Ferroli Rendimax 16 CE Installation And Operating Instructions Manual Download Page 17

17

S.p.A.

7.TROUBLE SHOOTING

Pilot burner fails to ignite

No gas

Open the gas cock

Air in the pipes

vent as described in the section on ignition

Pilot nozzle blocked

Clean the nozzle with compressed air

Insufficient gas flow

Adjust flow using the screw on the valve

Pilot goes out

Faulty thermocouple

Control or replace the thermocouple

Incorrect flame adjustment

Adjust the flame using the screw on the gas
valve

Insufficient flame

Adjust the flame until it envelopes the
thermocouple  as indicated in figure 12

Poor contact with the gas valve coil

Tighten the connector on the gas valve

Main burner fails to ignite

No current

Restore current

Blocked nozzles

Clean the nozzles thoroughly

Faulty gas valve

Repair or replace the gas valve

Flue gas thermostat activated

Manually reset

Blowout at main burner

Insufficient gas

Control gas pressure at the main burner

Boiler dirty

Check and clean the boiler

Burner dirty

Check and clean the burner

Smell of unburnt gas

Boiler dirty

Check and clean the boiler body

Insufficient flue draught

Control flue draught efficiency

Insufficient air change

Improve room ventilation

Summary of Contents for Rendimax 16 CE

Page 1: ...GAS FIRED BOILER CAST IRON GAS FIRED BOILER for central heating for central heating for central heating for central heating for central heating Installation and operating instructions Installation an...

Page 2: ...2 S p A Contents 1 Description 2 Dimensions and technical specifications 3 Installation 4 Adjustment 5 Gas conversion 6 Maintenance and cleaning 7 Troubleshooting...

Page 3: ...roduction The standard version is designed to work with natural gas To use the boiler with L P G on site conversion must be carried out following the instructions given below This conversion must be d...

Page 4: ...View with open door KEY 1 Boiler thermostat 2 Boiler temperature pressure gauge 3 Safety valve 4 Gas valve 5 Circulation pump only PV version 6 Boiler drain cock 7 Pilot burner 8 Piezo Igniter 9 Gas M...

Page 5: ...er content lt 7 3 9 0 10 7 12 4 Expans vessel vol 6 6 8 lt Boiler Rendimax 16 CE Rendimax 23 CE Rendimax 30 CE Rendimax 36 CE Rated 1 94 2 70 3 47 4 23 Min 1 16 1 69 2 46 2 95 Gas flow rate at the bur...

Page 6: ...It is important to ensure that the boiler is connected to an efficient earth system The terminal board for connecting the boiler to the room thermostat if used is inside the control panel follow the e...

Page 7: ...the protective cover on the control panel Fig 2 part 13 and reset the thermostat manually The boiler will then operate normally again If you replace the FLUE GAS THERMOSTAT use original components onl...

Page 8: ...r leaks from the system or boiler that the electrical connections are correct and the earth wire has been connected to an efficient earth installation that there are no inflammable liquids or material...

Page 9: ...ew 7 Main burner adjustment screw 8 Slow opening adjustment screw 4 03 Igniting the boiler with HONEYWELL V4600C gas valve fig 7a Position the boiler thermostat 1 fig 2 on minimum Open the gas cock an...

Page 10: ...the pressure point screw pos4 fig 7b Push and keep pushed the knob in the position a Ignite the pilot burner by pressing the piezoelectric igniter 8 fig 2 on the left side of the boiler Keep gas valv...

Page 11: ...ion Check that the fuel consumption indicated on the meter corresponds to the value indicated in the table Check that water circulates correctly between the boiler and system Check that flue connectio...

Page 12: ...seless Adjust the screw 1 STEP ADJ until the gas pressure is the right one Seal the screws 1 STEP ADJ and REG ADJ 5 03 2 System nr 2 In the even the screw REG ADJ is already adjusted and sealed Tighte...

Page 13: ...elope completely the thermocouple fig 10 without burning excessive gas To adjust the pilot flame operate on the screw 3 fig 7b To adjust the pressure at main burner operate on the screw 2 fig 7b Rotat...

Page 14: ...ariability with L P G 5 08 Heat output variability characteristics To adjust furnace heat input simply regulate the main burner via the gas valve fig 8 This in turn varies the heat output to the C H w...

Page 15: ...the burner and boiler body and chimney should be clean To clean them you are advised to use a soft brush or compressed air Avoid chemical products water pressure in the system cold should be between 0...

Page 16: ...combustion chamber door to the boiler g remove the whole gas assembly Now you may clean all the smoke passages in the boiler using a pipe brush 3 Remember you should check and if necessary clean the...

Page 17: ...envelopes the thermocouple as indicated in figure 12 Poor contact with the gas valve coil Tighten the connector on the gas valve Main burner fails to ignite No current Restore current Blocked nozzles...

Page 18: ...tat bulb out of its sheath Check the bulb is well inserted Faulty adjustment on the panel See section on adjustment Condensation in boiler Faulty thermostat adjustment Adjust the thermostat to a highe...

Page 19: ...19 S p A...

Page 20: ...LY 37047 SAN BONIFACIO VR ITALY tel 045 6139411 tlx 480172 tel 045 6139411 tlx 480172 tel 045 6139411 tlx 480172 tel 045 6139411 tlx 480172 tel 045 6139411 tlx 480172 fax 045 6100233 6100933 fax 045 6...

Reviews: