User’s Manual CCT-05
FEMA ELECTRÓNICA - Page 3
Frequency Signals
up to 40 Khz
CCT-05
Signal converter for frequency signals. Internal jumper selection for 5 different ranges of measure, ranging from 0/40 Hz up
to 0/40 Khz. Accepts PNP, NPN, Namur and sinusoidal signal types. Provides two types of excitation voltages for transduc
-
ers, 24 Vdc for PNP and NPN types, and 8,2 Vdc for NAMUR types.
Configure the desired frequency input range and sensor type by selecting the appropriate jumpers on «MP» module, as
shown on the tables below:
INPUT RANGE SELECTION
MP
3 2 1
PT2
7
8
9
10
PT1
4 5 6
PT1 - Fine Gain Adjustment. (Additional P2 potentiom
-
eter on input module ME).
PT2 - Trigger Adjustment. Is the voltage level at which the
input signal is recognized to be as logic ‘1’ or logic ‘0’. It
can be set empirically operating on potentiometer PT2.
0/22.5-40 KHz
1,6
0/12.5-22.5 KHz
1,5
0/7-12.5 KHz
1,4
0/4-7 KHz
1
0/2.25-4 KHz
2,6
0/1.25-2.25 KHz
2,5
0/700-1250 Hz
2,4
0/400-700 Hz
2
0/225-400 Hz
3,6
0/125-225 Hz
3,5
0/70-125 Hz
3,4
0/40-70 Hz
3
SENSOR
JUMPER
CONNECTIONS
«MP»
Push-Pull (3 wires)
10
3,5,6
NPN-PNP (3 wires)
10
3,5,6
NPN (open collector)
10,7
5,6
PNP (open collector)
10,8
5,6
NAMUR
10,9
4,5
Vac<100V
10
5,6
Vac>100V
---
5,6
RANGE
JUMPER
«MP»
RANGE
JUMPER
«MP»
CONNECTIONS
Power
Fuse
Switch
Sinusoidal
-
+
+
-
NPN, PNP
-
+
Namur
-
+
Voltage
output
Current
output
+
-
-
+
The CCT converters allow different power modules in AC and DC. The instrument does not have internal protection fuse.
Following is a recommendation on value and type of fuse for each power module available.
Fuses
Ref.
Power
Fuse Recommended
«0»
230 Vac 50/60 Hz
50 mA Time Lag
«1»
115 Vac 50/60 Hz
100 mA Time Lag
«2»
24 Vac 50/60 Hz
300 mA Time Lag
«3»
48 Vac 50/60 Hz
150 mA Time Lag
«6»
24 Vdc
300 mA Fast Fuse