Table 4.4-3 :Detailed Pin Function Of COM Port On IVGM

15

16

Make sure Meter & CT are connected between house loads and grid, and follow the Smart Meter 

direction sign on CT, refer to Figure 4.4-4.

Hybrid solar inverter   

Hybrid solar inverter  

Position

1

2

3

4

5

6

7

8

Note

Function

485_A2

485_B2

485_A3

485_B3

485_A3

485_B3

RY_4

RY_5

RS485-2 For Meter 

RS485-3 For Remote Monitor

Figure 4.4-4 Smart meter connection

Inverter side

Grid side

4.5 DRMS Connection

DRMS(Demand response enabling device) is used for Australia and New Zealand installation 
(also used as remote shutdown function in European countries), in compliance with Australia and 
New Zealand safety requirements( or European countries).  Inverter integrates control logic and 
provides an interface for DRMS.  The DRMS is not provided by inverter manufacturer.  Detailed 
connection of DRMS & Remote Shutdown are shown below:

Step 1. 

Screw this plate off from the inverter. See Figure 4.6-1.

Figure 4.5-1 DRMS interface

\

Step 2. 

Plug out the RJ45 terminal and dismantle the resistor on it. Plug the resistor out, leave 

the RJ45 terminal for next step.

Figure 4.5-2 operating steps

P3

GN

P2

BN-WH

P1

BN

P8

ORG-WH

P4

BU-WH

P7

ORG

P6

GN-WH

P5

BU

P2

BN-WH

P1

BN

P1

P8

P8

P1

IVGM side

Meter side

Note

The cable should be made refer to Figure 4.4-3

Figure 4.4-3 Smart meter cable

Summary of Contents for IVGM4648

Page 1: ...Hybrid solar inverter 358 010244 02 IVGM4648 5048 ...

Page 2: ...RICAL CONNECTION 4 1 PV Connection 4 2 Battery Connection 4 3 On Grid Back Up Connection 4 4 Smart Meter CT Connection 4 5 DRMS Connection 4 6 Lithium Battery Communication 4 7 Installation of WiFi module 4 8 Wiring System 5 Display and operation 5 1 Operation and Display Panel 5 2 LCD Display Icons 5 3 Base information Page 6 Warning Code Table 7 Troubleshooting 8 Appendix 2 2 3 4 5 5 6 6 8 9 9 1...

Page 3: ...n explosion Please strictly follow installation procedure when you want to disconnect AC or DC terminals Please refer to Installation section of this manual for the details Grounding instructions this inverter should be connected to a permanent grounded wiring system Be sure to comply with local requirements and regulation to install this inverter Never cause AC output and DC input short circuited...

Page 4: ...pe Make life full of hope Mode 3 When grid fails the system automatically switches to Back Up mode The Back Up load can be supported by PV and battery Mode 4 There is no PV the battery is low and the battery is charged through the grid Make life full of hope Make life full of hope 03 04 1 Figure 2 2 2 Inverter dimensions 1 Inverter Indicators 2 LCD display 3 Button 4 Battery connection port 5 PV i...

Page 5: ...ansion Bolts Meter CT 4 7 8 3 3 Installation Environment Choose a dry clean and tidy place convenient for installation Ambient temperature range 25 60 Relative humidity 0 100 non condensed Install in a well ventilated place No flammable or explosive materials close to inverter The AC overvoltage category of inverter is category III Maximum altitude 2000m 1 2 3 4 5 6 7 8 2 pairs Figure 3 1 1 Packin...

Page 6: ... direct sunlight or badweather like snow rain lightning etc 3 4 Mounting The inverter is suitable for mounting on concrete or other non combustible surface only Step 1 Please use the mounting bracket as a template to drill 4 holes in the right positions 10mm in diameter and 80mm in depth Use M8 expansion bolts in accessory box and fix the mounting With a 12mm drill bracket onto the wall tightly Th...

Page 7: ...p 1 Prepare PV positive and negative power cables Figure 4 1 1 pv cables and pv plugs Step 2 Connect PV cables to PV connectors See Figure 4 1 2 Figure 4 1 2 PV cables to PV connectors PV cables must be tightly crimped into the connectors For Amphenol connector the limit buckle cannot be pressed There will be a click sound if connectors are inserted correctly into PV plugs NOTE Step 3 Screw the ca...

