SERIES I3 · Model I3D

Section OEM . ISOLATED SIGNAL CONVERTERS

www.fema.es 

7

‘NORMAL MODE’

When the power supply is connected, the instrument:

• activates the ‘

configuration digits

’, and displays the code for the actual 

configuration (see section 5)
• the instrument is in ‘

normal mode

’ of operation

HOW TO ACCESS THE  ‘CONFIGURATION MODE’ AND THE ‘TOOLS’ MENU

With the instrument in ‘

normal mode

’ of operation, there is access to the 

configuration mode

’ and the ‘

tools

’ menu.

• to access the ‘

configuration mode

’, press the ‘

SQ

’ (

<

) key for 1 second 

(see section 10.2)
• to access the ‘

tools

’ menu, press the ‘

UP

’ (

5

) key for 1 second (see 

section 10.3)

‘ECO’ FUNCTION (‘CONFIGURATION DIGITS’ ARE AUTOMATICALLY 

POWERED OFF)

If there is no interaction from the operator for 60 seconds, the instrument 

powers off the ‘

configuration digits

’. The decimal point remains active 

(flashing), indicating that the instrument is working correctly.

HOW TO POWER ON THE ‘CONFIGURATION DIGITS’ 

To power on the ‘

configuration digits

’, press one of the front keys ‘

SQ

’ 

(

<

) or ‘

UP

’ (

5

). This will power on the ‘

configuration digits

’, and activate 

the ‘

normal mode

’ of operation.

10. Operate the configuration system

CONFIGURATION SYSTEM

The 

Series I3 

of isolated signal converters provide a fast and easy 

configuration system, based on function codes.

‘CONFIGURATION DIGITS’

The instrument provides two numerical leds, to inform about the actual 

state of the instrument, active input signal range, and error codes (see 

section 15).

CONFIGURATION KEYPAD

The configuration keypad is located inside the instrument, behind the 

removable  front  cover.  To  access  the  configuration  keypad,  remove 

the  input signal terminal, and open the front cover (see section 9). The 

instrument allows to password lock the keypad functions, by activating 

an access code (‘

password

’ function) (see section 10.4).

10.1.  ‘Normal mode’ of operation

HOW TO ACCESS THE ‘CONFIGURATION MODE’

With the instrument in ‘

normal mode

’ of operation (see section 10.1), 

press for 1 second the ‘

SQ

’  (

<

)  key.  The  horizontal  leds  light  from 

bottom to top. When the upper led lights, the instrument activates the 

configuration mode

’.

If the key is released before activating the ‘

configuration mode

’, 

the horizontal leds light downwards from top to bottom, and 

the instrument returns to ‘

normal mode

’ of operation.

Inside the ‘

configuration mode

’ the decimal point is not active.

Inside the ‘

configuration mode

’, the ‘

configuration digits

’ display the code 

of the active configuration (see section 5). Press the ‘

UP

’ (

5

) key to 

increase the code.

• press once to increase the value in +1
• maintain the key pressed to automatically increase the value

When the desired code is reached, press the ‘

SQ

’ (

<

) key. The leds light 

a  round  shape  while  new  configuration  is  stored,  and  the  instrument 

returns to ‘

normal mode

’ of operation.

When exiting the ‘

configuration mode

’ without changes (‘

rollback

’ 

activation, selection of inactive codes, etc), the horizontal leds 

light down from top to bottom, and the instrument returns to 

normal mode

’ of operation.

‘ROLLBACK’ FUNCTION

If there is no interaction from the operator for 60 seconds, the instrument 

exits the ‘

configuration mode

’ and returns to ‘

normal mode

’ of operation, 

discarding changes.

10.2.  ‘Configuration mode’

Summary of Contents for I3 Series

Page 1: ...SERIES I3 Model I3D USER S MANUAL ISOLATED SIGNAL DUPLICATOR Section OEM 5577r03 Process 0 10Vdc Process 4 20mA OEM YOURCONVERTER APPLICATIONS www fema es Duplicator Process Double...

Page 2: ...3 7 Technical specifications 3 8 Connections and dimensions mm inch 4 9 Access the Configuration system 6 10 Operate theconfiguration system 7 10 1 Normal mode of operation 7 10 2 Configuration mode 7...

Page 3: ...mA active max 20 5mA min 3mA maximum load 400Ohm passive 4 20mA output 4 20mA passive max 30Vdc on terminals OUTPUT SIGNAL2 active 4 20mA output 4 20mA active max 20 5mA min 3mA maximum load 400Ohm pa...

Page 4: ...on device Use time lag fuse with value 250 mA for voltages 50Vac dc 400 mA for voltages 50Vac dc fuse output 4 20mA passive current out output 4 20mA current in output 4 20mA active current out POWER...

Page 5: ...c The instrument has two outputs output1 is fixed to 4 20 mA active and passive output2 is fixed to 4 20 mA active and passive To select the active or passive mA versions at the input and output signa...

Page 6: ...operations must be performed by qualified operators When correctly connected the input signal terminal prevents the front cover from opening ACCESS THE CONFIGURATION SYSTEM Step numbers as referenced...

Page 7: ...eypad is located inside the instrument behind the removable front cover To access the configuration keypad remove the input signal terminal and open the front cover see section 9 The instrument allows...

Page 8: ...and return to the Force high Fh menu entry Table 6 Tools menu UP Press UP 5 for 1 second to access the tools menu Force Low Force high Exit 9 Operate theconfiguration system cont HOWTO BLOCK ACCESSTO...

Page 9: ...rovalves together with signal and or control cables Before proceeding to the power connection verify that the voltage level available matches the power levels indicated in the label on the instrument...

Page 10: ...fixed to 3mA Possible shortcircuit at input Possible open circuit at input E4 Overload at the 4 20mA input The input signal detected is higher than 90mA The instrument self protection has opened the c...

Page 11: ...SERIES I3 Model I3D Section OEM ISOLATED SIGNAL CONVERTERS www fema es 11 Notes...

Page 12: ......

Reviews: