background image

1.

Before  teaching  in  the  EDIT  mode,  select  the  desired  switching  function
(threshold  value  or  window  comparator) 

è

  chapter  5.4.  EDIT  mode.

Threshold  comparator

Window  comparator

The  (taught)  switching  point  is  derived  from
the  average  value  of  both  measurement  values
SP  =  1/2  (Flow  1  +  Flow  2)
Special  case:  SP  =  Flow  1  =  Flow  2

The  taught  switching  window  is  derived  from
the  measurement  values:
SP.Lo  =  Flow  1
SP.Hi  =  Flow  2

Fig.19

For  teaching  the  switching  variables:
2.

Generate  a  flow  (Flow  1)

3.

First  press  the  A  button  and  then  also  the  Edit  button.
[Out  A]  and  bar  display  flash  and  the  measurement  value  is  taken  over  as  the
first  Teach  point  or  [Lock]  flashes  if  security  blocking  is  active.

Only  with  active  security  blocking  [Lock]:
4.

Press  the  A/B  buttons  until  the  chosen  security  code  is  set.

5.

Press  the  Edit  button.
[Out  A]  and  the  bar  display  flash  and  the  measurement  value  is  taken  over  as
the  first  Teach  point.

6.

Generate  a  second  flow  (Flow  2)

7.

First  press  the  A  button  and  then  also  the  Edit  button.
The  second  Teach  point  is  taken  over  and  the  switching  point  (SP)  or
switching  points  (SP.Lo  and  SP.Hi)  become  valid.
The  SFAB  is  in  the  RUN  mode.

5.6 RECORDER  mode

Fig.20

In  the  RECORDER  mode,  a  manual  accumulated  air  consumption  measurement  can
be  performed.
1.

Press  the  A  button  and  B  button  at  the  same  time.
The  SFAB  is  in  the  RECORDER  mode.
The  status  of  the  air  consumption  measurement  [Run]  or  [Stop]  is  displayed.

2.

If  [Stop]  is  displayed,  press  the  A  button.
[Run]  with  a  running  light  is  displayed.  The  air  consumption  measurement  is
started.

3.

Press  the  A  button  again.
[Stop]  is  displayed.  The  air  consumption  measurement  is  stopped.

4.

Press  the  A  button  and  B  button  at  the  same  time.
The  SFAB  is  in  the  RUN  mode.

Note

If  the  RECORDER  mode  is  left  during  an  ongoing  air  consumption  measurement
[Run],  the  air  consumption  measurement  will  continue  in  the  background.

Resetting  measurement  value  to  zero.

· Press  the  B  button  in  the  RECORDER  mode  to  reset  a  measurement  value  to

zero.

6

Operation

Important:

Excessive  internal  heat  will  destroy  the  SFAB.
· Avoid  high  cycle  frequencies  with  large  pressure  amplitudes.  Otherwise,  the

admissible  limit  temperatures  of  the  used  materials  will  be  exceeded.

The  air  mass  stream  displayed  by  the  SFAB  refers  to  the  standard  conditions  that
were  set  under  Options  in  the  special  menu.
When  comparing  volume  flows:
· Make  sure  that  the  volume  flows  to  be  compared  (e.g.operating  volume  flow,

amount  supplied  by  a  compressor,  measured  values  of  a  flow  sensor  from
another  manufacturer)  refer  to  the  same  basic  conditions.

· After  the  power  supply  is  switched  on,  the  SFAB  needs  a  warm−up  time  of 

5  minutes  until  it  achieves  the  specified  accuracy.

6.1 Resetting  the  SFAB  to  the  factory  settings

(also  if  the  security  code  cannot  be  found)

Note

The  current  settings  will  be  lost  after  a  reset  to  the  factory  setting.  If  necessary,
make  a  note  of  these  settings  before  a  reset.

To  reset  the  SFAB  to  factory  setting,  proceed  as  follows:
1.

switch  off  the  operating  voltage

2.

Press  all  three  setting  elements  (A  button  +  B  button  +  Edit  button)
simultaneously  and  hold  them  down.

3.

Switch  the  operating  voltage  back  on.
The  SFAB  is  in  the  RUN  mode.

7

Care  and  maintenance

· Switch  off  the  following  sources  of  energy  before  cleaning  the  exterior  of  the

device:
 the  operating  voltage
 the  compressed  air  supply.

· If  necessary,  clean  the  exterior  of  the  SFAB.

Permitted  cleaning  agents  are  soap  suds  (max.  +60  °C),  petroleum  ether  and  all
non−abrasive  agents.

8

Dismantling

1.

Switch  off  the  following  sources  of  energy  before
dismantling:
 operating  voltage
 compressed  air.

2.

Disconnect  the  respective  connections  from
the  SFAB.

3.

In  the  case  of  hat  rail  or  wall  fitting,  remove
the  SFAB  as  shown  here.

4.

With  plate  fitting:  Loosen  the  two  fastening
screws.

Fig.21

9

Eliminating  faults

Fault

Possible  cause

Remedy

Incorrect  measurement
display

SFAB  operated  with
non−permitted  medium

Operate  SFAB  only  with
permitted  media

display

SFAB  contaminated

Replace  device

With  flow  measurement:
Measured  value  is

Measurement  outside  permitted
measuring  range

Accuracy  refers  only  to  the
permitted  measuring  range

Measured  value  is
displayed  flashing

Incorrect  flow  direction

Correct  the  tubing 

è

  chapter  4.2

With  air  consumption
measurement:
Measured  value  is
displayed  flashing

Measuring  range  end  value  is
exceeded  at  least  once.  Specified
accuracy  cannot  therefore  be
maintained.

Make  sure  that  the  measurement
range  limit  value  is  not  exceeded

Outputs  do  not  switch
according  to  the  setting.

Short  circuit/overload  at  relevant
output

Eliminate  short  circuit/overload

Settings  cannot  be
edited  (Lock)

Access  protection  active

Enter  the  security  code

O.FLO

Measurement  range  exceeded 
(is  displayed  in  the  RUN  mode)

Check  operating  conditions

Er1,  Er2,  Er3

Device  defective

Replace  device

Er9

Measurement  range  fallen  below
(is  displayed  in  the  RUN  mode)

Check  operating  conditions

Er10

Measurement  range  exceeded 
(is  displayed  in  the  RUN  mode)

Check  operating  conditions

Er17

Undervoltage

Maintain  operating  voltage

g

Check  electrical  wiring

Fig.22

10

Accessory

Select  the  appropriate  accessories  from  our  catalogue.

è

www.festo.com/catalogue/SFAB

Summary of Contents for SFAB-10U

Page 1: ...ing systems or end devices in industry suitable media è chapter 11 Technical specifications Measurement is carried out by means of a thermal procedure The amount of heat which is drawn from a heated surface of the sensor by the medium flowing through it is calculated here Through the amount of heat removed the flow or accumulated air consumption is determined and shown on the display The connectio...

Page 2: ... hoses into the PlugInconnections of connection 1 and connection 2 è Marking on the product Note If the hoses are connected to the SFAB incorrectly the measurement values will flash in the display 4 3 Electrical connection Warning Use only power units which guarantee reliable electrical isolation of the operating voltage as per IEC DIN EN 60204 1 Observe also the general requirements for PELV powe...

Page 3: ...ate can be reached from other modes by pressing Edit button for 3 seconds or passage of a monitoring time timeout 1 Switch on the operating voltage The SFAB is in the RUN mode 2 Check the settings of the SFAB è chapter 5 3 SHOW mode 5 1 Icons for representing the menu structure Icon Meaning Automatic return to the basic status RUN mode when the monitoring time has expired here 80 seconds In order ...

Page 4: ...g impulse CI switching element function no nc closer opener minimum flow value F Lo Flow Low In order to delete the minimum value press the EDIT button briefly maximum flow value F Hi Flow High In order to delete the maximum value press the EDIT button briefly The following settings are displayed for OUT B the switching function threshold value or window comparator switching point SP switching poi...

Page 5: ...s 8 Set the value for the hysteresis Hy with the A B buttons 9 Press the Edit button to confirm the set value no or nc flashes 10 Select the switching element function no nc with the A B buttons 11 Press the Edit button to confirm the set value The SFAB is in the RUN mode Carry out a test run with various flows to ascertain whether the SFAB switches as desired switching points and hysterisis b Set...

Page 6: ...IG F with the currently chosen value flashes The digital filter can be set d Setting smoothing for the digital filter The display values can be smoothed with the digital filter The degree of smoothing can be set in 6 steps from d1 low smoothing to d6 maximum smoothing With increasing smoothing the switch on switch off time of the switch outputs rises With d OFF the response time of the analogue ou...

Page 7: ...a flow sensor from another manufacturer refer to the same basic conditions After the power supply is switched on the SFAB needs a warm up time of 5 minutes until it achieves the specified accuracy 6 1 Resetting the SFAB to the factory settings also if the security code cannot be found Note The current settings will be lost after a reset to the factory setting If necessary make a note of these sett...

Page 8: ... 0 Ū 10 Max load resistance at current output Ohm 500 Min load resistance at voltage output kOhm 10 Rise time ms 15 30 60 factory setting 125 250 500 999 adjustable Output additional data Protection against short circuit yes Protection against overloading yes Electronics Operating voltage range DC V 15 Ū 30 Protection against polarity reversal for all electrical connections Electromechanics Electr...

Reviews: