Set the following functions on the DIL switch:
Dual in-line
switch
– the hundreds figure of the fieldbus address
– the fieldbus protocol PROFIBUS-DP.
Switch elements 3..6 must be set at the position
specified below, in order that the fieldbus protocol
PROFIBUS-DP is set.
DIL switch
(factory
setting)
Switch
element
Function description
1
fieldbus address
ON: fieldbus address > 100
OFF: fieldbus address < 100
2
Diagnostic information V
Valves
/V
Outputs
ON: active
OFF: not active
3
Fieldbus protocol PROFIBUS-DP
ON: must be set at ON
OFF: reserved
4
Fieldbus protocol
ON: must be set at ON
OFF: reserved
5
Fieldbus protocol
ON: must be set at ON
OFF: reserved
6
Fieldbus protocol
ON: reserved
OFF: must be set at OFF
1. Installation
1-6
CP FB13-E 9904b