals and reference them to the COM or C terminals The FP A...

Page 5: ...o 20 Also with the over ranging feature a noisy signal near full scale does not create rectification errors Status Indicators Figure 4 shows the module label and status indicators To see wiring diagrams for the input channels remove the slide in card Figure 4 Status Indicators After you insert the module into a terminal base and apply power the green POWER indicator lights and the FP AI 100 inform...

Page 6: ...he product is specifically designed for such an application as is the FP AI 100 When you use a product like the FP AI 100 in applications with hazardous potentials follow these guidelines to make sure your total system is safe The safety isolation of the FP AI 100 is from input to output not between channels on the same module If any of the channels on a module are wired at a hazardous potential m...

Page 7: ...s 360 S s 2 8 ms Voltage Inputs The following input signal ranges are software selectable per channel Voltage Input Range Effective Resolution Typical Offset Error at 15 to 35 C Maximum Offset Error at 40 to 70 C 0 1 V 0 5 V 0 15 V 0 30 V 1 V 5 V 15 V 30 V 1 5 mV 5 mV 15 mV 25 mV 1 5 mV 5 mV 25 mV 40 mV 1 1 mV 1 LSB 4 mV 1 LSB 10 mV 1 LSB 20 mV 1 LSB 1 7 mV 1 LSB 7 mV 1 LSB 20 mV 1 LSB 40 mV 1 LSB...

Page 8: ...C 0 1 V 0 5 V 0 15 V 0 30 V 1 V 5 V 15 V 30 V 0 1 2 V 0 6 V 0 18 V 0 36 V 1 2 V 6 V 18 V 36 V 0 09 0 09 0 12 0 22 0 08 0 08 0 11 0 20 0 50 0 50 0 55 0 53 0 50 0 53 0 57 0 54 Current Input Range Effective Resolution Typical Offset Error at 15 to 35 C Maximum Offset Error at 40 to 70 C 0 20 mA 4 20 mA 20 mA 15 µΑ 15 µΑ 20 µΑ 12 µΑ 1 LSB 12 µΑ 1 LSB 27 µΑ 1 LSB 40 µΑ 1 LSB 40 µΑ 1 LSB 100 µΑ 1 LSB Ef...

Page 9: ...g CE Mark Compliance This product meets applicable EU directive s as follows Safety isolation EN 61010 double insulation for 250 Vrms working isolation installation category II EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 m Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP AI 100 installed on a terminal base Dimensions are given in inc...