6. Control via FHPP
74
Festo.P.BE-CMMP-CAM-SW-EN en 1105a
6.6
Description of the status bytes
6.6.1
Status byte 1 SCON
Bit
DE
EN
Description
B0
ENABLED
Regler
freigegeben
Drive Enabled
= 0:
Drive blocked, controller not active
= 1:
Drive (controller) enabled.
B1
OPEN
Betrieb
freigegeben
Operation
Enabled
= 0:
Stop active
= 1:
Operation enabled, positioning possible
…
B6
OPM1
Rückmeldung
Betriebsart
Display
Operating Mode
= 00: Record selection (standard)
= 01: Direct operation
= 10: Reserved
= 11: Reserved
B7
OPM2
6.6.2
Status byte 2 SPOS
Bit
DE
EN
Description
B0
HALT
Halt
HALT
= 0:
Halt is active
= 1:
Halt is not active, drive can be moved
B1
ACK
Bestätigung
Start
ACKnowledge
Start
= 0:
Ready for start (homing, jog)
= 1:
Start executed (homing, jog)
…