background image

After determining the location of the venting 
system termination point (See Diagram A), 
cut a square hole through the wall 1" larger 
than the outer pipe diameter of the power 
venter. Mount the power venter through the 
wall, keeping the outer pipe centered in the 
hole. (See Figure 3) Fasten the power 
venter to the outside wall with appropriate 
fasteners. Seal the edges of the power 
venter base plate to the wall with a high 
temperature silicone sealant. DO NOT 
enclose the spaced plates on  the power 
venter body. This will result in reduced cooling of the power venter 
body. Galvanized metal sheets may be installed over surrounding 
building surfaces to protect building materials for degradation by flue 
gases. Brick or tile may be placed on  the ground below the power 
venter to protect the soil and vegetation from the effects of heated 
exhaust air. The power venter should be placed so that vegetation 
and other objects are not in direct contact with the power venter or 
blocking the outlet. Snow should be cleared from the outlet area as 
needed. Wood or vinyl siding should be cut so that the unit mounts 
directly on the wall board to provide a stable support. If the siding is 
greater than 1/2" thick use a spacer plate or board behind the power 
venter mounting plate. (See Figure 4) 

NOTE:

 

If mounting the power venter through a combustible wall material and the 

flue gas temperature is above 400°F at the power venter inlet, line the square 
hole with a piece of corrosion resistant sheet metal or non-combustible material. 
The liner piece should be the same width as the wall section. (See Figure 3) The 
power venter has maximum flue gas temperature of 550°F at the power venter 
inlet. Figure 5 shows how the airflow pattern through an SWG reduces the 
required clearances to combustibles. For installation in wall thickness over 8-
inches, use an SWG Series Through Wall Extension Kit, Model PEK.

 

4.  Remove the end pipe cover screws on the sides of the outside pipe and remove end pipe cover. Then mount the 

backing plate over the outer pipe and route the flexible conduit and pressure switch tube (if applicable) through the 
holes provided in the backing plate. Fasten the backing plate to the inside wall with appropriate fasteners. (See Figure 
6) Re-install end pipe cover and screws. 

 

Diagram A 

Figure 6

Figure 3

Figure 5

Figure 4

Page 5 

Summary of Contents for 46229000

Page 1: ...ivates the power venter at the same time as the burner fires 3 After the heating requirement has been satisfied the thermostat circuit will open and de activate the burner and power venter circuit 4 For venting system equipped with a post purge device the power venter operates for a period of time after the burner has shut off to purge remaining flue gases CONTROL KITS CK 41 For operation with gas...

Page 2: ...tained from combustible materials Class B Vent Pipe should be used for gas appliances and Class L Type Vent Pipe for oil appliances Refer to national or local codes for guidelines 5 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 6 This equipment is designed to overcome minor negative pressure conditions To ensure extreme negative pressure ...

Page 3: ...zing based on appliance maximum input rate not actual firing rate Do not exceed maximum BTU HR input rating or maximum oil GPH input For multiple venting system applications add the input for each appliance Category I gas fired draft induced systems require an SWG 4 HD or larger Category III gas fired draft induced systems require an SWG 5 or larger PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE ...

Page 4: ... insure that the motor and blower wheel rotate freely DO NOT install if any damage is apparent Refer to unit sizing chart to check proper venting sizing 2 Location of the termination of the venting system should be installed in accordance with the National Fuel Gas Code A N S I Z223 1 and or manufacturer s recommendations which are applicable See requirements below or refer to installation locatio...

Page 5: ...ing should be cut so that the unit mounts directly on the wall board to provide a stable support If the siding is greater than 1 2 thick use a spacer plate or board behind the power venter mounting plate See Figure 4 NOTE If mounting the power venter through a combustible wall material and the flue gas temperature is above 400 F at the power venter inlet line the square hole with a piece of corros...

Page 6: ...The horizontal section of the vent pipe should have a slight upward slope from the appliance to the power venter For clearances to combustible materials multiple appliance venting and other installation requirements refer to the National Fuel Gas Code A N S I Z223 1 and or any applicable local codes or appliance manufacturer s installation instructions INSTALLATION USING SINGLE WALL VENT PIPE INST...

Page 7: ... stabilize flue gas temperatures check for negative draft or up draft at the heating appliance outlet or air flow into the draft hood Use a draft gauge velocity meter or match test procedure Adjust the adjustment damper closed to obtain the minimum air flow required to maintain draft Then increase air flow slightly 10 over minimum air flow rate to ensure proper venting For gas fired power burners ...

Page 8: ... Fuel Gas Code A N S I Z223 1 or any applicable local codes for guidance 3 Place in operation the appliance being inspected Follow the lighting instructions and adjust thermostat so appliance will operate continuously 4 Determine that the pilot or burner is operating properly and that the main burner ignition operates satisfactorily by interrupting and re establishing the electrical power of the a...

Page 9: ...er choke plate to insure it is secured in place Check the barometric draft control if installed to insure the gate swings freely 4 System Safety Devices With the heating system operating disconnect the pressure sensing tube from the pressure switch on the CK Kit This will stop the burner operation Re connecting the tube will relight the burner For 30 millivolt operating systems disconnect one lead...

Page 10: ...e circular cover plate with the holes in the motor mount bracket on the motor assembly See Figure 12 2 Slide the motor assembly onto the protruding threaded studs on the venter body with the exhaust chute pointing downward and replace the four nuts securely to the threaded studs See Figure 12 3 Reattach the flexible conduit and wires to the motor and secure the cover on the electrical box 4 Instal...

Page 11: ...Page 11 ...

Page 12: ...PN 46229000 Rev A 08 00 ...

Reviews: