42
Festo — CPX-AP-A-EP-M12 — 2022-07
Diagnostics and fault clearance
ID hex (dec)
Message
Description
06 | 00 | 0189
(100663689)
Modulidentification
check failed
Ident check failed for configured module at slot %u
(Detected %u - Configured %u)
Remedy
–
Download updated slot configuration
Diag-
nostic
status
Error
08 | 00 | 012E
(134218030)
Device address
invalid
The address, which was assigned to the device is invalid.
Remedy
–
Verify address configuration settings. Is the
address assigned by software or set by
hardware (dip switch).
–
Check the assigned address of the device.
–
Check for multiple address assignment of
the same address.
–
Check dip switch setting.
Diag-
nostic
status
Warning
08 | 01 | 0127
(134283559)
AP Module Discon-
nected
The AP system communication to a module has failed.
Remedy
–
Restart AP system.
–
Check communication cable (AP)
Diag-
nostic
status
Error
08 | 01 | 0132
(134283570)
AP master process
data output watchdog
timed out
The process data watchdog for the outputs timed out in
the master
Remedy
–
Adjust cycle time and watchdog parameter.
–
Restart AP system.
–
Check wiring.
Diag-
nostic
status
Error
08 | 01 | 0133
(134283571)
AP master process
data input watchdog
timed out
The process data watchdog for the inputs timed out in the
master
Remedy
–
Adjust cycle time and watchdog parameter.
–
Restart AP system.
–
Check wiring.