FORCE W
167
EN
cod. 3541Q760 - Rev. 00 - 01/2019
Parameters Menu - Transparent Parameters
31 parameters are available, indicated by the letter
“P”
, which are not modifiable from Remote Timer Control.
Table. 5- Parameters - Transparent
Notes
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
Parameter Description
Range
FORCE W 60
FORCE W 80 FORCE W 99 FORCE W 120 FORCE W 150
P01
Ignition power
0-100%
30
30
30
30
30
P02
Heating ramp
1-10°C/minute
1
1
1
1
1
P03
Virtual set point min. temperature
20-80°C
20
20
20
20
20
P04
Heating standby time
0-10 minutes
4
4
4
4
4
P05
Heating Post-Circulation
0-255 minutes
3
3
3
3
3
P06
Pump operation
0-3 Operation strategy
0
0
0
0
P07
Modulating pump min. speed
0-100%
30
30
30
30
30
P08
Modulating pump start speed
0-100%
75
75
75
75
75
P09
Modulating pump max. speed
30-100%
100
100
100
100
100
P10
Pump deactivation temperature during Post-Circulation
0-100°C
35
35
35
35
35
P11
Pump activation hysteresis temperature during Post-Circulation 0-20°C
5
5
5
5
5
P12
Heating user min. setpoint
10-90°C
20
20
20
20
20
P13
Heating user max. setpoint
20-90°C
80
80
80
80
80
P14
Max. output in heating
0-100%
80
80
80
80
80
P15
DHW ramp
1-10°C/min
5
5
5
5
5
P16
DHW standby time
0-255 seconds
120
120
120
120
120
P17
DHW pump Post-Circulation
0-255 seconds
30
30
30
30
30
P18
Not implemented
--
--
--
--
--
--
P19
Not implemented
--
--
--
--
--
--
P20
Max. output in DHW
0-100%
80%
80%
80%
80%
P21
Not implemented
--
--
--
--
--
--
P22
Not implemented
--
--
--
--
--
--
P23
Not implemented
--
--
--
--
--
--
P24
Fan frequency in standby mode
0-255 Hz
0
0
0
0
0
P25
Modulating pump adjustment temperature
0-60°C
20
20
20
20
20
P26
Primary exchanger protection temperature
0-80°C
35
35
35
35
35
P27
System min. pressure value
--
--
--
--
--
P28
System nominal pressure value
--
--
--
--
--
P29
Exchanger protection activation
0
= No F43,
1-15
= 1-15°C/second
0=No F43
0=No F43
0=No F43
P30
Heating hysteresis after ignition
6-30°C
10
10
10
10
10
P31
Timer for heating hysteresis after ignition
0-180 seconds
60
60
60
60
60