4.4 Technical data table
Table 11- Technical data table
Data
Unit
BLUEHELIX TECH RRT 30 H
BLUEHELIX TECH RRT 34 H
PRODUCT IDENTIFICATION CODES
0T3D3AWA
0T3D4AWA
COUNTRIES OF DESTINATION
IT-ES-RO-PL
GAS CATEGORY
(IT) - II2H3+ (ES) - II2H3B/P (RO) - II2ELw3B/P (PL)
Max. heating capacity
kW
30,6
34,7
Qn
Min. heating capacity
kW
6,4
6,4
Qn
Max. Heat Output in heating (80/60°C)
kW
30,0
34,0
Pn
Min. Heat Output in heating (80/60°C)
kW
6,3
6,3
Pn
Max. Heat Output in heating (50/30°C)
kW
32,5
36,9
Min. Heat Output in heating (50/30°C)
kW
6,9
6,9
Efficiency Pmax (80-60°C)
%
97,9
97,9
Efficiency Pmin (80-60°C)
%
98,0
98,0
Efficiency Pmax (50-30°C)
%
106,1
106,1
Efficiency Pmin (50-30°C)
%
107,5
107,5
Efficiency 30%
%
109,5
109,5
Gas supply pressure G20
mbar
20
20
Max. gas flow G20
m
3
/h
3,24
3,67
Min. gas flow G20
m
3
/h
0,68
0,68
CO
2
- G20
%
9 ±0,8
9 ±0,8
Gas supply pressure G31
mbar
37
37
Max. gas flow G31
kg/h
2.38
2.70
Min. gas flow G31
kg/h
0.50
0.50
CO
2
- G31
%
10 ±0,8
10 ±0,8
NOx emissions class
-
6
6
NOx
Max. working pressure in heating
bar
3.0
3.0
PMS
Min. working pressure in heating
bar
0.8
0.8
Heating adjustment max. temperature
°C
95
95
tmax
Heating water content
liters
4,2
4,2
Heating expansion tank capacity
liters
10
10
Heating expansion tank prefilling pressure
bar
0.8
0.8
Protection rating
IP
IPX4D
IPX4D
Power supply voltage
V/Hz
230V/50Hz
230V/50Hz
Electrical power input
W
80
83
W
Empty weight
kg
31
31
Type of unit
C10-C11-C13-C23-C33-C43-C53-C63-C83-C93--B23-B33