25
OPTIMAX HE PLUS S
Cod. 3540R543 - 08/2012 (Rev. 00)
Table 6 - List of faults
Fault
code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas
fl
ow to the boiler and that the air has been purged
from the pipes
Detection or Ignition electrode fault
Check that the electrodes are correctly positioned and free of any deposits
Defective gas valve
Check and change the gas valve
Incorrect inlet gas pressure
Check inlet gas pressure
Siphon obstructed
Check and if necessary change the siphon
A02
Flame detected with
the burner off
Ionisation electrode defective
Check the ionising electrode wiring
Main board defective
Check the PCB
A03
High limit protection
Flow temperature sensor not active or correctly located
Check the correct positioning and operation of the
fl
ow sensor
No system circulation
Check pump and radiator valves present in the system
Check operation of the internal by-pass
A04
Flue gas fault
Fault F07 happened 3 times in the last 24 hours
Check the
fl
ue
A05
Fan problem
Tachometer signal interrupted for 1 hour or longer
Check the wiring and the fan
A06
No flame after the
ignition phase (6 times
in 4 minutes)
Detection electrode fault
Check that the electrodes are correctly positioned and if necessary change it
Flame unstable
Check the burner
Incorrect valve gas Offset
Check the Offset at the minimum power
Flue gas circuit obstructed
Check if
fl
ue gas circuit is free
Siphon obstructed
Check and if necessary change the siphon
A41
Flow sensor discon-
nected
Sensor disconnected
Check the correct positioning and operation of the
fl
ow sensor
F07
High fume tempera-
ture
The exchanger probe detects and excessive temperature
for over 2 minutes
Check the exchanger
F10
Flow sensor fault
Sensor damaged or short circuited
Check the wiring or change the sensor
Sensor damaged or wiring broken
F11
Return sensor fault
Sensor damaged or wiring shorted
Check the wiring or change the sensor
Sensor damaged or wiring broken
F13
Exchanger probe
fault
Exchanger Probe damaged or wiring shorted
Check the wiring or replace the Exchanger probe
Exchanger Probe damaged or wiring broken
F14
Flow sensor fault
Sensor damaged or short circuited
Check the wiring or change the sensor
Sensor damaged or wiring broken
F15
Fan problem
Tachometer signal interrupted, fan connection
Check the wiring and the fan
Fan damaged, debris in fan
Check the fan, clean debris
F34
Supply voltage under
170V
Electric supply problem
Check the electrical system
F35
Irregular mains fre-
quency
Electric supply problem
Check the electrical system
F37
Incorrect system water
pressure
Pressure too low
Fill the system
Sensor damaged
Check the sensor
F42
Flow sensor fault
Sensor damaged
Change the sensor