OPTIMAX HE PLUS S
Cod. 3540R543 - 08/2012 (Rev. 00)
The expansion tank must be
fi
lled.
The gas
fl
ow and pressure must correspond to that given in the respective tables.
The boiler casing, panel and aesthetic parts can be cleaned with a soft damp cloth, possibly soaked in soapy
water. Do not use any abrasive detergents and solvents.
Opening the case
To open the boiler casing, you need to follow the sequence
given below and the instructions of
fi
g. 26.
Using a screwdriver, fully unscrew and remove the 2
screws “A”
Open by lowering the panel “B”
Lift and take off the casing “C”
1.
2.
3.
C
B
D
B
fdp
dpn
gps
u
sft
fu
2
3
4
5
1
CB
S
fdp
dpn
gps
u
sft
fu
2
3
4
5
1
CB
S
fi
g. 26 - Opening the casing
Before carrying out any operation inside the boiler, disconnect the electrical power supply and close the gas
cock upstream
Combustion check
Connect the
fl
ue gas analyzer to the
fl
ue gas sampling point as shown in the
fi
g. 27 and check combustion as described
in table 4 and table 5.
Press the CH button for 5 seconds to place boiler into
test mode
Wait for 10 minutes for the boiler to stabilize fully
Take the measurement and record
Take the boiler to minimum output by pressing the
CH button, allow the boiler to stabilize for a further 10
minutes.
Take the measurement and record.
1.
2.
3.
4.
5.
2
3
2
3
fi
g. 27 - Flue gas sampling Point
1
= AIR -
2
= FUMES
Table 4 - Maximum rate
Table 5 - Minimum rate
NATURAL GAS ACCEPTABLE
COMBUSTION RANGE
MAXIMUM RATE AFTER 10 MINUTES FROM COLD
NATURAL GAS ACCEPTABLE
COMBUSTION RANGE
MINIMUM RATE AFTER 10 MINUTES FROM COLD
Boiler model
CO/CO
2
RATIO
CO
2
NG
CO
2
LPG
Boiler model
CO/CO
2
RATIO
CO
2
NG
CO
2
LPG
Optimax HE
Plus 18 S
0.004
9.0
10.00
Optimax HE
Plus 18 S
0.004
8.5
9.5
Optimax HE
Plus 25 S
0.004
9.0
10.00
Optimax HE
Plus 25 S
0.004
8.5
9.5
Optimax HE
Plus 35 S
0.004
9.0
10.00
Optimax HE
Plus 35 S
0.004
8.5
9.5
If the combustion reading is greater than the acceptable value AND the integrity of the complete
fl
ue system and
combustion circuit seals have been veri
fi
ed and the inlet gas pressure (and gas rate) have been veri
fi
ed, proceed
as in section Setting the Air/Gas Ratio valve.
•
•