Pegasus F2 N T
25
4.3 Technical data table
Gas supply
Heating Power (Net Heat Value - Hi)
Useful heating power
Powers
kW
51
kW
56
Dimensions, weights connections
Depth
mm
900
Width
mm
550
Height
mm
1000
Boiler water content
litres
22
N° burner trains
3
Minimum working pressure in heating
bar
0.8
Maximum working pressure in heating
bar
6
Maximum working temperature
°C
100
Electrical protection rating
IP
X0D
Electrical power supply
Power voltage/frequency
V/Hz
230/50
Max electrical power absorbed
W
5
Heating system delivery
inches
1” 1/2
Gas system connection
inches
3/4”
Weight with packing
kg
250
Heating
Delivery G20
nm3/h
5.9
Main nozzles G20
mm
3 x 3.50
Pressure at burner G20
mbar
13.3
Feed pressure G20
mbar
20.0
Delivery G25
nm3/h
Main nozzles G25
mm
3 x 3.50
Pressure at burner G25
mbar
Supply pressure G25
mbar
25.0
N° elements
4
Delivery G31
kg/h
4.34
Main nozzles G31
mm
3 x 2.15
Pressure at burner G31
mbar
36
Supply pressure G31
mbar
37.0
Heating system return
inches.
1” 1/2
68
74.8
900
640
1000
26
4
0.8
6
100
X0D
230/50
5
1” 1/2
3/4”
300
7.9
4 x 3.50
13.3
20.0
4 x 3.50
25.0
5
5.79
4 x 2.15
36
37.0
1” 1/2
85
93.5
900
720
1000
30
5
0.8
6
100
X0D
230/50
5
1” 1/2
3/4”
350
9.9
5 x 3.50
13.3
20.0
5 x 3.50
25.0
6
7.24
5 x 2.15
36
37.0
1” 1/2
102.0
112.0
900
800
1000
34
6
0.8
6
100
X0D
230/50
5
1” 1/2
3/4”
400
11.8
6 x 3.50
13.3
20.0
6 x 3.50
25.0
7
8.68
6 x 2.15
36.0
37.0
1” 1/2
51
68
85
102
Pilot nozzle G31
mm
1 x 0.24
1 x 0.24
1 x 0.24
1 x 0.24
Pilot nozzle G20-G25
mm
1 x 0.40
1 x 0.40
1 x 0.40
1 x 0.40
5.9
13.3
7.9
13.3
9.9
13.3
11.8
13.3
MODEL