FP-AI-100

6

www.natinst.com

Isolation and Safety Guidelines

Caution

Before you connect any circuits that may 

contain hazardous voltages to the FP-AI-100, read the 
following information.

This section describes the isolation of the FP-AI-100 and its 
compliance with international safety standards. The field wiring 
connections are isolated from the backplane provided by the 
terminal base with an optical and galvanic isolation barrier 
designed and tested to provide protection against fault voltages of 
up to 2,500 Vrms. In addition, the FP-AI-100 provides double 
insulation
 (compliant with IEC 1010-1) for working 
common-mode voltages of 250 Vrms. Safety standards (such as 
those published by UL and IEC) require the use of double 
insulation between hazardous voltages and any human-accessible 
parts or circuits.

Never try to use any isolation product between human-accessible 
parts (such as DIN rails or monitoring stations) and circuits that 
may be at hazardous potentials under normal conditions, unless the 
product is specifically designed for such an application, as is the 
FP-AI-100. 

When you use a product like the FP-AI-100 in applications with 
hazardous potentials, follow these guidelines to make sure your 
total system is safe:

The safety isolation of the FP-AI-100 is from input to output, 
not between channels on the same module. If any of the 
channels on a module are wired at a hazardous potential, make 
sure that all other devices or circuits connected to that module 
are properly insulated from human contact.

Do not share the external supply voltages (V and C on the 
terminal base) with other devices (including other FieldPoint 
devices), unless those devices are isolated from human contact.

As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes and 
common sense practices. Mount terminal bases in an area, 
position, or cabinet that prevents accidental or unauthorized 
access to wiring that carries hazardous voltages.

The isolation of the FP-AI-100 is certified as double-insulated 
for normal operating voltages of 250 Vrms. Do not use the 
FP-AI-100 as the only isolating barrier between human contact 
and working voltages of more than 250 Vrms.

Summary of Contents for FP-AI-100

Page 1: ...icular FieldPoint network module you are using with the FP AI 100 Features The FP AI 100 is a FieldPoint analog input module with the following features Eight analog voltage or current input channels 11 input ranges 15 V 5 V 1 V 0 15 V 0 5 V 0 1 V 20 mA 0 20 mA 4 20 mA 0 30 V 30 V 12 bit resolution Hot plug and play operation 2 500 Vrms input to output isolation Double insulated for 250 V safe wor...

Page 2: ...odule Field Wiring The terminal base provides connections for each input channel and an external supply to power field devices Each channel has one input terminal for voltage Vin or current Iin inputs Both voltage and current inputs are referenced to the COM terminals To connect an external supply to power field devices connect to the V and C terminals of the terminal base If you use an external s...

Page 3: ...f the FP AI 100 module Table 1 Terminal Assignments Channel Terminal Numbers Vin Iin Vsup COM 0 1 2 17 18 1 3 4 19 20 2 5 6 21 22 3 7 8 23 24 4 9 10 25 26 5 11 12 27 28 6 13 14 29 30 7 15 16 31 32 External Power Supply Loop Powered Current Transmitter Powered Voltage Transmitter V C Vsup Iin Vsup Vin OUT COM a With an External Supply to Power Field Devices Current Source Voltage Source Iin COM Vin...

Page 4: ...am of the input circuit of one single channel Figure 3 Analog Input Circuit Voltage Inputs Connect positive voltage inputs to the Vin terminal and connect negative voltage inputs to the COM terminal The input ranges for voltage signals are 15 V 5 V 1 V 0 15 V 0 5 V 0 1 V 0 30 V and 30 V Current Inputs Connect current inputs to the Iin terminals and reference them to the COM or C terminals The FP A...

Page 5: ...o 20 Also with the over ranging feature a noisy signal near full scale does not create rectification errors Status Indicators Figure 4 shows the module label and status indicators To see wiring diagrams for the input channels remove the slide in card Figure 4 Status Indicators After you insert the module into a terminal base and apply power the green POWER indicator lights and the FP AI 100 inform...

Page 6: ...he product is specifically designed for such an application as is the FP AI 100 When you use a product like the FP AI 100 in applications with hazardous potentials follow these guidelines to make sure your total system is safe The safety isolation of the FP AI 100 is from input to output not between channels on the same module If any of the channels on a module are wired at a hazardous potential m...

Page 7: ...s 360 S s 2 8 ms Voltage Inputs The following input signal ranges are software selectable per channel Voltage Input Range Effective Resolution Typical Offset Error at 15 to 35 C Maximum Offset Error at 40 to 70 C 0 1 V 0 5 V 0 15 V 0 30 V 1 V 5 V 15 V 30 V 1 5 mV 5 mV 15 mV 25 mV 1 5 mV 5 mV 25 mV 40 mV 1 1 mV 1 LSB 4 mV 1 LSB 10 mV 1 LSB 20 mV 1 LSB 1 7 mV 1 LSB 7 mV 1 LSB 20 mV 1 LSB 40 mV 1 LSB...

Page 8: ...C 0 1 V 0 5 V 0 15 V 0 30 V 1 V 5 V 15 V 30 V 0 1 2 V 0 6 V 0 18 V 0 36 V 1 2 V 6 V 18 V 36 V 0 09 0 09 0 12 0 22 0 08 0 08 0 11 0 20 0 50 0 50 0 55 0 53 0 50 0 53 0 57 0 54 Current Input Range Effective Resolution Typical Offset Error at 15 to 35 C Maximum Offset Error at 40 to 70 C 0 20 mA 4 20 mA 20 mA 15 µΑ 15 µΑ 20 µΑ 12 µΑ 1 LSB 12 µΑ 1 LSB 27 µΑ 1 LSB 40 µΑ 1 LSB 40 µΑ 1 LSB 100 µΑ 1 LSB Ef...

Page 9: ...g CE Mark Compliance This product meets applicable EU directive s as follows Safety isolation EN 61010 double insulation for 250 Vrms working isolation installation category II EMC directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 m Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP AI 100 installed on a terminal base Dimensions are given in inc...

Page 10: ......

Reviews: