background image

8099693

CPX-AP-I-PN-M12

PROFINET interface

8099693
2019-06
[8099695]

Instructions | Operat-
ing

Summary of Contents for CPX-AP-I-PN-M12

Page 1: ...8099693 CPX AP I PN M12 PROFINET interface 8099693 2019 06 8099695 Instructions Operat ing...

Page 2: ...Translation of the original instructions PI PROFIBUS PROFINET is a registered trademark of its respective trademark holder in certain coun tries 2 Festo CPX AP I PN M12 2019 06...

Page 3: ...nformation 5 4 Service 5 5 Product overview 6 5 1 Function 6 5 2 Configuration 7 5 2 1 Product design 7 5 2 2 LED displays 8 5 2 3 Connecting elements 8 6 Assembly 9 7 Installation 9 8 Commissioning 1...

Page 4: ...vision 1 or later Tab 2 Product version The product version can be identified from the product labelling There may be an updated version of this document for these or later product versions www festo...

Page 5: ...face between an automa tion system CPX AP and a higher order controller through participation in an PROFINET IO network Use the product only as follows Use only in an industrial environment Outside of...

Page 6: ...vice description file is available on the Festo Support Portal www festo com sp Identification Maintenance I M The Identification and Maintenance I M function serves as an electronic rating plate of t...

Page 7: ...Mounting interface connection side bottom and connection functional earth FE 6 Mounting interface lateral bottom and connection for functional earth FE 7 Connection for power supply XD1 8 Connection...

Page 8: ...onnecting elements Connection for power supply XD1 Plug M8 4 pin A coded Signal 1 24 V DC logic supply PS 2 0 V DC load supply PL 3 0 V DC logic supply PS 4 24 V DC load supply PL Tab 4 Connection for...

Page 9: ...Received data 3 TD Transmitted data 4 RD Received data Thread Shield Functional earth Tab 7 Connection for network 6 Assembly Assemble the module as outlined in the Instruction manual for automation s...

Page 10: ...omponents of the module after error free commissioning MD SD PL MT Illuminated green Illuminated green Illuminated green Off Tab 8 Behaviour of the display components after error free commissioning XF...

Page 11: ...off factory setting 2 load voltage monitoring active 1 UINT8 rw 20085 Measured value temperature AP ASIC C 1 INT16 ro 20087 Current measured value of logic supply PS mV 1 UINT16 ro 20088 Current meas...

Page 12: ...b server Diagnostics via PROFINET IO Diagnostics as part of PROFINET IO functions 10 5 Diagnostics via PROFINET IO via control soft ware through the network 10 2 Diagnostic messages Only the diagnosti...

Page 13: ...08 01 0127 134283559 Communication to AP module interrupted Diagnost ic status Error The device description file stored in the device at the fact ory is invalid or missing Remedy Restart device Check...

Page 14: ...gree of severity Warning e g parameterisation error Take appropriate remedial action e g check parameterisation Illuminated red Module diagnostics active Degree of severity Error e g undervoltage in l...

Page 15: ...pply PL to a module not available or firmware update in a module active Flashes red System diagnostics active Degree of severity Warning e g e g parameterisation error in a module Illuminated red Syst...

Page 16: ...tolerance range Check load supply PL Tab 14 LED load supply PL Maintenance MT LED yellow Meaning Remedy Off No maintenance needed Illuminated Maintenance required in at least one module in the automat...

Page 17: ...ed or disturbed Check network connection Device name device number not correct Check device name device number Flashes red IO controller defective Perform maintenance on IO controller Tab 16 LED PROFI...

Page 18: ...e g module related and channel related status information as well as error detection in the online mode of the control software and in the user program of the high order controller Diagnostic messages...

Page 19: ...11 Disposal ENVIRONMENT Send the packaging and product for environmentally sound recycling in accordance with the current regulations www festo com sp Disposal 19 Festo CPX AP I PN M12 2019 06...

Page 20: ...odules 80 max Module code hex dec 0x2081 8321d Module identification CPX AP I PN M12 Degree of protection in accordance with EN 60529 IP65 IP67 if lines are connected and connections that are not requ...

Page 21: ...c supply PS ms 10 Load supply PL V DC 24 25 Intrinsic current con sumption at nominal voltage 24 V from PL mA Typ 5 Reverse polarity pro tection 24 V PL against 0 V PL Yes Diagnostic message undervolt...

Page 22: ...X Cable length per segment m 100 max Factory settings IP address 0 0 0 0 Subnet mask 0 0 0 0 Cable specification Cable type Ethernet twisted pair cable shielded Transmission class Category Cat 5 or h...