Fig. 18
Ø80
Ø80
AIR
FLUE
1
2
3.04 Top Outlet: Two Pipe Flue System
3.04.1 Two pipe connection
Two separate ducts Ø80 for air intake and fl ue gas
discharge can be directly connected to the boiler.
For conversion mount the separate outlet kit 1 to
top outlet (see 3.03)
Insert blanking plate 2
in remaining air intake
Connect fl ue duct to central hole Ø80 and air duct to left or right air intake hole Ø80. Insert blanking
plate 2 in remaining air intake.
A varied selection of accessories for two pipe systems are available from Ferroli (ref. to page 17). Before
installing your system please check via calculation table at 3.04.2 you are not exceeding the maximum
permissible length for the appliance.
IMPORTANT:
Notes on two pipe system installation:
When using the two pipe system the fl ue discharge pipe must have a 25mm air gap when passing through combustible
materials. Where the fl ue discharge pipe passes through the airing space of an airing cupboard it must be protected
by a non combustible guard or expanded metal giving an annular air gap of at least 25mm.
Where the fl ue discharge pipe passes through a wall containing cavity insulation, a non combustible sleeve must
be fi tted. Additionally a gap of 25mm between the sleeve and the insulation should be provided by cutting
back the insulation or packing loose fi ll bead insulation with mineral fi bre. Where the fl ue pipe is run
through an unheated roof space it should be insulated with non combustible insulating material to prevent
condensation. The fl ue pipe should be supported at intervals of not more than 1.8m and the support
should be preferably below a joint.
3.04.2 Two pipe fl ue system
To determine the maximum length of fl ue and air pipe permissible.
The calculation is based on a standard reference resistance of 1 metre of 80 mm horizontal air intake pipe. For
every confi guration of the two-pipe system all components will have a resistance factor based upon this reference.
(I.e. a 90 degree bend fi tted in the fl ue line would attract a resistance factor equivalent to 2.5 Metres of horizontal
80mm pipe). This is expressed as
X
metres. Each boiler will have a maximum equivalent length of fl ue/air pipe
and this is shown in the table as
N
metres. Therefore when calculating the proposed fl ue run the equivalent
resistance of every length of pipe and every bend, whether air intake or fl ue discharge is added together to
give an actual total fl ue length. The fi nal fi gure calculated must not exceed the permitted maximum length
(N metres) for each boiler type.
Calculation Routine
1. Identify all the components needed to complete the proposed fl ue/air pipe run.
2. Calculate the sum of all the equivalent lengths (see table at next page).
3. For boilers, which may require a fl ue restrictor, refer to table at page 13 (par. 3.02) to ascertain the correct
size and add this resistance to your total.
4. Check and verify that the total fl ue/air pipe length (fl ow resistance) does not exceed 50 mt. maximum
permitted for
Ferroli F30
.
I M P O RTA N T
: Resistance factors apply to standard férroli components only.