Compact mode
PLEASE NOTE
Observe the sequence "inputs before outputs" in
compact mode, if both inputs and outputs are in-
stalled in a CP system.
In compact mode configure the sum of the input bytes
and the sum of the output bytes separately and inde-
pendently of each other (see fig. 2/9).
The following applies:
••
CP valve terminals occupy two output bytes inde-
pendently of the valves fitted.
••
Assign the DP identifiers in ascending order without
gaps. No field may remain unused.
Enter inputs before outputs.
••
If there are only output modules or CP valve termi-
nals, enter their DP identifiers in line 0.
••
The highest string with the highest number of inputs
or outputs defines the sum of input or output bytes.
••
Non-existent CP valve terminals, output modules or
input modules occupy input or output bytes if a
higher string is occupied with inputs or outputs.
Maximum configuration in compact mode
023 039 8 input bytes and 8 output bytes.