background image

page 5 of 12

SIDEWALL VENT HOOD INSTALLATION

1. Use the inside wall plate as a template to mark 

the hole location. Cut a hole 1" larger than 
the  marked  hole  to  facilitate  easy  installation 
(See Figure 4)

2.  Center vent hood through the hole from outside. 

Fasten the vent hood to the outside wall with the 
appropriate type of mounting screws.

3.  Fasten the wall end plate to the inside wall with 

the appropriate type of mounting screws.  NOTE: 
Apply sealant to the outside mounting plate of 
the vent hood to prevent leakage.

4.  Connect the venter outlet or a properly sized section of vent pipe onto the inner pipe of the vent hood. Fasten 

the connection with three sheet metal screws or equivalent fastening method. 

5.  Seal the vent hood inlet connection and any other vent pipe joints on the outlet side of the venter with an 

approved high temperature silicone adhesive sealant or equivalent material.

INSTALLATION OF POWER VENTER

CAUTION: Failure to install, maintain and/or operate the power venting system in accordance with manufacturer's 
instructions will result in conditions which may produce bodily injury and/or property damage.

1.  Remove power venter from box and inspect unit for damage. If the carton has been crushed or mutilated, 

check unit very carefully for damage. Rotate venter wheel to ensure that the motor and venter wheel 
rotate freely. DO NOT install if any damage is apparent. Refer to unit sizing chart to check proper venting 
sizing.

2.  Location of the termination of the venting system should be installed in accordance with the National Fuel 

Gas Code, ANSI Z233.1, manufacturer's recommendations, and/or local codes which are applicable. See the 
following requirements or refer to Diagram A for typical locations.

a.  The exit termination of mechanical draft systems shall not be less than 7' above grade when located 

adjacent to public walkways.

b.  A venting system shall terminate at least 3' above any forced air inlet located within 10'.

c.  The venting system of other than a direct vent appliance shall terminate at least 4' below, 4' 

horizontally from, or 1' above any door, window, or gravity air inlet into the building.

d.  The vent termination of a direct vent appliance with an input of 50,000 BTU/HR or less, shall be 

located at least 9" from any opening through which vented gases could enter the building. With an 
input over 50,000 BTU/HR, a 12" termination clearance shall be required.

e.  The vent termination point shall not be installed closer than 3' from an inside corner of an 

L-shaped structure.

f.  The vent termination should not be mounted directly above or within 3' horizontally from an oil tank 

vent or gas meter.

g.  The bottom of the vent terminal shall be located at least 12" above fi nished grade.

8. Air fl ow adjustment MUST be made to ensure appliance effi

  ciency. This should be done at the appliance 

exhaust outlet with a velocity meter, draft gauge or by the “match test procedure”. The match test is in 
accordance with National Fuel Gas Code A.N.S.I.Z223.1, Section 8.6.

9.  On heating appliances not equipped with a draft hood, a barometric draft control MUST be installed to 

regulate proper air fl ow and fl uctuations in the system’s air fl ow during operation. Fluctuations can come 
from wind loads on the outlet of the venter, house depressurization during windy days, and the diff erent 
house ventilation requirements between summer and winter operation. Use a Field Controls Type MG-1 
Barometric Draft Control. Gas-fi red draft induced systems should have a single-acting or double-acting 
barometric draft control installed.

Figure 4

P/N 46246300 Rev M 04/20

NOTE: If mounting the power venter through a combustable wall material, a minimum clearance of 1/2” 
must be maintained between the venter outerpipe and combustible materials.

Summary of Contents for PVG-100

Page 1: ... with pre wired integral 24 VAC Relay Timer factory set Draft Proving Switch and direct access Terminal Blocks 1 Installation Instruction Sheet OPTIONAL SYSTEM COMPONENTS NOT INCLUDED Side Wall Vent Hood Spill Switches Barometric Draft Control CONTENTS PAGE System Operation 2 Power Venter Sizing 3 4 Installation Safety Instructions 4 5 Installation of Power Venter 5 6 General Wiring Instructions 7...

