FEMA ELECTRÓNICA . SERIES B . Models Bxx-RTU
30
2. Output and control modules
The R1 module provides 1 relay output to install in large for
-
mat industrial meters from Series B. Formats B26 and B46 ac
-
cept up to 3 relays, and formats B24 and B44 accept up to 2
relays.
Configuration is performed from the front keypad of the in
-
strument, by setting the alarm parameters. Check the alarm
menu parameters at the instrument user’s manual for full in
-
formation.
Modules R1 can be provided factory installed into a Series B
instrument, or standalone for delayed installation. No solder
-
ing or special configuration is required. See section
on how
to install output and control modules.
2.1 Module R1
Type of relay
3 contacts (Com, NO, NC)
Max. current
3 A (resistive load)
Voltage
250 Vac continuous
Isolation
3500 Veff
Terminal
plug-in screw clamp, pitch 5.08 mm
Installation allowed at slot 1, slot 2, slot 3
2.2 Module T1
Type of output
transistor
Max. voltage
35 Vdc
Max. current
50 mA
Isolation
3500 Veff, optoisolated
Terminal
plug-in screw clamp, pitch 5.08 mm
Installation allowed at slot 1, slot 2, slot 3
The T1 module provides 1 transistor output to install in large
format industrial meters from Series B. Formats B26 and B46
accept up to 3 transistor outputs, and formats B24 and B44
accept up to 2 transistor outputs.
Configuration is performed from the front keypad of the in
-
strument, by setting the alarm parameters. Check the alarm
menu parameters at the instrument user’s manual for full in
-
formation.
Modules T1 can be provided factory installed into a Series B
instrument, or standalone for delayed installation. No solder
-
ing or special configuration is required. See section
on how
to install output and control modules.
‘com’ (‘A’)
‘NC’ (‘C’)
‘NO’ (‘B’)
Figure 11 - Module ‘R1’ and internal schematic
NOpen
NClosed
Common
C
B
A
Module R1
A
Common
B
NO (Normally Open)
C
NC (Normally Closed)
Figure 12 - Connections for ‘R1’ relay output module
‘B’
‘A’
Figure 13 - Module ‘T1’ and internal schematic
B
Not connected
A
C
B
A
Module T1
A
Emitter
B
Collector
C
Not connected
Figure 14 - Connections for ‘T1’ transistor output module
For more information:
http://fema.es/docs/4326_SERIES-B_OPTIONS_manual_en.pdf