MOUNTING CONTROL BOX 

The control box must be mounted within 6’ of the vent damper, and within 
reach of the appliance’s existing damper cable.  If the control box must be 
mounted out of reach of the power venter’s attached wiring, an additional 
installer supplied junction box and wiring (with approves wiring enclosure if 
necessary) will be required. (See Figure 1 & 2) 
1.  Install the flexible conduit connector onto the CK-41P control box and 

secure with fastening nut.  If additional wiring is required, install the 
flexible conduit connector onto the installer supplied junction box. 

2.  Fasten the flexible conduit from the SWG Venter into the conduit 

connector.  Mount the CK-41P control box onto a non-heated vertical 
surface of the appliance or nearby wall or floor joist through the four 
dimpled locations on the base of the box.  NOTE:  

The mounted 

pressure switch diaphragm must be mounted with a vertical orientation; 
see label on pressure switch

. (See Figure 3)  If required, run additional 

wiring as in figure 2 and connect to CK-41P control box, if required, 
using the supplied flexible conduit connector and approved connectors 
and anti-short bushings. 

P

RESSURE 

S

WITCH 

S

ENSING 

T

UBE 

I

NSTALLATION

1.  Attach the 1/4 inch tubing connector to the pressure tube on the SWG 

Venter. (See Fig. 3) 

2.  Connect installer supplied 1/4" O.D. aluminum, copper or stainless steel 

tubing to the tubing connector. 

3.  Route the tubing to the CK-41F junction box and connect the tubing to 

the pressure switch using supplied plastic nut. When routing the tubing, 
avoid kinking the tubing by bending the tubing too sharply. Support the 
tubing at 2’ intervals using installer supplied tube clamps. 

P

ROVING 

S

WITCH 

A

DJUSTMENTS

After proper air flow is established, the pressure switch adjustment is 
made by turning the pressure switch adjustment screw clockwise (See 
Fig. 4) until burner operation stops. Turn the adjustment screw 
counterclockwise until burner ignites. Turn the adjustment screw an 
additional 1/4 to 3/4 turn counterclockwise to ensure adequate switch 
adjustment. 
 

WARNING: 

Failure to properly adjust the pressure switch as specified 

above could lead to improper operation of the pressure switch, which will 
result in a hazardous condition and bodily harm!

 

Figure 1

Figure 2

Figure 3

Figure 4

Summary of Contents for 46457800

Page 1: ...er cable connection ITEMS INCLUDED IN KIT 1 Control box with mounted pressure switch post purge timer and 7 vent damper cable 2 Flexible conduit connector 1 tubing connectors ITEMS NOT INCLUDED IN KIT O D aluminum copper or stainless steel tubing Junction box with connectors and additional circuit wiring if required DO NOT DESTROY THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT WARNING INSTALLER IF ...

Page 2: ... control box if required using the supplied flexible conduit connector and approved connectors and anti short bushings PRESSURE SWITCH SENSING TUBE INSTALLATION 1 Attach the 1 4 inch tubing connector to the pressure tube on the SWG Venter See Fig 3 2 Connect installer supplied 1 4 O D aluminum copper or stainless steel tubing to the tubing connector 3 Route the tubing to the CK 41F junction box an...

Page 3: ...nd B LOW VOLTAGE WIRING INSTRUCTIONS FOR BOILERS 1 Route the appliance s vent damper cable to the CK 41P Plug the cable into the receptacle located inside the CK 41P using the supplied plastic knockout grommet if the cable does not have a conduit connector See Diagram A 2 Connect the CK 41P s pre wired damper cable to the vent damper See Diagram A Snap the end of the flexible conduit into place on...

Page 4: ...ther voltage the appliance is not calling for heat to the CK 41P If there is 24 volts continuously for at least 45 second there should be 115 volts from N to M If not the time relay is defective or L1 and N are not properly wired 2 Flue gas odor a Check system draft Adjust power venter s airflow adjustment damper if necessary b Check for negative pressure in building 3 Venter activates but burner ...

Page 5: ... POST PURGE TIMER M TO 3 ON POST PURGE TIMER OTHERS PER HARNESS COLORS REPAIR AND REPLACEMENT PARTS LIST REPAIR AND REPLACEMENT PARTS LIST DESCRIPTION PART NUMBER Pressure Switch 46273100 Post Purge Timer 46282800 Wire Harness 46457200 ...

Page 6: ..._______ INSTALLER S NAME _____________________________________________________ INSTALLER S COMPANY _________________________________________________ INSTALLER S PHONE NO ________________________________________________ DATE OF INSTALLATION _________________________________________________ CK 41P ...

Page 7: ...Page 7 ...

Page 8: ...Page 8 P N 46457800 Rev B 06 04 ...

Reviews: