Field Controls 46229000 Manual Download Page 4

Figure 2

E

QUIVALENT 

L

ENGTH 

(F

EET

) O

V

ENT 

P

IPE 

F

OR 

V

ENT 

P

IPE 

F

ITTING

 

VENT PIPE DIAMETER 

VENT PIPE 

FITTINGS 

3” 

4” 

5” 

6” 

7” 

8” 

9” 

10” 

TEE 

19  25  31  38  44  50  56 

63 

90° ELBOW 

11  12  14  16 

18 

45° ELBOW 

d/D 

¼ 

11  14  17  19  22  25 

28 

½ 

10  12  13  15 

17 

SUDDEN 

REDUCER OR 

INCREASER 

FOR THREE 

*RATIOS (d/D) 

¾ 

*Reducer or increaser ratio (d/D) small diameter divided by the larger diameter. 
Example 4" to 8" reducer: The reducer ratio is d/D = 4/8 = 1/2. To estimate the 
equivalent foot length for the fitting, use the smaller pipe diameter for the 
equivalent length. See Figure 2. Example 4" to 8" reducer; the reducer ratio is 1/2 
and the smaller pipe diameter is 4". So, from the chart, the equivalent feet would 
be 7 feet. 

Example: 

System Pipe Size = 4" 

Step 1   Two 4" 90? Elbows @ 7 feet each = 14 Ft. 
Step 2   Ten 2 Foot Lengths of 4" Pipe = 20 Ft. 
Step 3   Total Equivalent Feet = 14 Ft. + 20 Ft. = 34 Ft. 

CAUTION:

 

Failure to install, maintain and/or operate the power venting system in accordance with manufacturer's 

instructions will result in conditions which may produce bodily injury and/or property damage.

 

1.  Remove power venter from box and inspect unit for damage. If the carton has been crushed or mutilated, check unit 

very carefully for damage. Rotate blower wheel to insure that the motor and blower wheel rotate freely. DO NOT 
install if any damage is apparent. Refer to unit sizing chart to check proper venting sizing. 

2.  Location of the termination of the venting system should be installed in accordance with the National Fuel Gas Code, 

A.N.S.I.Z223.1, and/or manufacturer's recommendations which are applicable. See requirements below or refer to 
installation location Diagram A for typical locations. 
a.  The exit termination of mechanical draft systems shall not be less than 7' above grade when located adjacent to 

public walkways. 

b.  A venting system shall terminate at least 3' above any forced air inlet located within 10'. 
c.  The venting system of other than a direct vent appliance shall terminate at least 4' below, 4' horizontally from, or 

1' above any door, window or gravity air inlet into the building. 

d.  The vent termination of a direct vent appliance with an input of 50,000 BTU's per hour or less, shall be located at 

least 9" from any opening through which vented gases could enter the building. With an input over 50,000 BTU's 
per hour, a 12" termination clearance shall be required. 

e.  The vent termination point shall not be installed closer than 3' from an inside corner of an L-shaped structure. 
f. 

The vent termination should not be mounted directly above, or within 3' horizontally from an oil tank vent or gas 
meter. 

g.  The bottom of the vent terminal shall be located at least 12" above finished grade. 

3. 

Page 4 

Summary of Contents for 46229000

Page 1: ...ivates the power venter at the same time as the burner fires 3 After the heating requirement has been satisfied the thermostat circuit will open and de activate the burner and power venter circuit 4 For venting system equipped with a post purge device the power venter operates for a period of time after the burner has shut off to purge remaining flue gases CONTROL KITS CK 41 For operation with gas...

Page 2: ...tained from combustible materials Class B Vent Pipe should be used for gas appliances and Class L Type Vent Pipe for oil appliances Refer to national or local codes for guidelines 5 Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage 6 This equipment is designed to overcome minor negative pressure conditions To ensure extreme negative pressure ...

Page 3: ...zing based on appliance maximum input rate not actual firing rate Do not exceed maximum BTU HR input rating or maximum oil GPH input For multiple venting system applications add the input for each appliance Category I gas fired draft induced systems require an SWG 4 HD or larger Category III gas fired draft induced systems require an SWG 5 or larger PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE ...

Page 4: ... insure that the motor and blower wheel rotate freely DO NOT install if any damage is apparent Refer to unit sizing chart to check proper venting sizing 2 Location of the termination of the venting system should be installed in accordance with the National Fuel Gas Code A N S I Z223 1 and or manufacturer s recommendations which are applicable See requirements below or refer to installation locatio...

Page 5: ...ing should be cut so that the unit mounts directly on the wall board to provide a stable support If the siding is greater than 1 2 thick use a spacer plate or board behind the power venter mounting plate See Figure 4 NOTE If mounting the power venter through a combustible wall material and the flue gas temperature is above 400 F at the power venter inlet line the square hole with a piece of corros...

Page 6: ...The horizontal section of the vent pipe should have a slight upward slope from the appliance to the power venter For clearances to combustible materials multiple appliance venting and other installation requirements refer to the National Fuel Gas Code A N S I Z223 1 and or any applicable local codes or appliance manufacturer s installation instructions INSTALLATION USING SINGLE WALL VENT PIPE INST...

Page 7: ... stabilize flue gas temperatures check for negative draft or up draft at the heating appliance outlet or air flow into the draft hood Use a draft gauge velocity meter or match test procedure Adjust the adjustment damper closed to obtain the minimum air flow required to maintain draft Then increase air flow slightly 10 over minimum air flow rate to ensure proper venting For gas fired power burners ...

Page 8: ... Fuel Gas Code A N S I Z223 1 or any applicable local codes for guidance 3 Place in operation the appliance being inspected Follow the lighting instructions and adjust thermostat so appliance will operate continuously 4 Determine that the pilot or burner is operating properly and that the main burner ignition operates satisfactorily by interrupting and re establishing the electrical power of the a...

Page 9: ...er choke plate to insure it is secured in place Check the barometric draft control if installed to insure the gate swings freely 4 System Safety Devices With the heating system operating disconnect the pressure sensing tube from the pressure switch on the CK Kit This will stop the burner operation Re connecting the tube will relight the burner For 30 millivolt operating systems disconnect one lead...

Page 10: ...e circular cover plate with the holes in the motor mount bracket on the motor assembly See Figure 12 2 Slide the motor assembly onto the protruding threaded studs on the venter body with the exhaust chute pointing downward and replace the four nuts securely to the threaded studs See Figure 12 3 Reattach the flexible conduit and wires to the motor and secure the cover on the electrical box 4 Instal...

Page 11: ...Page 11 ...

Page 12: ...PN 46229000 Rev A 08 00 ...

Reviews: