background image

 

will only run in the manual mode while the green button is 
held in. 

To operate the pump in automatic mode, just ensure that 
the red pushbutton is in the “ON” position (pulled out).  The 
pump will start running automatically when the fuel level is 
low and will illuminate the green run lamp.  When the tank 
is full, the pump is turned off and the green lamp is 
extinguished. 

The red lamp will illuminate if there has been an electrical 
overload. 

Care must be taken to ensure that the pump is primed with 
fuel prior to operation to lubricate the seals.  Also, the 
pump should never be run when the bulk tanks are empty 
or when valves on the fuel fill lines are closed. 

4.5.4 Meters/Gauges:

 The following additional meters or 

gauges may be fitted to the control panel: 

3 Ammeters

 mounted on the panel instead of one ammeter 

and a selector switch.  This allows a continuous indication 
of the current flowing in each phase, not applicable for 
PowerWizard as module will display all phase currents. 

Kilowatt (kW) Meter

 to provide accurate readings of the 

load being supplied by the generating set, not applicable 
for PowerWizard as the PowerWizard 2.0 can display 
kilowatts. 

Combined Tachometer and Frequency Meter

 to replace 

the standard frequency meter. This meter allows both 
engine speed in revolutions per minute (RPM) and output 
frequency to be indicated on the front panel, not applicable 
for PowerWizard as module will display RPM and Hz. 

Lube Oil Temperature Gauge

 to monitor the lubricating oil 

temperature when the engine is operating.  The normal 
operating temperature should be approximately 90° - 110° 
C (195° - 230°F), not applicable for PowerWizard 2.0 as 
the module will display this. 

Ammeter for Battery Trickle Charger

 to monitor the current 

flow to the battery.  It is used to observe the charging 
current being supplied by the battery trickle charger.  
When the batteries are fully charged this current will be 
small (less than 5 Amps) but with a partially discharged 
battery this current may be as high as 40 Amps. 

4.5.5 Speed/Voltage Control:

 Three controls may be 

fitted to adjust the speed or voltage of the generating set:  
Speed Adjust Potentiometer, a Raise/Lower Switch and a 
Voltage Adjust Potentiometer.  These should only be 
adjusted by a qualified generating set technician according 
to instructions in the Technical Manual.  For some 
electronic engines, speed can be adjusted on the 
PowerWizard 2.0 module. 

4.5.6 Alarm Signalling:

 Three options may be fitted to the 

control panel to supplement the standard alarm indications 
of the alarm lamps: 

panel mounted alarm siren

  will sound when an alarm 

condition is indicated.  An Alarm Mute pushbutton is fitted 
on the panel to silence the siren. 

An 

audible alarm siren supplied loose

  will sound when an 

alarm condition is indicated.  It can be fitted at a 
convenient location.  An Alarm Mute pushbutton is fitted on 
the panel to silence the siren. 

set of volt free contacts for common alarm

 change over 

in the event of an alarm condition.  These are for 
connection to an existing alarm system.  These contacts 
remain in the "alarm" state until the control system is reset. 

4.5.7 Automatic Preheat Control:

 glow plugs operates 

automatically prior to and during engine cranking.  The 
automatic cranking sequence will be delayed by the 
preheating period.  

4.5.8 Remote Annunciator Panels:

 8 or 16 channel 

remote annunciators may be fitted and connected  to 4001 
and 4001E Series Control Systems.  These provide repeat 
indicators for the shutdown and alarm fault lamps on the 
control panel.  They also include an audible alarm and 
alarm mute button. 

Two further options may be fitted with the above remote 
annunciators: A Normal/Run switch allows manual starting 
of the set from the remote location and an Emergency 
Stop Pushbutton allows manual stopping. 

For PowerWizard 2.0 panels, a 16 channel remote 
annunicator may be fitted that has an audible alarm and 
alarm mute button. 

4.5.9 X100 AMF Upgrade:

 When the generating set is 

installed to automatically provide standby power in the 
event of mains failure, a load transfer switch is required.  
This switch transfers the load from the mains after a failure 
and puts the load on the operating generating set. After the 
mains are re-established, the load is transferred back to 
the mains.   

To accomplish this, one option is to utilise a dedicated TC 
Series or ATI Series Load Transfer Panel as discussed in 
Section 4.6.  However, the X100 option provides this 
functionality in the control panel itself, so an independent 
transfer switch can be used.  

A 2001, 4001 or 4001E Series Panel fitted with the X100 
option is often referred to as a 2101, 4101 or 4101E Series 
Panel, respectively.

  

 
The X100 upgrade adds a status display panel to the 
control panel as shown in Figure 4.2.  This provides 
indication of Mains Available, Mains on Load, Generator 
Available and Generator on Load.  A test switch is 
provided for maintenance. 

 

 

Item 

Description 

 

 

 

 

1. 

“Generator Available” Status Lamp 

 

2. 

“Generator On Load” Status Lamp 

 

3. 

Lamp Test Pushbutton 

 

4. 

“Mains on Load” Status Lamp  

 

5. 

“Mains Available” Status Lamp 

 6. 

Test 

Switch 

Figure 4.2: Typical X100 Status Display Panel 

The X100 operates as follows: 

On mains failure, the generating set is automatically 
started and the contactors closed to connect the load to 
the generator. 

On restoration of mains power, the load is transferred back 
to the mains.  After a cool down period, the generator set 
is automatically shut down. 

The Test Switch mounted on the control panel allows 
testing of the system for maintenance purposes. 

Two additional options may be fitted with X100: 

PRM1 

Electronic Mains Monitoring Relay - This relay is 

essential when an independent  load transfer panel is not 
fitted with a mains monitoring relay. 

PST1 

Manual/Auto Retransfer Selector Circuit - This 

option, if fitted, enables the operator to manually control 
the timing of the retransfer of  the load from the generating 
set to the restored mains supply.  The controls comprise a 
Manual/Auto Retransfer Selector Switch and a Retransfer 
Button.  On a mains failure, the generating set will start 
and accept load in the normal sequence.  With the 
Retransfer Selector Switch in the “AUTO” position the load 
will be automatically retransferred back to the mains when 
available as described above.  If the Retransfer Selector 
Switch is in the “MANUAL” position, on restoration of the 
mains, the “Mains Available” indicator will illuminate but 

 

9

Summary of Contents for OLYMPIAN 1001 Series

Page 1: ...GENERATING SET OPERATOR S MANUAL ...

Page 2: ...i ...

Page 3: ... otherwise operating the generating set The Generating Set Technical Operation and Maintenance Manual the Engine Manual and the Alternator Manuals are designed for qualified generating set technicians for installation maintenance and trouble shooting of the set Document PWPO1 GB Issue Date 02 09 Part Number 277 584 ii ...

Page 4: ...rol System Fault Finding Trouble Shooting Guide 1001 2001 4001 4001E 11 4 7 Control System Fault Finding Trouble Shooting Guide PowerWizard Panels 13 4 8 Load Transfer Panels 19 4 9 Engine Interface Module Description 19 4 10 Output Circuit Breaker Description 19 5 OPERATION 20 5 1 General 20 5 2 Pre Start Checks applicable to all control systems 20 5 3 Normal Startup Shutdown Key Start Panel 1001...

Page 5: ...ting set room is properly ventilated Keep the room the floor and the generating set clean When spills of fuel oil battery electrolyte or coolant occur they should be cleaned up immediately Never store flammable liquids near the engine Store oily rags in covered metal containers Do not smoke or allow sparks flames or other sources of ignition around fuel or batteries Fuel vapours are explosive Hydr...

Page 6: ...e chest to rise Let the chest fall completely Give breaths at a rate of 10 per minute 4 If the victim must be left to get help give 10 breaths first and then return quickly and continue 5 Check for pulse after every 10 breaths 6 When breathing restarts place the victim into the recovery position described later in this section IF NO BREATHING AND NO PULSE 1 Call or telephone for medical help 2 Giv...

Page 7: ...trical power is produced by an alternator fine tuned to the output of this generating set The engine and alternator are coupled together and mounted on a heavy duty steel baseframe Except for the largest sets this baseframe includes a fuel tank with a capacity of approximately 8 hours operation at full load An extended capacity fuel tank of approximately 24 hours operation may be fitted instead Th...

Page 8: ...ing set is running ensure that the AC voltmeter selector switch is not in the OFF position 2 AC VOLTMETER SELECTOR SWITCH A selector switch allowing the operator to select voltage reading between phases or between a phase and neutral The OFF position allows the voltmeter zero position to be checked while the generating set is running 3 AC AMMETER An ammeter that indicates the AC electrical current...

Page 9: ...ents the red light will turn off 6 ALARM ACKNOWLEDGMENT SILENCE Pressing the Acknowledge key will cause the horn relay output to turn off and silence the horn Pressing the key will also cause any yellow or red flashing lights to turn off or to become solid depending on the active status of the alarms The Acknowledge key may also be configured to send out a Global Alarm Silence on J1939 Data Link w...

Page 10: ...p position When shutting down the generating set the load should be turned off by switching the alternator output circuit breaker to OFF handle down The engine should be allowed to cool prior to stopping it After a few minutes the Key Switch is turned to Position O Off which shuts the generating set down In case of emergency where immediate shutdown is necessary the Key Switch should be turned to ...

Page 11: ...7 14 EMERGENCY STOP 1001 Series Panel 2001 Series Panel 4001 Series Panel 4001E Series Panel PowerWizard Series Panel Figure 4 1 Diagram of Typical Control Panels ...

Page 12: ...een reset When low oil pressure is sensed the generating set is automatically shut down The RED SHUTDOWN LIGHT will begin to flash until the ACKNOWLEGE key is pressed The RED SHUTDOWN LIGHT will stay on until the fault has been resolved on the generating set the LOW OIL PRESSURE shutdown event has been reset Engine speed is monitored by the speed sensor in the fly wheel housing of the generating s...

Page 13: ... system is reset 4 5 7 Automatic Preheat Control glow plugs operates automatically prior to and during engine cranking The automatic cranking sequence will be delayed by the preheating period 4 5 8 Remote Annunciator Panels 8 or 16 channel remote annunciators may be fitted and connected to 4001 and 4001E Series Control Systems These provide repeat indicators for the shutdown and alarm fault lamps ...

Page 14: ...out in two triangular formations These give indication of which phase voltage or current is being measured In the case of the voltmeter one LED illuminated indicates the phase to neutral voltage for that particular phase If two LED s are illuminated then the voltage shown is the phase to phase voltage for these two phases Only one LED will be illuminated below the ammeter This LED shows which phas...

Page 15: ...EED fault lamp will also illuminate after the Emergency Stop Pushbutton has been depressed even though there has been no overspeed condition The Emergency Stop Pushbutton and any remote stop buttons must be released before the fault can be cleared 1 Refer to a qualified generating set technician Engine Stops Due to High Lube Oil Temp Optional Shutdown HIGH LUBE OIL TEMP Fault Lamp Illuminates 1 Re...

Page 16: ...2 Refer to a qualified generating set technician Alarm for Low Coolant Temp Optional Alarm 2001 4001 4001E Series Only LOW COOLANT TEMP Alarm Lamp Illuminates 1 Check that the immersion heaters are switched on and are operating 2 Refer to a qualified generating set technician Generating Set Does Not Go On Load All control systems Generating Set is Running but the Load is Not Being Powered 1 Check ...

Page 17: ...ssed or the Stop key is held down for 5 seconds and Cooldown time is skipped 2 Refer to a qualified generating set technician Engine Stops Due to Low Oil Pressure Low Oil Pressure in event log Red Shutdown LED Illuminates 1 Refer to a qualified generating set technician Engine Stops Due to High Coolant Temp High coolant temp in event log Red Shutdown LED Illuminates 1 Refer to a qualified generati...

Page 18: ...sed 3 Check Circuit Breaker is on handle up 4 Refer to a qualified generating set technician Alarm for Approaching High Engine Temp APPROACHING HIGH COOLANT TEMP Alarm in event Log Amber LED Illuminates 1 Refer to a qualified generating set technician Alarm for approaching low oil pressure APPROACHING LOW OIL PRESSURE Alarm in event Log Amber LED Illuminates 1 Refer to a qualified generating set t...

