Page 4
Diagram A – Typical Furnace Wiring
Diagram B – Boiler Wiring with Aquastat
Page 1: ...ion or company which either in person or through a representative is engaged in and is responsible for the installation and operation of gas appliances who is experienced in such work familiar with al...
Page 2: ...ector Mount the CK 41F junction box or installer supplied junction box onto the wall or floor joist without straining the flexible conduit Fasten the CK 41F junction box through the four dimpled locat...
Page 3: ...fety control circuits between the venter and the appliance MUST be wired in accordance with the National Electrical Code for class one wiring or equivalent methods Route the venter motor and control w...
Page 4: ...Page 4 Diagram A Typical Furnace Wiring Diagram B Boiler Wiring with Aquastat...
Page 5: ...Page 5...
Page 6: ...Page 6 Diagram E...
Page 7: ...e Purge time 1 to 2 min 2 While system is operating disconnect power to the venter motor This should open the pressure switch contacts and stop burner operation TROUBLE SHOOTING HINTS 1 Venter does no...