CE Declaration of conformity

1.- Open the housing to access the instrument internal circuits

2.-  Select jumpers on boards «ME», «MP» and «MS»

3.-  Connect signal generator to signal input terminals

4.- Connect multimeter to signal output terminals

5.- Power up the instrument as indicated on the label

6.-  Generate the low signal level  and operate potentiometer 

P1 on «ME» until the multimeter shows the desired signal 

output

7.- Generate the high signal level and operate potentiometer  

P2 on «ME» until the multimeter shows the desired signal 

output

8.- Repeat steps 6 to 7 in order to correct deviations and 

check the adjust

The CCT has available outputs in voltage and current. Only 

one of the outputs can be active.  Additional to the standard 

0/10 Vdc and 4/20mA outputs, it is possible to reconfigure 

the instrument to any of the outputs shown in the table below.

Other mA outputs 

(Resistances in Ohms)

OUTPUT R18  R24  R25

0/5mA  - - - 

100 

- - -

0/10mA  - - - 

49,9  - - -

1/5mA  100K  124 

- - -

0/20mA  - - - 

- - - 

24,9

Other Vdc outputs

(Resistances in KOhms)

OUTPUT R29  R30  R31  R32

±10Vdc   49,9   - - - 

200  - - -

0/1Vdc  - - -  - - - 

11 

100

0/5Vdc  - - -  - - - 

100  100

1/5Vdc  - - -  100  66,5  100

Jumpers E and F .- Closed in  4/20 mA output. Open for other outputs

Note .- The symbol «- - -» means «NOT  installed»

Placed  on  the  «ME»  module  are  the  potentiometers  and 

jumpers for Zero and Gain adjustment.

Jumper 1 - Closed for Gross Positive Offset

Jumper 2 - Closed for Gross Negative Offset

Jumper A - Closed for Fine Negative Offset

Jumper B - Closed for Maximum GAIN 

Jumper C - Closed for Middle GAIN 

Jumper B and C - Open for Minimum GAIN

P1 .-  Zero Adjust Potentiometer

P2 .-  Gain Adjust Potentiometer

Output signal module (MS)

Readjustment procedure

Input signal module (ME)

E F

MS

R30

R29

R18

R31

R32

R24

R25

ABC

ME

P1

P2

1

2

Manufacturer  FEMA ELECTRÓNICA, S.A.

 

 

Altimira 14 - Pol. Ind. Santiga

 

 

E08210 - Barberà del Vallès 

 

 

BARCELONA  - SPAIN

 

 

www.fema.es - [email protected]

Products  CCT-01, 04, 05, 06, 08, 20, 22, 23, 24, 25, 26, 27, 32, 55I, 55V, 80, 90, 95

The manufacturer declares that the instruments indicated comply 

with the directives and rules indicated below.

Electromagnetic compatibility directive 2014/30/EU

 

Low voltage directive 2014/35/EU

 

ROHS directive 2015/863/EU

 

WEEE directive 2012/19/EU

Security rules EN-61010-1

Instrument  

Fixed, Permanently connected

 

Pollution degree 1 and 2 (without condensation) 

 

Isolation  

Double (exception for CCT-01 and CCT-08, when 

measuring between >300Vac/dc and 600Vac/dc, isolation is BASIC)

 

Overvoltage category 2

Electromagnetic compatibility rules EN-61326-1

EM environment Industrial 

CISPR 11  

Instrument Class A & Class B Group 1

For a detailed declaration see document:

 

www.fema.es/docs/5232_CE-Declaration_CCT_en.pdf
Barberà del Vallès, October 2020

 

Xavier Juncà - Product Manager

According  to  directive  2012/19/EU,  electronic 

equipment must be recycled in a selective and 

controlled way at the end of its useful life.

This instrument has been designed and verified conforming to 

the 61010-1 CE Security Regulation, for industrial applications. 

Installation  of  this  instrument  must  be  performed  by  qualified 

personnel only. This manual contains the appropriate information 

for the installation. Using the instrument in ways not specified 

by  the  manufacturer  may  lead  to  a  reduction  of  the  specified 

protection level. Disconnect the instrument from all external 

circuits  before  starting  any  maintenance  and  /  or  installation 

action.
The instrument does not have a general switch and will start 

operation as soon as power is connected. The instrument 

does not have protection fuse, the fuse must be added during 

installation.
The instrument is designed to be DIN rail mounted, inside a 

cabinet, protected from direct impacts. An appropriate ventilation 

of the instrument must be assured. Do not expose the instrument 

to excess of humidity. Maintain clean by using a humid rag and 

do NOT use abrasive products such as alcohols, solvents, etc. 

General recommendations for electrical installations apply, and 

for proper functionality we recommend : if possible, install the 

instrument far from electrical noise or magnetic field generators 

such as power relays, electrical motors, speed variators, ... If 

possible, do not install along the same conduits power cables 

(power,  motor  controllers,  electrovalves,  ...)  together  with 

signal  and/or  control  cables.  Before  proceeding  to  the  power 

connection, verify that the voltage level available matches the 

power levels indicated in the label on the instrument. In case of 

fire,  disconnect  the  instrument  from  the  power  line,  fire  alarm 

according to local rules, disconnect the air conditioning, attack 

fire with carbonic snow, never with water.

Precautions on installation