Page 1: ...8099730 CPX AP I 4IOL M12 IO Link master 8099730 2020 03 8099732 Instructions Operat ing ...

Page 2: ...Translation of the original instructions IO Link is a registered trademark of its respective trademark holder in certain countries 2 Festo CPX AP I 4IOL M12 2020 03 ...

Page 3: ... 4 Service 5 5 Product overview 5 5 1 Function 5 5 2 Configuration 6 5 2 1 Product design 6 5 2 2 LED displays 7 5 2 3 Connecting elements 7 6 Assembly 9 7 Installation 9 8 Commissioning 9 8 1 Address space data length inputs outputs 10 8 2 IO Link Device description file IO Link Device Description 10 9 Parameterisation 10 10 Diagnostics and fault clearance 13 10 1 Diagnostic messages 13 10 2 LED ...

Page 4: ...n can be determined using the product label There may be an updated version of this document for these or later product versions è www festo com sp 1 3 Product labelling The product labelling is located on the right hand side of the module The Data Matrix code is on the connection side Scanning the printed Data Matrix Code with an appropriate device opens the Festo Support Portal with the informat...

Page 5: ... radio interference Use only in combination with modules and components that are permissible for the respective product variant è www festo com catalogue Only use the product if it is in perfect technical condition 2 3 Training of qualified personnel Installation commissioning maintenance and disassembly should only be conducted by qualified per sonnel The qualified personnel must be familiar with...

Page 6: ...unication forwarding XF20 7 Connection for system communication XF10 8 Connection for voltage forwarding XD2 9 Connection for power supply XD1 10 Mounting interface connection side bottom and connection functional earth FE 11 Mounting interface lateral bottom and connection for functional earth FE 12 Inscription label optional 13 Mounting interface lateral top Fig 1 Product design Product overview...

Page 7: ... green red yellow 5 Status diagnostics of IO Link port 0 X0 0 green red yellow 6 Status diagnostics for load supply PL green red Fig 2 LED displays 5 2 3 Connecting elements Connection for power supply XD1 Plug M8 4 pin A coded Signal 1 24 V DC logic supply PS 2 0 V DC load supply PL 3 0 V DC logic supply PS 4 24 V DC load supply PL Tab 4 Connection for power supply Product overview 7 Festo CPX AP...

Page 8: ...or system communication Connection for system communication XF20 Socket M8 4 pin D coded Signal 1 RX Received data 2 TX Transmitted data 3 RX Received data 4 TX Transmitted data Tab 7 Connection for system communication IO Link Ports X0 X3 connection Socket M12 5 pin A coded Signal 1 L 24 V DC operating voltage supply PS 2 P24 24 V DC load voltage supply PL 3 L 0 V DC operating voltage supply PS 4...

Page 9: ... 5 8 Commissioning Commission the automation system CPX AP in accordance with the Instruction manual for auto mation system CPX AP è 1 1 Other applicable documents Behaviour of the display components of the module after error free commissioning MD PL green light green light Tab 9 Behaviour of the LED displays of the module after error free commissioning Information on troubleshooting in the event ...

Page 10: ...EtherCAT 2 The last 4 input bytes contain the IO Link port qualifier information bytes for port 0 3 3 Factory setting Tab 10 The IO Link Device Tool software can be used to set the address space data length inputs outputs è www festo com sp The setting is saved permanently in the module Changes only become effective after a restart of the automation system CPX AP 8 2 IO Link Device description fil...

Page 11: ... 4 8 ms 68 8 0 ms 73 10 0 ms 78 12 0 ms 88 16 0 ms 98 20 0 ms 133 40 0 ms 158 80 0 ms 183 120 0 ms 4 UINT8 rw 20050 Activation of diagnostics for IO Link device lost factory setting TRUE 4 BOOL rw 20071 Port mode 0 DEACTIVATED factory setting 1 IOL_MANUAL 2 IOL_AUTOSTART 3 DI_CQ 97 PREOPERATE3 4 UINT8 rw 20072 Review and backup2 0 no test factory setting 1 device compatible V1 0 2 device compatibl...