Page 19: ...nce in circuit 114 Engine coolant temperature signal out of range low Defaults to 180 F 82 C Signal voltage less than 0 127V Short circuit to earth 115 Engine coolant temperature signal out of range high Defaults to 180 F 82 C Signal voltage greater than 4 6V Open circuit Sensor failure 121 Manifold air pressure signal out of range high Defaults to ECM setting Low power Slow acceleration Signal vo...

Page 20: ...test in engine off test only Open circuit or short circuit to earth 244 Engine data link failed open circuit test Output circuit test in engine off test only Open circuit or short circuit to earth 254 Open circuit test out of range high High voltage during open circuit test 255 Open circuit test out of range low Low voltage during open circuit test 311 Engine oil temperature signal out of range lo...

Page 21: ... high to low 451 Number 1 injector unit short circuit to B or earth high Found by the ECM Injector unit electrical wiring loom shorted to earth low 452 Number 2 injector unit short circuit to B or earth high Found by the ECM Injector unit electrical wiring loom shorted to earth low 453 Number 3 injector unit short circuit to B or earth high Found by the ECM Injector unit electrical wiring loom sho...

Page 22: ...ting code and ECM do not match ECM programming fault Components not compatible 621 Engine using default rating Engine operates AL25 HP default ECM installed but not programmed 622 Engine using field default rating Engine limited to 160 HP Options not available ECM installed but not programmed 623 Invalid engine rating code ECM not programmed correctly 624 Field default active Programming problem E...

Page 23: ...he mains the Mains Available indicator will illuminate but the generator will continue to supply load When it is convenient for retransfer to take place the operator presses the Retransfer Button which causes the load to be transferred back to the mains and after a cool down period automatically shuts down the generator 4 8 2 TC Compact Load Transfer Panel The TC Compact Load Transfer Panel is des...

Page 24: ... replace as necessary 6 Check the battery terminals for corrosion clean as necessary WARNING When working with the batteries do not smoke or use an open flame in the vicinity Hydrogen gas from batteries is explosive Do not short the positive and negative terminals together 7 Check the battery electrolyte level fill with distilled water as necessary 8 Check the control panel and the generating set ...

Page 25: ...e engine fires The engine will automatically crank up to 3 times or until the engine fires If the engine does not fire the control system locks out on FAIL TO START and illuminates a fault lamp on the control panel If this happens refer to the trouble shooting guide in Section 4 5 or a qualified generating set technician to determine the cause of failure to start WHEN ENGINE HAS STARTED 3 Check fo...

Page 26: ...y abnormally high temperature or abnormally low oil pressure Pressing the ENGINE OVERVIEW key will display these readings The oil pressure should be in the normal range within 10 seconds of starting 6 Switch the Alternator Output Circuit Breaker to ON handle up 7 Shutdown To shut the generating set down turn off the load by switching the alternator Output Circuit Breaker to OFF handle down Press t...

Page 27: ...spheric pollution Dealing with lead acid batteries can be hazardous so it is important to follow all safety guidelines Battery acid can burn clothing and skin and even cause blindness if it leaks so wear protective clothing when inspecting a battery prior to its disconnection transportation Disconnect the battery safely before inspecting it see below Before removing a battery carry out a thorough ...

Page 28: ...24 HAZARD LABEL LEGEND Some or all of these hazard warning labels will appear on your generating set ...

Page 29: ...werWizard 8 Functional Description PowerWizard Control Systems 8 Gauges 9 Heaters 8 Hours Run Meter 4 Key Switch 4 Load Transfer Panels 19 Maintenance 22 Meters 9 Normal Manual Startup Shutdown 22 Oil Pressure Gauge 4 Overspeed Signal EIM Plus only 19 Panel Equipment 4 5 PowerWizard 5 PowerWizard Autostart Panels 22 Pre Start Checks 20 Rating Label 3 Remote Annunciator Panels 9 Safety 1 Chemical 1...

Reviews: