11.5 Output, Signal Shape
The following signal shapes may be selected for the outputs:
DIP
USB
Output, signal shape
OFF
Presence
Continuous signal output
(factory defaults)
ON
Pulse
Pulse output
On
Continuous output turned on
Off
Continuous output turned off
General Fault Output for collective message
To adjust the output modes listed above the direction logic of the VEK MNE2 may not be enabled! I.e.
you must select OFF on DIP-switch Dir Mode and. in the service program.
11.6 Invert Output Signal Behavior
Inverted or non-inverted signal output may be selected for all output modes. This enables open-circuit or
closed-circuit-principle for the relays.
DIP
USB
OFF
Not Inverted Not inverted signal output (open-circuit-principle)
ON
Inverted
Inverted signal output (closed-circuit-principle)
The service tool can show a detailed representation of the currently used relay's operating principle
(open-circuit or closed circuit)!
11.7 Loop Error Behavior (Error Mode)
When Error mode is selected In the settings, it specifies the behavior of the loop channel when a loop fault
occurs and what condition the hardware output assumes.
DIP
USB
Output signal for a Loop Error
Covered same as for the covered loop
(factory defaults)
Free
same as for the free loop
Loop Fault
Only with the check box selected in the service program (factory default), the errors
associated with this loop channel are passed on. The field Error Mode displays Ac-
tive. Otherwise, Inactive Is displayed.
Adjusting
If the check box is checked, the time during the frequency adjustment will be consid-
ered in addition as error condition of the loop. In the factory defaults, the check box
is not checked.
The settings for behavior on loop error can only be changed in the service program!