Page 2: ...run the power venter for a period of time after the burner has shut off to purge remaining flue gases UNIT SPECIFICATIONS Table 1 UNIT DIMENSIONS INCHES ELECTRICAL RATINGS MODEL H W D I O VAC Hz RPM WATT AMP TP PVG 100 7 5 10 0 7 0 4 4 115 60 3000 145 2 1 YES PVG 300 7 5 11 5 7 0 4 4 115 60 3000 145 2 1 YES PVG 600 8 75 12 0 8 5 5 5 115 60 3000 167 1 5 YES Inlet and outlet diameter Thermally prote...

Page 3: ...H IN FEET 1 Calculate the total equivalent feet for each type of fitting used in the venting system from the following chart 2 Calculate the total amount of feet for the straight lengths of vent pipe 3 Add the equivalent feet for the fittings with the total amount of feet of straight lengths Table 3 Reducer or increaser ratio d D small diameter divided by the larger diameter See Figure 3 Example 4...

Page 4: ...nded by the National Fuel Gas Code ANSI Z223 1 or refer to the General Installation Inspection section of this manual 3 Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls 4 Single wall vent pipe may be used to join an appliance to the venting system but if proper clearances cannot be maintained from combusti...

Page 5: ...stems shall not be less than 7 above grade when located adjacent to public walkways b A venting system shall terminate at least 3 above any forced air inlet located within 10 c The venting system of other than a direct vent appliance shall terminate at least 4 below 4 horizontally from or 1 above any door window or gravity air inlet into the building d The vent termination of a direct vent applian...

Page 6: ...regulate any draft fluctuations during operation 1 Use approved vent connectors to join the heating appliance outlet to the venter inlet securing each joint with sheet metal screws or equivalent means of fastening when required 2 Seal all pipe joints on the outlet side of the venter with a high temperature silicone adhesive or equivalent Test the vent connections for leaks by using a soap solution...

Page 7: ...r circuit breaker rated at 15 amperes Prevent wiring contact with any heat source Wire the venter in accordance with the National Electrical Code and applicable local codes Refer to Diagram B for proper wiring specifications Diagram B 3 Wire the switch into the low voltage thermostat circuit Refer to the appropriate wiring diagram in this manual 4 After installation check the amperage through the ...

Page 8: ...a heating appliance in accordance with the National Fuel Gas Code ANSI Z223 1 The following procedure will help in evaluation of the venting system It is intended as a guide to aid in determining that the appliance is properly installed and is in a safe condition for continuous use This is a generalized procedure which cannot anticipate all situations Accordingly in some cases deviation from this ...

Page 9: ...nce a year motor should rotate freely To prolong the life of the PVG 600 motor it must be lubricated with six drops of SWG Superlube Part 46226200 annually The PVG 100 and PVG 300 have sealed ball bearings and therefore do not need to be oiled Blower Wheel Inspect the blower wheel annually to clear any soot ash or coating which inhibits either rotation or air flow Remove all foreign materials befo...

Page 10: ...city of the venter selected b A CK 41 Control Kit must be added to the system to properly control the venter when common venting an additional 24 VAC furnace or boiler Tee the draft tube on the PVG unit to connect to the air pressure switch on the Control Kit Refer to Diagram D for wiring instructions PV SERIES POWER VENTER VERTICAL VENTING OPTION Diagram C illustrates correct and incorrect instal...

Page 11: ...L1 L2 TERMINAL STRIP IN 24VAC CONTROL KIT ON SECOND APPLIANCE APPLIANCE CONNECTIONS L1 L2 GAS PRESSURE SWITCH ON MILLIVOLT APPLIANCE PVG WIRING FOR MULTIPLE 24VAC APPLIANCES PVG WIRING FOR MULTIPLE 24VAC APPLIANCES VENTING SYSTEM OPERATIONAL INFORMATION Date Heating appliance BTU HR input Gas valve operation pressure Vent system draft above draft hood or below barometric draft control CO2 measurem...

Page 12: ...m ventCool Field Controls Technical Support Field Controls Technical Support 1 800 742 8368 1 800 742 8368 fieldtec fieldcontrols com fieldtec fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information abou...

Reviews: