When using additional proximity
sensors:
 Place the proximity sensors in

the corresponding grooves. Cov­
er rails over the grooves fasten
the cables and protect them
against dirt.

 During assembly, maintain the

required minimum distances
from ferrous materials.

Fig. 6

7.2 Electrical installation

Warning

 Use only power sources which guarantee reliable electrical isolation of

the operating voltage in accordance with IEC/DIN EN 60204-1. Observe
also the general requirements for PELV power circuits in accordance with
IEC/DIN EN 60204-1.

Note

Installation errors can damage the electronics or cause malfunctions.
 Make sure that the length of the signal line does not exceed the maximum

permissible length of 15 m.

 Connect the earth terminal (Fig. 1 

9

 ) to the earth potential with low imped­

ance (short cable with large cross-section) – tightening torque 5 Nm ± 10 %.

 Dimension pneumatic lines and electric cables sufficiently.
 Use an electric connecting cable, with at least 5 wires, with an outside dia­

meter of Fig. 7 – conductor cross-section [mm²]: 0.75 … 1.5.

 Recommendation: For the DFPI-...-C1V-P-A, use the pre-assembled connecting

cable NHSB with protective conduit according to accessories 
(

è

 www.festo.com/catalogue).

Type

Outside diameter [mm]

DFPI

-...-

C1V-A

 

è

 

Fig. 8

4.5

 … 

10

DFPI

-...-

C1V-

P

-A

 

è

 

Fig. 9

6.5 

 8

Fig. 7

The electrical connection is concealed by the flange receptacle (

è

 Fig. 1). 

To perform electrical installation you will have to dismantle the flange receptacle.

For DFPI-...-ND2P-C1V-A

1

Mounting screws – tightening
torque 1.4 Nm ± 10 %

2

Seal

3

Tightening torque 
0.3 Nm ± 10 %

4

Tightening torque 
1.5 Nm ± 10 %

5

Tightening torque 
3.5 Nm ± 10 %

Fig. 8

1

2

3

4

5

For DFPI-...-ND2P-C1V-P-A (protected pneumatic connections)

1

Mounting screws – tightening
torque 2.7 Nm ± 10 %

2

With guided air vent: plug
screw with sealing ring
(mounted at factory); With
on-site air vent: filter nipple or
silencer (accessories)

3

Seals (O-rings)

4

Mounting thread (M32 x 1.5)
for connection line
(accessories) – tightening
torque 7 Nm ± 10 %.

Fig. 9

1

2

3

4

1. Loosen the mounting screws of the flange receptacle (

è

 Fig. 9 

or Fig. 8 

1

 )

and carefully remove the flange receptacle.

2. For DFPI-C1V-A: If necessary, loosen the cable conduit fitting (

è

 Fig. 8 

3

 ).

For DFPI-C1V-P-A: 

è

 Assembly instructions for connecting cable (accessories).

3. Route the electric cable through the flange receptacle.
4. If necessary, loosen the socket strip of the electrical connection, which is

fastened with two screws.

5. Use the wire end sleeves suitable for the connection and wire the socket strip

according to the pin allocation (

è

 Fig. 10) – tightening torque 0.22 … 0,25Nm.

The integrated positioner is supplied with operating voltage and the setpoint
signal via the 5-pin plug connector.

Pin

Allocation

Connection

1

Power supply

 

24 V DC

1)

5

1

2

Input analogue setpoint value 4 … 20 mA

2)

3

GND Power supply/Input/Output

4

Output analogue actual value 4 … 20 mA

2)

5

Input initialisation 24 V DC

1)

Permissible operating voltage range 

è

 Technical data in section 13

2)

Reference between position and analogue value is dependent on the initialization (

è

 Fig. 13)

Fig. 10

6. Carefully plug the wired-up socket strip onto the plug connector.
7. Fasten the socket strip with the two screws – tightening torque 0.5 Nm ± 10 %.
8. Mount the flange receptacle. When doing so, make sure that the seals are cor­

rectly seated – tightening torque 

è

 Fig. 8 or Fig. 9.

9. For DFPI-...-ND2P-C1V-A: Retighten the cable conduit fitting – tightening torque

è

 Fig. 8.

For DFPI-...-ND2P-C1V-P-A  before tightening the cable conduit fitting (accessories)
you first have to perform the pneumatic installation (

è

 section 7.3).

7.3 Pneumatic installation

 Check the necessity of an emergency compressed air supply and of non-return

valves. You will then avoid sudden compensating movements of the piston rod if
there is a drop in pressure and a sudden sliding down of the moving load in a
vertical or inclined mounting position.

For DFPI-...-ND2P-C1V-A

1. If necessary, remove the adhesive labels from the supply ports.
2. Use only suitable threaded connectors – pneumatic connection G¼.
3. Connect the tubing of the DFPI to the compressed air connections (

è

 Fig. 1).

– Connection P: compressed air supply port for operating pressure
– Connection R: exhaust port

For DFPI-...-ND2P-C1V-P-A (protected pneumatic connections)

 Use the pre-assembled connecting cable NHSB with protective conduit accord­

ing to accessories or externally calibrated pneumatic connection lines with the
following outside diameter:
– Connection P: 8 mm; connection R: 10 mm

The flange receptacle has two threaded holes (

è

 Fig. 11). Push-in fittings are

pre-assembled in the factory (included in scope of delivery).
1. If necessary, loosen the cable conduit fitting (

è

 assembly instructions of the

accessories).

2. Remove the blanking plugs from the push-in fittings, if necessary.

1

Pneumatic connection P

2

Pneumatic connection R,
(guided exhaust)

3

From the plant: plug screw G¼
Optional – for on-site air vent:
filter nipple G¼ or silencer G¼
(accessories)

4

Passage for electric cables

Fig. 11

1

2

3

4

3. Decide whether the air vent should be made on site or guided.

For guided air vent:

At the factory, the plug screw (

è

 Fig. 11 

3

 ) is already mounted and the

DFPI-...-C1V-P-A is thus prepared for guided air venting.
 If the plug screw has been dismounted: Reseal the connection for air vent on

site with sealing ring and plug screw – tightening torque 13.5 Nm.

 Connect the tubing of the DFPI to the connections P and R (

è

 Fig. 11)

Insert

the compressed air tubing into the push-in fitting up to the stop.

For on-site air venting directly at the DFPI:

 Seal the unused connection R (

è

 Fig. 11 

2

 ) with the plug (accessories).

 Open the connection for on-site air vent by dismounting the plug screw

(

è

 Fig. 11 

3

 ).

 Screw a filter nipple G¼ (for air vent without silencer) or a silencer G¼ (acces­

sories) into the connection for on-site air vent (

è

 Fig. 11 

3

 ) – tightening

torque 4 Nm ± 10 %.

4. Connect tubing to the DFPI at the connection P by inserting the compressed air

tubing into the push-in fitting up to the stop.