Section OEM . ISOLATED SIGNAL CONVERTERS
3
Table 2
|
Input and output signals - Configuration codes
Code
Input signal
Output 1
Output 2
10
4/20 mA
4/20 mA
4/20 mA
11
0/10 Vdc
4/20 mA
4/20 mA
12-14
[no function assigned]
15
Function ‘
password
’
16
Reset to default factory parameters
17
Firmware version
18
Working mode (see section 10.5)
19
[no function assigned]
---
Exit the menu without saving changes
5. Configuration codes
To activate the desired input signal range, activate the range configuration
code (see Table 2) into ‘
configuration mode
’ (see section 10.2). See
INPUT SIGNAL RANGES
process
4/20 mA, 0/10 Vdc
type of signal
active and passive, the instrument provides
excitation voltage to power the transducer.
excitation voltage
+15 Vdc, max. 25 mA, shortcircuit protected
input impedance (mA)
variable impedance, voltage drop on terminals <1.2 Vdc
input impedance (Vdc)
1 MOhm
maximum oversignal
*
25 mA for mA
25 Vdc for Vdc
*
‘maximum oversignal’ is the maximum signal accepted by the instrument. Higher signal
values may cause instrument damage. Lower values are non destructive but may be out
of accuracy specifications.
ACCURACY AT 25 ºC
0.5 % F.S. for mA, 0.3 % F.S. for Vdc
THERMAL DRIFT
<100 ppm/º (F.S.)
STEP RESPONSE
0 to 99 % of signal
<200 mSec. in ‘
Mode 1
’, <550 mSec. in ‘
Mode 2
’
OUTPUT SIGNAL 1
active 4/20 mA output
4/20 mA active, max. 20.5 mA, min. 3 mA,
maximum load < 400 Ohm
passive 4/20 mA output
4/20 mA passive, max. 30 Vdc on terminals
OUTPUT SIGNAL 2
active 4/20 mA output
4/20 mA active, max. 20.5 mA, min. 3 mA,
maximum load < 400 Ohm
passive 4/20 mA output
4/20 mA passive, max. 30 Vdc on terminals
CONFIGURATION
key pad
2 keys
display
2 digits, 7 segments, 5 mm height, red color
POWER SUPPLY
voltage range
24 to 240 Vac/dc ±10 %, isolated
AC frequency
45 to 65 Hz
consumption
<4.0 W
power wires
1 mm
2
to 2.5 mm
2
(AWG17 to AWG14)
overvoltage category
2
ISOLATION 4 WAYS
between all circuits
2300 Veff (60 seconds)
except for output 1 - output 2 1500 Vdc (60 seconds)
ENVIRONMENTAL
IP protection
IP30
impact protection
IK06
operation temperature
0 to +50 ºC
storage temperature
-20 to +70 ºC
‘warm-up’ time
15 minutes
humidity
0 to 95% non condensing
altitude
up to 2000 meters
MECHANICAL
size
106 x 108 x 22.5 mm
mounting
standard DIN rail (35 x 7.5 mm)
connections
plug-in screw terminal (pitch 5.08 mm)
housing material
polyamide V0
weight
<150 grams
packaging
120 x 115 x 30 mm, cardboard
Codes with ‘
no function assigned
’ will display message ‘
nA
’
indicating the code is ‘
not available
’.
To select the ‘
active
’ or ‘
passive
’ mA versions at the input and
output signals, configure the connection terminals as explained
To measure process signals and provide dual outputs in standard
4/20 mA signals. Inputs and outputs are isolated.
Single and dual signal retransmission to one or two remote acquisition
devices (HMI, PLC, Scada, ...). Local and remote verification of process
values.
6. Typical applications
7. Technical specifications