Page 8: ...are shown as below Battery Terminal Cable Figure 4 3 1 Install AC cables for the inverter Don t connect the PE wire wrong Table 4 3 1 Recommended table of AC circuit breakers INVERTER MODEL AC BREAKER SPECIFIFICATION IVGM4648 5048 40A 230V 2P The absence of AC breaker on back up side will lead to inverter damage if an electrical short circuit happens on back up side NOTE 1 On the AC side the indiv...

Page 9: ...lar inverter Hybrid solar inverter RUN COM R P Figure 4 3 6 Install ac connection terminals Table 4 4 1 Smart Meter LED Indications STATUS OFF ON Blinking Run Green Com Red R P Red Red The instrument is not running Negative power The instrument is running normally The instrument is in communication status The instrument is not communicating Negative value indicator lamp Positive power NO Function ...

Page 10: ... remote shutdown function in European countries in compliance with Australia and New Zealand safety requirements or European countries Inverter integrates control logic and provides an interface for DRMS The DRMS is not provided by inverter manufacturer Detailed connection of DRMS Remote Shutdown are shown below Step 1 Screw this plate off from the inverter See Figure 4 6 1 Figure 4 5 1 DRMS inter...

Page 11: ... white Orange Green white Blue Blue white Green Brown white Brown Function VCC COM GND RS485 B1 RS485 A1 CANL1 CANH1 Hybrid solar inverter Hybrid solar inverter Make life full of hope Figure 4 5 5 RJ45 interface Table 4 6 1 Port pin allocation table Function DRM1 5 DRM2 6 DRM3 7 DRM4 8 REFGEN COM DRMO Step 3 2 For Remote Shutdown Run the cable through the steel plate Then wire from pins 5 and 6 Ta...

Page 12: ...UP or DOWN button as below page you can see the parameters of SOC battery pack units and other informations in the communication system LCD will be rolled these parameters or informations automatically 3 Configure battery type to lithium battery on the app And then LCD will show you Li icon Rated Output frequency 50Hz Battery Type Lithium batt When it displays b50 means BMS doesn t allow inverter ...

Page 13: ...P L1 L2 L3 kWh VA Hz 888 OUTPUTBATBMS L1 L2 L3 kWh VA Hz 888 88ERROR S M L3 L2 L1 METER PV1 PV2 Hold on the ESC button last for 3S to turn off the inveter Hold on the ENTER button last for 3S to turn on the inveter Indicates Lithium battery type Indicates communication is built between inverter and battery 5 2 LCD Display Icons Indicates load level by 1 25 26 50 51 75 and 76 100 Hybrid solar inver...

Page 14: ...age The base information Indicates communication is built between inverter and meter 54 0V 40A CPU software version is 1100 CPU software version Hybrid solar inverter Hybrid solar inverter PV1 PV1 PV2 Pv2 450V PV1 450V PV2 PV1 Pv2 ...

Page 15: ...rn to repair center Leakage current sensor failed 39 Hybrid solar inverter Hybrid solar inverter 7 Troubleshooting This chapter describes the fault alarm and fault code for quick troubleshooting Table 7 1 Fault code PV voltage is too high Over current happen at PV port Battery voltage is too high Over current happen at Battery Abnormal LLC Over current happen at Buckboost Reduce the number of Pv m...

Page 16: ...start the unit if the error happens again please return to repair center Restart the unit if the error happens again please return to repair center Restart the unit if the error happens again please return to repair center Restart the unit if the error happens again please return to repair center 42 43 44 45 46 47 48 49 50 51 52 Appendix Model IVGM5048 Battery Voltage Range Max charging and discha...

Page 17: ... Style Warranty Grid Regulation Safety Regulation EMC Net Weight Gross Weight Product Dimension Package Dimension General Data 4600VA 4600W 5000VA 5000W 25 C 60 C 45 Derating IP65 100 Nature 2000m RS232 RS485 CAN RS485 WiFi GPRS LCD LED Wall mounted 10 years VDE AR N 4105 G99 1 EN50549 1 CEI 0 21 AS 4777 2 NRS 097 2 1 IEC 62109 1 2 IEC 62040 1 EN61000 6 1 EN61000 6 3 Features Support WiFi for mobi...

Reviews: