2
Product description
26
Festo – GDCP-CMMO-ST-EA-SY-EN – 2017-05c – English
2.4.2
Control profiles of the I/O interface (valve, binary)
For activation of the motor controller via the I/O interface, 2 control profiles (valve, binary) are avail
able. During the initial start-up phase the valve profile is active (factory setting).
The change of profile takes place via FCT [...][Application Data] Operation Modes
A web server start-up requires the valve profile to be set for the I/O interface. A
change of profile via web server involves the downloading of a corresponding
parameter file to the motor controller. All OMS parameter files from Festo contain
“Valve Profile” parameterisation.
Profile
Description
Valve
è
I/O control for a simple positioning mode, optionally with reduced torque.
Based on the pneumatic valve pilot, 7 position records can be selected directly
through one input each (7 separate inputs). Upon reaching the target position the
output corresponding to the input is set (7 separate outputs).
Binary
è
I/O control with extended function in all controller operating modes.
Via 5 inputs, 31 records can be addressed in binary form (plus record 0 = homing).
Achievement of the target parameter is reported via the MOTION COMPLETE
output.
The binary profile can be changed over by input DIN8 between 2 operating modes:
–
Mode 0: Normal operation
–
Mode 1: jogging/teaching during the commissioning process
Tab. 2.16 Control profiles of the I/O interface