Current consumption at pin 1 of CP fieldbus node
Current consumption of CP fieldbus node
250 mA
Maximum current consumption of electronic
components
(internal electronic components of all
CP modules)
+ 560 mA
Current consumption of all connected
sensors (see manufacturer specifications)
+ _____ A
Sum of current consumption at pin 1
= _____ A
______ A
Current consumption at pin 2 of CP fieldbus node
Current consumption of all valve coils
supplied simultaneously with power
1)
_____
A
Sum of current consumption at pin 2
= _____ A
+______ A
Current consumption at pin 1 of output modules
Current consumption of all simultaneously
actuated electrical outputs (internal
consumption at logic 1)
2)
_____
x _____A
Load current of simultaneously actuated
outputs
+ _____ A
Sum of current consumption of outputs
= _____ A
+______ A
Total current consumption of the CP system
=______ A
1) Current consumption depends on valve type (see technical specifications for valves)
2) Internal consumption at logic 1 (see technical specifications for output module)
PLEASE NOTE
Select a power unit which has sufficient output for
further extensions to the CP system.
3. Installation
CP... 9806A
3-9
Summary of Contents for Compact Performance System
Page 1: ...Compact Performance CP system Installation and commissioning...
Page 3: ...Part no 165 226 Title Manual Designation P BE CPSYS GB II CP 9806A...
Page 12: ...Chapter 1 System overview 1 System overview CP 9806A 1 1...
Page 33: ...1 System overview 1 22 CP 9806A...
Page 34: ...Chapter 2 Fitting 2 Fitting CP 9806A 2 1...
Page 46: ...Chapter 3 Installation 3 Installation CP 9806A 3 1...
Page 64: ...Chapter 4 Commissioning 4 Commissioning CP 9806A 4 1...
Page 82: ...Appendix A Technical appendix A Technical appendix CP 9806A A 1...
Page 91: ...V Voltage connecting 3 14 selecting the cable 3 16 A Technical appendix A 10 CP 9806A...