1.- Open the housing to access the instrument internal circuits
2.- Select jumpers on boards «ME», «MP» and «MS»
3.- Connect signal generator to signal input terminals
4.- Connect multimeter to signal output terminals
5.- Power up the instrument as indicated on the label
6.- Generate the low signal level and operate potentiometer
P1 on «ME» until the multimeter shows the desired signal
output
7.- Generate the high signal level and operate potentiometer
P2 on «ME» until the multimeter shows the desired signal
output
8.- Repeat steps 6 to 7 in order to correct deviations and
check the adjust
The CCT has available outputs in voltage and current. Only
one of the outputs can be active. Additional to the standard
0/10 Vdc and 4/20mA outputs, it is possible to reconfigure
the instrument to any of the outputs shown in the table below.
Other mA outputs
(Resistances in Ohms)
OUTPUT R18 R24 R25
0/5mA - - -
100
- - -
0/10mA - - -
49,9 - - -
1/5mA 100K 124
- - -
0/20mA - - -
- - -
24,9
Other Vdc outputs
(Resistances in KOhms)
OUTPUT R29 R30 R31 R32
±10Vdc 49,9 - - -
200 - - -
0/1Vdc - - - - - -
11
100
0/5Vdc - - - - - -
100 100
1/5Vdc - - - 100 66,5 100
Jumpers E and F .- Closed in 4/20 mA output. Open for other outputs
Note .- The symbol «- - -» means «NOT installed»
Placed on the «ME» module are the potentiometers and
jumpers for Zero and Gain adjustment.
Jumper 1 - Closed for Gross Positive Offset
Jumper 2 - Closed for Gross Negative Offset
Jumper A - Closed for Fine Negative Offset
Jumper B - Closed for Maximum GAIN
Jumper C - Closed for Middle GAIN
Jumper B and C - Open for Minimum GAIN
P1 .- Zero Adjust Potentiometer
P2 .- Gain Adjust Potentiometer
Output signal module (MS)
Readjustment procedure
Input signal module (ME)
E F
MS
R30
R29
R18
R31
R32
R24
R25
ABC
ME
P1
P2
1
2
Manufacturer FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 - Barberà del Vallès
BARCELONA - SPAIN
www.fema.es - [email protected]
Products CCT-01, 04, 05, 06, 08, 20, 22, 23, 24, 25, 26, 27, 32, 55I, 55V, 80, 90, 95
The manufacturer declares that the instruments indicated comply
with the directives and rules indicated below.
Electromagnetic compatibility directive 2014/30/EU
Low voltage directive 2014/35/EU
ROHS directive 2015/863/EU
WEEE directive 2012/19/EU
Security rules EN-61010-1
Instrument
Fixed, Permanently connected
Pollution degree 1 and 2 (without condensation)
Isolation
Double (exception for CCT-01 and CCT-08, when
measuring between >300Vac/dc and 600Vac/dc, isolation is BASIC)
Overvoltage category 2
Electromagnetic compatibility rules EN-61326-1
EM environment Industrial
CISPR 11
Instrument Class A & Class B Group 1
For a detailed declaration see document:
www.fema.es/docs/5232_CE-Declaration_CCT_en.pdf
Barberà del Vallès, October 2020
Xavier Juncà - Product Manager
According to directive 2012/19/EU, electronic
equipment must be recycled in a selective and
controlled way at the end of its useful life.
This instrument has been designed and verified conforming to
the 61010-1 CE Security Regulation, for industrial applications.
Installation of this instrument must be performed by qualified
personnel only. This manual contains the appropriate information
for the installation. Using the instrument in ways not specified
by the manufacturer may lead to a reduction of the specified
protection level. Disconnect the instrument from all external
circuits before starting any maintenance and / or installation
action.
The instrument does not have a general switch and will start
operation as soon as power is connected. The instrument
does not have protection fuse, the fuse must be added during
installation.
The instrument is designed to be DIN rail mounted, inside a
cabinet, protected from direct impacts. An appropriate ventilation
of the instrument must be assured. Do not expose the instrument
to excess of humidity. Maintain clean by using a humid rag and
do NOT use abrasive products such as alcohols, solvents, etc.
General recommendations for electrical installations apply, and
for proper functionality we recommend : if possible, install the
instrument far from electrical noise or magnetic field generators
such as power relays, electrical motors, speed variators, ... If
possible, do not install along the same conduits power cables
(power, motor controllers, electrovalves, ...) together with
signal and/or control cables. Before proceeding to the power
connection, verify that the voltage level available matches the
power levels indicated in the label on the instrument. In case of
fire, disconnect the instrument from the power line, fire alarm
according to local rules, disconnect the air conditioning, attack
fire with carbonic snow, never with water.
Precautions on installation