Page 12: ...4 Port status information 0 NO_DEVICE factory setting 1 DEACTIVATED 2 PORT_DIAG 3 PREOPERATE 4 OPERATE 5 DI_CQ 6 DO_CQ 254 PORT_POWER_OFF 255 NOT_AVAILABLE 4 UINT8 ro 20075 Revision ID 4 UINT8 ro 20076 Transmission rate 0 Not detected 1 COM1 2 COM2 3 COM3 4 UINT8 ro 20077 Actual cycle time in 100 µs 4 UINT16 ro 20078 Actual vendor ID 4 UINT16 ro 20079 Actual device ID 4 UINT32 ro 20108 Input data ...

Page 13: ...08 variant 4 8209 variant 4 OE 8210 variant 16 8211 variant 16 OE 8212 variant 32 8213 variant 32 OE 1 UINT16 rw 20093 Hardware version 1 UINT8 ro 20097 Activation of the sensor supply factory setting TRUE 1 BOOL rw 1 ro read only rw read write Tab 13 AP parameter 10 Diagnostics and fault clearance 10 1 Diagnostic messages Diagnostic messages of an IO Link device are sent to the IO Link master via...

Page 14: ...PL 24 V DC Diagnost ic status Error A switch off of the load supply PL was detected The cause can be a deliberate shutdown by the emergency stop Remedy Check if the emergency stop was activ ated Check load supply PL 02 01 0106 33620230 Switch off load supply PL 24 V DC Diagnost ic status Information Overvoltage load supply PL 24 V DC Remedy Check load supply PL 02 01 013F 33620287 Overvoltage load...

Page 15: ...ut process data watchdog of the AP module expired Diagnost ic status Error System initialisation module detection has failed The system is in maintenance mode No I O function avail able Remedy Restart system Update firmware to the latest version Contact Festo Service 08 01 01A2 134283682 Device in System State Emergency Operation Diagnost ic status Error Tab 14 Diagnostic messages Diagnostics and ...

Page 16: ...gree of severity Warning e g parameterisation error Take appropriate remedial action e g check parameterisation Illuminated red Module diagnostics active Degree of severity Error e g undervoltage in load supply PL Take appropriate remedial action e g check load supply PL LED flashes red quickly Module ramp up not yet completed System communication not yet initial ised Flashes quickly green Module ...

Page 17: ...en Load supply PL available Flashes green Load supply PL not available Check load supply PL Flashes red Load supply PL outside the tolerance range Check load supply PL Tab 16 LED load supply PL Diagnostics and fault clearance 17 Festo CPX AP I 4IOL M12 2020 03 ...

Page 18: ... 1 Off Digital input not set process signal 0 Channel error red Error pending at Port Possible causes Incorrect device connected Check Device and setpoint configuration è parameters 20072 20073 20080 Configured process data length insufficient Adjust process data length Data memory error Check data memory Invalid cycle time Adjust cycle time è parameter 20049 Lights red Incorrect protocol revision...

Page 19: ...event code is mapped to a diagnostic ID in the IO Link master IO Link CPX AP Attribute Value Attribute Value Port 0 3 Channel 0 3 Instance 0 Device 5 output channel Source 1 Master Channel type 4 input channel 0 reserved Information 1 Notification Information 2 Warning Warning Type 3 Error Severity Error 0 reserved 1 Event single shot 0 Inform 2 Event disappears 2 Resolve Mode 3 Event appears Type...

Page 20: ... ID Remedy Check whether the correct IO Link device is connected 1803h 08 0A 01A8 Incorrect Device ID deviation of the Inspection Level Diagnost ic status Error IO Link Backup Restorefailed memory out of range 2048 octets Remedy 1809h 08 0A 0183 BackupInconsistency memory out of range 2048 octets Diagnost ic status Error IO Link Backup Restore failed DataStorageIndex not available Remedy 180Ah 08 ...

Page 21: ...tible 6001h 08 0A 014D Version error incom patible protocol ver sion Diagnost ic status Error Tab 19 IO Link master event codes IO Link device event codes IO Link event code hex Diagnostics ID hex Message Description General malfunction Unknown error of the IO Link device Remedy Check IO Link device 1000h 0D 00 0141 General malfunction of IO Link device Diagnost ic status Information The connected...

Page 22: ... drive layout possible overloading during continu ous operation 4210h 03 01 002F Device overtemperat ure Diagnost ic status Error Device undertemperature Remedy Check ambient conditions 4220h 03 01 002D Device undertemper ature Diagnost ic status Error Hardware error of the IO Link device Remedy Repair or replace IO Link device 5000h 10 02 0145 Device hardware error Diagnost ic status Error Malfun...

Page 23: ...ve fuse 5101h 0A 00 014A Fuse blown opened Diagnost ic status Error Overvoltage in the logic supply PS 24 V DC has been detected Remedy Check logic supply PS 5110h 02 01 0017 Overvoltage in logic supply PS 24 V DC Diagnost ic status Warning Undervoltage of the logic supply PS 24 V DC was detected Remedy Check logic supply PS 5111h 02 01 0016 Undervoltage in logic supply PS 24 V DC Diagnost ic stat...

Page 24: ...cted Diagnost ic status Error Wire break at lower level IO Link device 1 15 Remedy Check wiring 7701h 770Fh 10 02 0152 10 02 0160 Wire break at lower level device 1 15 Diagnost ic status Error Short circuit check installation Remedy Check installation 7710h 01 01 0161 Short circuit check installation Diagnost ic status Error Earth fault check installation Remedy Check installation 7711h 01 01 0162...

Page 25: ...heck input signal Check parameters and config uration 8C20h 07 05 0166 Measuring range exceeded Diagnost ic status Error Underflow of the process variable area pro cess data uncertain Remedy Check input signal Check parameters and config uration 8C30h 07 07 0167 Underflow of the pro cess variable range process data uncer tain Diagnost ic status Warning Maintenance cleaning Remedy Clean device 8C40...

Page 26: ...ic event note warning or error has occurred IO Link event specific details are attached to this message Remedy è Description IO Link Master or IO Link device All other event codes 08 0A 0108 IO Link event Diagnost ic status Information Warning Error Tab 20 IO Link device event codes 11 Disposal ENVIRONMENT Send the packaging and product for environmentally sound recycling in accordance with the cu...

Page 27: ... hex dec Dependent on the set data length è Tab 10 0x2009 8201d factory setting Module identification CPX AP I 4IOL M12 Degree of protection in accordance with EN 60529 IP65 IP67 if lines are connected and connections that are not required are closed with a cover cap Protection against elec tric shock protection against direct and indirect contact in accordance with IEC 60204 1 through the use of ...

Page 28: ... supply PL V DC 24 _ 25 Intrinsic current con sumption at nominal operating voltage 24 V from PL mA typ 5 without connected Devices Capacitive load at load supply PL 24 V PL to 0 V PL nF Typ 35 24 V PL to FE nF Typ 35 0 V PL to FE nF Typ 20 Undervoltage identification in logic supply PS Trigger level V DC 17 Hysteresis V DC 0 5 Tab 22 Power supply Technical data 28 Festo CPX AP I 4IOL M12 2020 03 ...

Page 29: ...alue can be set è parameter 20049 Process data length per Port bytes 32 I 32 O max PS supply PS current per module Port A 2 0 5 max Short circuit protection PS electronic per module A 2 Behaviour after PS overload automatic return PS reverse polarity pro tection yes internal only PL supply PL current per module Port A 4 1 5 max not on all ports simultaneously PL short circuit protec tion no Extern...