Setting "HOLD/STOP"
(error reaction of the outputs)
The reaction of the outputs to an error (transmis-
sion error on the FIPIO-field bus or interruption
in the field bus cable) can be set as follows:
DIL-Switch
Error reaction of outputs
STOP
*)
HOLD
*) Factory setting
Fig. 3/6: Setting "HOLD/STOP"
DIL switch 1
Error reaction
OFF
(STOP mode)
All outputs will be switched off if
there is an error (valves and
electrical outputs).
ON
(HOLD mode)
All outputs retain their current
status if there is an error (valves
and electrical outputs).
VIFB16 - 03/05
3. Installation
0506b
3-13