INSTALLATION SAFETY INSTRUCTIONS
CAUTION: This device must be installed by a qualifi ed installer in accordance with the manufacturer's installation 
instructions. Appliances should have a minimum of 75% combustion effi

  ciency or have a maximum measured fl ue 

gas temperature of 550°F at the inlet of the venter.

1. The power venting system must be installed by a qualifi ed installer. "Qualifi ed Installer" shall mean an 

individual who has been properly trained or a licensed installer. The installer must write or imprint his name, 
phone number and date of installation on the installation tag. The tag should be attached to the power venter 
unit. Recording burner and venting system initial operational information is recommended as a guide for 
service or burner tune-up. Enter this in the space provided in this manual.

2.  Safety inspection of a venting system should be performed before and after installing a power venting system 

on an existing or new appliance. Procedures to follow are those recommended by the National Fuel Gas Code, 
ANSI Z223.1 or refer to the "General Installation Inspection" section of this manual.

3.  Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed 

wiring or plumbing inside walls.

4.  Single wall vent pipe may be used to join an appliance to the venting system, but if proper clearances cannot 

be maintained from combustible materials, Class B Vent Pipe should be used for gas appliances. Refer to 
national or local codes for guidelines.

5. Disconnect power supply before making wiring connections to prevent electrical shock and equipment 

damage.

6.  This equipment is designed to overcome minor negative pressure conditions. To ensure extreme negative 

pressure does not exist, follow the "General Installation Inspection" section of this manual.

7.  Heating appliances equipped with draft hoods, such as boilers or furnaces, LP and natural gas appliances 

SHOULD have a secondary spillage switch installed. On appliances without draft hoods, it is recommended 
that the secondary safety switch GSK-3 be installed into the system. Gas-fi red 30 millivolt power systems 
MUST be equipped with a spillage switch.

Diagram A

P/N 46246300 Rev M 04/20

Summary of Contents for PVG-100

Page 1: ... with pre wired integral 24 VAC Relay Timer factory set Draft Proving Switch and direct access Terminal Blocks 1 Installation Instruction Sheet OPTIONAL SYSTEM COMPONENTS NOT INCLUDED Side Wall Vent Hood Spill Switches Barometric Draft Control CONTENTS PAGE System Operation 2 Power Venter Sizing 3 4 Installation Safety Instructions 4 5 Installation of Power Venter 5 6 General Wiring Instructions 7...

Page 2: ...run the power venter for a period of time after the burner has shut off to purge remaining flue gases UNIT SPECIFICATIONS Table 1 UNIT DIMENSIONS INCHES ELECTRICAL RATINGS MODEL H W D I O VAC Hz RPM WATT AMP TP PVG 100 7 5 10 0 7 0 4 4 115 60 3000 145 2 1 YES PVG 300 7 5 11 5 7 0 4 4 115 60 3000 145 2 1 YES PVG 600 8 75 12 0 8 5 5 5 115 60 3000 167 1 5 YES Inlet and outlet diameter Thermally prote...

Page 3: ...H IN FEET 1 Calculate the total equivalent feet for each type of fitting used in the venting system from the following chart 2 Calculate the total amount of feet for the straight lengths of vent pipe 3 Add the equivalent feet for the fittings with the total amount of feet of straight lengths Table 3 Reducer or increaser ratio d D small diameter divided by the larger diameter See Figure 3 Example 4...

Page 4: ...nded by the National Fuel Gas Code ANSI Z223 1 or refer to the General Installation Inspection section of this manual 3 Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls 4 Single wall vent pipe may be used to join an appliance to the venting system but if proper clearances cannot be maintained from combusti...

Page 5: ...stems shall not be less than 7 above grade when located adjacent to public walkways b A venting system shall terminate at least 3 above any forced air inlet located within 10 c The venting system of other than a direct vent appliance shall terminate at least 4 below 4 horizontally from or 1 above any door window or gravity air inlet into the building d The vent termination of a direct vent applian...

Page 6: ...regulate any draft fluctuations during operation 1 Use approved vent connectors to join the heating appliance outlet to the venter inlet securing each joint with sheet metal screws or equivalent means of fastening when required 2 Seal all pipe joints on the outlet side of the venter with a high temperature silicone adhesive or equivalent Test the vent connections for leaks by using a soap solution...

Page 7: ...r circuit breaker rated at 15 amperes Prevent wiring contact with any heat source Wire the venter in accordance with the National Electrical Code and applicable local codes Refer to Diagram B for proper wiring specifications Diagram B 3 Wire the switch into the low voltage thermostat circuit Refer to the appropriate wiring diagram in this manual 4 After installation check the amperage through the ...

Page 8: ...a heating appliance in accordance with the National Fuel Gas Code ANSI Z223 1 The following procedure will help in evaluation of the venting system It is intended as a guide to aid in determining that the appliance is properly installed and is in a safe condition for continuous use This is a generalized procedure which cannot anticipate all situations Accordingly in some cases deviation from this ...

Page 9: ...nce a year motor should rotate freely To prolong the life of the PVG 600 motor it must be lubricated with six drops of SWG Superlube Part 46226200 annually The PVG 100 and PVG 300 have sealed ball bearings and therefore do not need to be oiled Blower Wheel Inspect the blower wheel annually to clear any soot ash or coating which inhibits either rotation or air flow Remove all foreign materials befo...

Page 10: ...city of the venter selected b A CK 41 Control Kit must be added to the system to properly control the venter when common venting an additional 24 VAC furnace or boiler Tee the draft tube on the PVG unit to connect to the air pressure switch on the Control Kit Refer to Diagram D for wiring instructions PV SERIES POWER VENTER VERTICAL VENTING OPTION Diagram C illustrates correct and incorrect instal...

Page 11: ...L1 L2 TERMINAL STRIP IN 24VAC CONTROL KIT ON SECOND APPLIANCE APPLIANCE CONNECTIONS L1 L2 GAS PRESSURE SWITCH ON MILLIVOLT APPLIANCE PVG WIRING FOR MULTIPLE 24VAC APPLIANCES PVG WIRING FOR MULTIPLE 24VAC APPLIANCES VENTING SYSTEM OPERATIONAL INFORMATION Date Heating appliance BTU HR input Gas valve operation pressure Vent system draft above draft hood or below barometric draft control CO2 measurem...

Page 12: ...m ventCool Field Controls Technical Support Field Controls Technical Support 1 800 742 8368 1 800 742 8368 fieldtec fieldcontrols com fieldtec fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com This manual may be downloaded and printed from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information abou...

Reviews: