background image

Festo  CPV..−GE−CC−8    0304NH    English

21

5

Technical  specifications

Type

CPV..−GE−CC−8

Temperature  range

 Operation
 Storage

−  5  ...  +  50  °C
−  20  ...  +  70  °C

Relative  humidity

95  %,  non−condensing

Protection  class 

as  per  EN  60529,

plug  connector  inserted  or  provided
with  protective  cap
 With  sub−base 

type  FBS−AB−1−KL−5POL

 With  sub−D  plug 

type  FBS−SUB−9−GS−2X4POL−B

IP20

IP65

Protection  against  electric  shock

(protection  against  direct  and  indirect
contact  as  per  EN  60204−1/IEC  204)

With  a  PELV  power  unit 
(Protected  Extra  Low  Voltage)

Protection  against  explosion

(as  per  EU  guidelines  94/9/EG,
EN50021  and  EN  50281−1−1).  Do  not
disconnect  electrical  connections
which  are  under  tension.

II  3  G/D  EEx  nA  II  T5  X
−5  °C 

Ţ

Ta  +50  °C  T  80  °C  IP65

(year  of  manufacture  see  Ex−
identification  on  the  product)

Electromagnetic  compatibility

 Interference  emitted

 Resistance  to  interference

Tested  as  per  EN  61000−6−4
(industry) 

*)

Tested  as  per  EN  61000−6−2
(industry)

Vibration  and  shock

See  manual  P.BE−CP−CC−..

Tested  as  per  DIN/IEC  68  /
EN60068

*)

The  CPV  Direct  is  intended  for  industrial  usage.

Summary of Contents for CPV-GE-CC-8 Series

Page 1: ...Kurz beschreibung Brief description CPV Ventilinsel mit Direkt anschluss Typ CPV GE CC 8 CPV valve termi nal with direct connection type CPV GE CC 8 Deutsch English 657 856 0304NH Compact Performance...

Page 2: ...Festo CPV GE CC 8 0304NH 2 Deutsch 3 English 13 Edition 0304NH Original de Festo SE Co KG D 73726 Esslingen Germany 2003 Internet http www festo com E Mail service_international festo com...

Page 3: ...rennung der Betriebsspannung nach IEC 742 EN 60742 VDE 0551 mit mindestens 4 kV Isolations festigkeit gew hrleisten PELV Schaltnetzteile sind zul ssig wenn sie die sichere Trennung im Sinne der EN 609...

Page 4: ...pulen 5 CP Erweiterungs anschluss 6 Schaltermodul abgenommen 1 2 3 4 5 6 2 1 Run und Pow Err LEDs 3 LED Run Bedeutung leuchtet gr n normaler Busbetrieb aus kein Busbetrieb LED Pow Err Bedeutung leucht...

Page 5: ...V Lastspannung Ventile 3 0 V 4 Erdungsanschluss 1 Bei angeschlossenen Modulen am Erweiterungsanschluss 2 3 Anschlussbeispiel mit PELV Netzteil und Potenzial ausgleich 1 PE 2 Potenzialausgleich 3 Lasts...

Page 6: ...u FE 1 Wird bei CC Link nicht verwendet Verbindung ber R C Kombination zu FE der CPV Direct 1 M 220 nF Anschluss mit Anschlussblock IP20 oder mit Sub D Stecker IP65 1 Anschlussblock Typ FBA 1 KL 5POL...

Page 7: ...10SBH 0 5 mm2 x 3 110 0 5 W Alternativ CSFV110 SLAB 110 0 5 W oder entsprechendes Kabel nach Kabel spezifikation 1 1 1 Befindet sich die CPV Direct am Anfang oder Ende des Feld bussystems ist als Busa...

Page 8: ...olgt vor 1 Spannungsversorgung abschalten 2 Schaltermodul demontieren 3 Mit den DIL Schaltern einstellen Baudrate Verhalten bei Feldbus Kommunikationsfehlern HOLD CLEAR CC Link Adresse 4 Schaltermodul...

Page 9: ...kBd 2 5 MBd 5 MBd 10 MBd 3 2 HOLD CLEAR einstellen 4fach DIL Schalter HOLD CLEAR 3 3 CC Link Adresse einstellen 8fach DIL Schalter BCD codierte Eingabe Beispiel Adresse 26 2 0 1 2 1 2 2 2 4 2 3 8 2 0...

Page 10: ...RWr 0 16RemoteInputf rdasCP Eingangsmodulam CP Erweiterungsanschluss Ausg nge RY 0 RY F 16 digitale Ausg nge f r die Ventilspulender CPV Direct RWw 0 Reserviert F r die Adressierung gilt allgemein Ein...

Page 11: ...ktes und indirektes Ber hren nach EN 60204 1 IEC 204 Durch PELV Netzteil Pro tected Extra Low Voltage Schutz gegen Explosion nach EU Richtlinie 94 9 EG EN 50021 und EN 50281 1 1 Elektr Anschl sse nich...

Page 12: ...C 24 V verpolungssicher 20 4 26 4 V Summe aller eingeschalte ten CP Magnetventile siehe BeschreibungPneumatik 4 Vss innerhalb Toleranz Feldbus Protokoll Version CC Link Chip Vendor Code Unterst tzte B...

Page 13: ...lation of the operating voltages as per IEC 742 EN 60742 VDE 0551 with at least 4 kV isolation resistance Protected Extra Low Voltage PELV Switch power packs are permitted providing they guarantee rel...

Page 14: ...ls 5 CP extension connection 6 Switch module removed 1 2 3 4 5 6 2 1 Run and Power Err LEDs 3 LED Run Meaning lights up green Normal bus operation off No bus operation LED Power Err Meaning lights up...

Page 15: ...he valves 3 0 V 4 Earth groundconnection 1 On the extension connection of connected modules 2 3 Example of connection with PELV power unit and potential equalization 1 PE 2 Potential equalization 3 Lo...

Page 16: ...onnection to FE 1 Not used with CC link Connection via R C element to FE of the CPV Direct 1 M 220 nF Connection with sub base IP20 or with sub D plug IP65 1 Sub base type FBA 1 KL 5POL Connect FG wit...

Page 17: ...ble FANC 110SBH 0 5 mm2 x 3 110 0 5 W Alternative CSFV110 SLAB 110 0 5 W or appropriate cable as per cable specifi cation 1 1 1 If the CPV Direct is at the beginning or the end of the field bus system...

Page 18: ...the configuration proceed as follows 1 Switch off the power supply 2 Remove the switch module 3 Set the following with the DIL switches the baud rate the reaction to field bus communication faults HOL...

Page 19: ...625 kBd 2 5 MBd 5 MBd 10 MBd 3 2 Setting HOLD CLEAR 4 element DIL switch HOLD CLEAR 3 3 Setting the CC link address 8 element DIL switch BCD coded entry Example Address 26 2 0 1 2 1 2 2 2 4 2 3 8 2 0...

Page 20: ...te RWr 0 16remoteinputsfortheCPinputmoduleonthe CP extension connection Outputs RY 0 RY F 16 digital outputs for the valve coils of the CPV Direct RWw 0 Reserved The following applies for the addressi...

Page 21: ...ct contact as per EN 60204 1 IEC 204 With a PELV power unit Protected Extra Low Voltage Protection against explosion as per EU guidelines 94 9 EG EN 50021 and EN 50281 1 1 Do not disconnect electrical...

Page 22: ...tconsumption Residual ripple 24 V DC protected against incorrect polarity 20 4 26 4 V Sum of all switched on CP solenoid valves see Pneumatics Manual 4 Vpp within tolerance Field bus Protocol Version...

Reviews: