WIRING 
CAUTION:

 

Disconnect electrical power when wiring power venter 

Wire the venter motor and controls in accordance with the National Electrical Code, manufacturer's recommendations 
and/or applicable local codes. Units must be grounded. Check ground circuit to make certain that the unit has been 
properly grounded. The wiring should be protected by an overcurrent circuit device rated at 15 amperes. CAUTION must 
be taken to ensure that the wiring does not come into contact with any heat source. All line voltage and safety control 
circuits, between the venter and the appliance, MUST be wired in accordance with the National Electrical Code for class 
one wiring or equivalent methods. Route the venter motor and control wiring with an appropriate wiring method. Refer to 
Wiring Diagrams A and B. 

L

OW 

V

OLTAGE 

W

IRING 

I

NSTRUCTIONS 

F

OR 

B

OILERS

1.  Route the appliance’s vent damper cable to the CK-41P.  Plug the cable into the receptacle located inside the CK-

41P using the supplied plastic knockout grommet (if the cable does not have a conduit connector).  (See Diagram A) 

2.  Connect the CK-41P’s pre-wired damper cable to the vent damper (See Diagram A).  Snap the end of the flexible 

conduit into place on the vent damper conduit bracket. 

 

L

INE 

V

OLTAGE 

W

IRING 

I

NSTRUCTIONS

1.  Verify that the circuit to be supplying power to the CK-41P is disconnected. 
2.  Connect the CK-41P green grounding wire to the circuit’s ground wire. Verify that the control box is properly 

grounded. 

3.  Connect 120 volts hot power source wire to terminal L1 on CK-41P. 
4.  Connect 120 volts neutral power source wire and white wire from venter motor to terminal N on the CK-41P. 
5.  Connect black wire from venter motor to terminal M on the CK-41P. 

Refer to the SWG Venter installation instructions for setting system air flow. 

Diagram A

Summary of Contents for 46457800

Page 1: ...er cable connection ITEMS INCLUDED IN KIT 1 Control box with mounted pressure switch post purge timer and 7 vent damper cable 2 Flexible conduit connector 1 tubing connectors ITEMS NOT INCLUDED IN KIT O D aluminum copper or stainless steel tubing Junction box with connectors and additional circuit wiring if required DO NOT DESTROY THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT WARNING INSTALLER IF ...

Page 2: ... control box if required using the supplied flexible conduit connector and approved connectors and anti short bushings PRESSURE SWITCH SENSING TUBE INSTALLATION 1 Attach the 1 4 inch tubing connector to the pressure tube on the SWG Venter See Fig 3 2 Connect installer supplied 1 4 O D aluminum copper or stainless steel tubing to the tubing connector 3 Route the tubing to the CK 41F junction box an...

Page 3: ...nd B LOW VOLTAGE WIRING INSTRUCTIONS FOR BOILERS 1 Route the appliance s vent damper cable to the CK 41P Plug the cable into the receptacle located inside the CK 41P using the supplied plastic knockout grommet if the cable does not have a conduit connector See Diagram A 2 Connect the CK 41P s pre wired damper cable to the vent damper See Diagram A Snap the end of the flexible conduit into place on...

Page 4: ...ther voltage the appliance is not calling for heat to the CK 41P If there is 24 volts continuously for at least 45 second there should be 115 volts from N to M If not the time relay is defective or L1 and N are not properly wired 2 Flue gas odor a Check system draft Adjust power venter s airflow adjustment damper if necessary b Check for negative pressure in building 3 Venter activates but burner ...

Page 5: ... POST PURGE TIMER M TO 3 ON POST PURGE TIMER OTHERS PER HARNESS COLORS REPAIR AND REPLACEMENT PARTS LIST REPAIR AND REPLACEMENT PARTS LIST DESCRIPTION PART NUMBER Pressure Switch 46273100 Post Purge Timer 46282800 Wire Harness 46457200 ...

Page 6: ..._______ INSTALLER S NAME _____________________________________________________ INSTALLER S COMPANY _________________________________________________ INSTALLER S PHONE NO ________________________________________________ DATE OF INSTALLATION _________________________________________________ CK 41P ...

Page 7: ...Page 7 ...

Page 8: ...Page 8 P N 46457800 Rev B 06 04 ...

Reviews: