Festo — CMMT-AS-...-S1 — 2021-04d
Technical data
–
Depending on the desired safety classification, evaluation of the SBA diagnostic output by the
safety relay unit is either mandatory or optional.
–
To achieve the safety classification Cat. 3, PL d, SIL 2 (or also Cat. 2, PL c/d) in conjunction with 2
brakes, evaluation of the SBA diagnostic output is mandatory.
–
If you require an SBC function with a classification higher than Cat. 1, PL c, the diagnostic outputs
must be checked regularly – at least 1 x once every 24 h – by having them tested automatically by
the safety relay unit (
è
EN ISO 13849-1, Annex G.2).
–
The safety relay unit must request the safety sub-function at least once within 24 h and thereby
monitor the SBA diagnostic output to achieve a diagnostic coverage of at least 60 %. If the signal
behaviour does not correspond to expectations, the system must be put into a safe condition within
the reaction time. It is essential that time monitoring be provided in the safety controller.
The technical data for the safety sub-function SS1 must be calculated individually according to the
application. Use the specified safety reference data for STO and SBC for the calculation.
9.2
General technical data
Product conformity
CE marking (declaration of con-
formity
in accordance with EU EMC Directive
1)
in accordance with EU Machinery Directive
in accordance with EU RoHS Directive
1) The device is intended for use in an industrial environment and with appropriate measures in commercial, residential and mixed
areas.
Tab. 18: Product conformity
General technical data
Type ID code
CMMT-AS
Type of mounting
Mounting plate, attached with screws
Mounting position
vertical, mounted on closed surface, free convection with unhin-
dered air flow from bottom to top
Product weight
è
Manual Assembly, Installation.
Tab. 19: General technical data
Ambient conditions, transport
Transport temperature
[°C]
−25
…
+70
Relative humidity
[%]
5
…
95 (non-condensing)
Max. transportation
duration
[d]
30